Field note

Two Full Load Amp Numbers, and Which One Goes in the Drive

Every drive job carries two full load amp numbers for the same motor. One comes from the NEC motor tables and the other comes off the motor’s nameplate, and on a lot of drawings they sit a few lines apart without anybody saying which one is for what. They do different jobs. Mixing them up does not usually cause trouble on the day of startup, which is why it survives, and it can quietly leave a motor without the protection everybody assumed it had.

The table number sizes the wiring

The table number is NEC Table 430.250, the full load current for three phase motors by horsepower and voltage. A 100 HP motor at 460 volts is 124 amps in that table, whatever motor is actually bolted to the base. The code uses that value on purpose for conductor ampacity and for short circuit and ground fault protection, because those have to be sized before anybody knows exactly which motor will be installed, and they have to stay right when the motor gets replaced with a different make.

A drive changes part of that picture. The conductors feeding the drive are sized at 125 percent of the drive’s rated input current, not from the motor table, because the drive is what the supply sees. On the output side, the motor table and the drive’s own markings still govern. None of that has anything to do with what you type into the drive.

The nameplate number goes in the drive

On most installations the drive is the motor overload. The code allows that when the drive is marked as providing motor overload protection, and when it does, no separate overload relay is needed. The drive works that protection out from the motor full load amps you enter during commissioning, and overload protection is set from the nameplate current of the motor you actually have, never from the table.

Use the nameplate value for the voltage the motor is actually wired for. A dual voltage motor marked 50/25 amps at 230/460 volts and wired for 460 gets 25 amps entered, not 50.

Enter a number that is too high and the drive lets the motor carry more current than the windings were built for, with no trip and no alarm, and the cost shows up years later as insulation that failed early. Enter a number that is too low and the drive trips on overload during normal running, which at least gets noticed, though usually what gets done is somebody raising the setting until the trips stop, which lands you back in the first case.

Do not assume the nameplate will come in under the table, either. Some premium efficiency motors carry a nameplate full load amps above the Table 430.250 value for their horsepower, because of how they are designed to get their efficiency. If that nameplate current is above the drive’s continuous output rating, the drive is too small for that motor even though the horsepower matches, and it needs the next frame up. The drive protects and sizes on current. Horsepower is just how motors get ordered.

The motor that changes behind the drive

Where this tends to go wrong is not the original startup. It is the motor replacement 3 or 10 years later, when a failed motor gets swapped for whatever was on the shelf or whatever the supplier had, the leads get landed, the drive gets reset, and the line runs. Nothing about the drive told anybody that it is now protecting a motor it has never met.

That swap is about to get more common in one horsepower band. ODP, TEFC, and explosion proof motors from 100 to 250 HP manufactured on or after June 1, 2027 have to meet NEMA Premium 4 instead of NEMA Premium. Motors built before that date can still be sold, but over the next few years a replacement in that size range is going to be a different design than the one that failed, with different losses, different current, and typically lower slip, which means a slightly higher full load speed.

Those designs also tend to draw more current when started across the line, enough that NEMA added Design BE and Design CE to cover them, and starters, breakers, and conductors on across the line circuits may need a second look. Behind a drive, inrush is not the issue, since the drive brings the motor up on a ramp. The issue is that every motor value in the drive belongs to the old motor.

So when a motor gets replaced behind an existing drive, whatever the efficiency class, treat it like a small commissioning job:

  1. Enter the new nameplate data: horsepower or kilowatts, voltage for the connection used, full load amps, rated speed, and frequency.
  2. Check the new full load amps against the drive’s continuous output rating before anything else.
  3. Run the motor identification run again, so the drive’s motor model matches the motor that is actually there. Sensorless vector and direct torque control depend on that model, and an old one gives poor speed regulation and torque ripple on the new motor.
  4. Confirm the overload settings came along with the new data, since some drives handle the overload level as a separate parameter.
  5. Take a new parameter backup, so the next restore does not put the old motor’s values back in.

The ID run carries the same cautions it always does. Assume the motor can turn even on a stationary ID run, and do not treat the direction it turns during the ID run as the correct process direction. Check rotation separately, uncoupled if you can.

Keep both numbers on the drawing

None of this means the table number is wrong. It is the right number for the wiring, the short circuit protection, and the drawing, and it should stay there. The nameplate number belongs in the drive and in the commissioning record, and when the motor changes, it changes. A one line that shows both, labeled, saves the next person from guessing.

Nameplate entry and the ID run are part of the first power up sequence in the VFD Commissioning Guide and the VFD Pre-Startup Checklist. Taking that backup after a motor swap is covered in Keypad Backups, Memory Modules, and Software Clones. The full commissioning sequence is in Before the First Fault, and if your crew swaps motors without touching the keypad, that is what the training is for.

Frequently Asked Questions

Should I use nameplate FLA or the NEC table FLA in a VFD?

Use the nameplate full load amps for the voltage connection you are actually running. The drive uses that number for motor overload protection, and overload protection is set from the nameplate. The NEC Table 430.250 value is for sizing conductors and short circuit and ground fault protection.

What happens if the motor FLA in the drive is set too high?

The drive lets the motor draw more current than its windings were built for without tripping, so the motor runs hot and the insulation ages early. Nothing alarms, which is why this one tends to go unnoticed until the motor fails.

Can the motor nameplate FLA be higher than the NEC table value?

Yes. Some premium efficiency motors have a nameplate full load amps above the table value for their horsepower. If it is above the drive's continuous output rating, the drive needs to go up a frame even though the horsepower matches.

Do I need to redo the ID run after replacing a motor?

Yes. The ID run measures the actual motor and builds the model the drive uses for sensorless vector and direct torque control. A model from the old motor will not match the new one, and the result is poor speed regulation and torque ripple.

Does the 2027 Premium 4 motor rule affect drives?

Indirectly. From June 1, 2027, ODP, TEFC, and explosion proof motors from 100 to 250 HP have to meet NEMA Premium 4. Behind a drive the higher starting current does not matter, but a replacement motor will have different nameplate data and typically lower slip, so the drive needs the new data and a new ID run.

The annual report: The State of the VFD 2026

Nineteen drive brands assessed, thirteen scored on what they will actually put on the public record. Free, in a Plant Edition for specification work and a Channel Edition for quoting.

Get the report

Wayward Leaders® is a veteran-owned VFD training practice. We teach maintenance teams and plant electricians to install, commission, and troubleshoot variable frequency drives correctly.

Every class ends with a scored competency assessment. The plant gets a way to prove what each technician can do, not a roster of who sat in the room.

The instruction is field-trained. It is drawn from nearly 8,000 VFD, power, and motor documents and from more than 750 commissioned drives captured through personal field experience and data collection. Carl Lee Tolbert, PhD, CMRP, and ATD Master Trainer™, leads it. He has delivered more than 5,000 hours of VFD instruction across 30 years and trained 8,000 industrial professionals, from International Paper to the U.S. Navy.

The premise is simple: VFDs do not fail. Installations fail them. The curriculum is built backward from that.

Installation, commissioning, troubleshooting, and fault diagnosis guides are published openly at waywardleaders.com.