Field note

Where the 1600 Volt Number Comes From

There is a line that turns up in a lot of motor specs, and this month I read it in two public design standards that bidders still price against: inverter duty motors shall meet NEMA MG-1 Part 31, 1600 V peak. It reads as conservative, it gets copied from one job to the next, and nobody questions it because the standard is named right beside it. Part 31 does not contain that number. It contains a multiplier, and the multiplier gives a different answer for every voltage class you buy motors in.

What Part 31 actually asks for

Part 31 sets the insulation withstand for definite purpose inverter fed motors at 3.1 times the motor’s rated line to line voltage, at rise times of 0.1 microsecond or longer. The requirement moves with the motor, so a 230 V motor and a 575 V motor are not held to the same peak, and one flat number cannot be right for both of them.

Motor rated voltagePart 31 peak (3.1 times rated)Against a flat 1600 V spec
208 V645 Vabout 2.5 times what the standard asks
230 V713 Vabout 2.2 times what the standard asks
460 V1426 Vclears it by 174 V
575 V1783 Vshort by about 183 V

Run the multiplier backward and 1600 V is what Part 31 would ask of a motor rated about 516 V. That makes it a fair shelf number for 460 V motors on a 480 V system, and nothing more. 1600 V is a real winding rating that motor makers build to and drive makers publish against, which is how it got close enough to the standard to be mistaken for it.

The two ways of being wrong do not cost the same. On a 208 or 230 V motor, the flat figure asks for more than double what the standard requires, which narrows the motors a bidder can offer and pays for margin nobody needed. One of the specs I read applies it to every drive installation in the building, small 208 V motors included. On a 575 V motor the flat figure runs the other way, and a 1600 V winding sits about 183 V under the Part 31 line. The spec that looked conservative is the one that lets an underrated motor through, and that is the direction that costs a motor.

Why the peak matters in the first place

A drive on a 480 V supply rectifies to a DC bus of about 650 VDC, and every PWM pulse leaves the output terminals at that full bus voltage in a fraction of a microsecond. The motor cable behaves like a transmission line. When the pulse reaches the motor, which has much higher impedance than the cable, it reflects and adds to itself, and the peak at the motor terminals can climb to roughly twice the bus. On standard drives with 200 to 300 feet of cable, 1200 to 1600 V at the motor terminals is a common reading. The mechanism, and what it does to a motor over time, is worked through in Reflected Wave and Long Motor Leads.

That puts the reflected peak on an ordinary 480 V job right on top of the 1426 V that Part 31 sets for a 460 V motor, which is why the multiplier was written the way it was. A 575 V system puts the bus near 815 VDC and every number above scales up with it, and that is the system where a flat 1600 V winding has the least room.

The cable length table is already built on the motor rating

Rockwell’s cable length tables for the PowerFlex drives are organized the same way Part 31 is. The columns are motor winding insulation ratings, 1000 V, 1200 V, 1488 V and 1600 V, and 1488 is 3.1 times 480. Rockwell’s own note on that column says an inverter duty motor is typically 1488 V and to ask the motor maker whether it meets MG-1 Part 31. Carrier frequency shows up in those tables as a row label, 2/4 kHz, while the columns you read across are all about the motor.

The spread across a single row is the part worth teaching. A PowerFlex 4M, 7.5 kW at 400 V, with no reactor or filter, is allowed 25 feet of motor cable on a 1000 V winding, 450 feet on a 1200 V winding, and 1200 feet on a 1488 V winding. Same drive, same carrier, same cable, and the allowed run went from 25 feet to 1200 because of what was printed on the motor nameplate. The 1600 V column on that row also reads 1200 feet, so on that drive the extra 112 V of winding rating buys no extra cable at all.

So the motor is often the cheapest lever on a long run. A reactor or filter bolted to the drive output is how you protect a motor that cannot take the peak, and on the runs that need one it is money well spent. Picking a motor that can take the peak at the voltage class it will actually see, and then reading the drive maker’s table at that rating, tells you how far you get before anything else has to be bought. The cable, shield and accessory decisions that sit alongside that choice are in the VFD Installation Guide.

What the spec line should say instead

The fix is small. Write the requirement against the motor’s own rated voltage, so a 460 V motor is held to 1426 V and a 575 V motor to 1783 V, and confirm the number with the motor maker rather than assuming it from the word inverter on the data sheet. Then take that rating to the drive maker’s cable length table for the run you actually have, and let the table decide whether the output needs a reactor or a filter. If a flat number has to go on the page for some reason, it belongs next to a voltage class, and 1600 V belongs next to 460 V and nowhere else.

Checking the nameplate against the run before the motor is ordered is the same discipline as the rest of the work in the VFD Maintenance and Reliability Guide, and the full treatment of insulation, cable and commissioning is in Before the First Fault. If your crew is specifying motors for drives without reading the drive maker’s table at the motor’s real rating, that is what the training is for.

Frequently Asked Questions

Does NEMA MG-1 Part 31 require 1600 V insulation on inverter duty motors?

No. Part 31 sets the withstand at 3.1 times the motor's rated line to line voltage, with rise times of 0.1 microsecond or longer. For a 460 V motor that works out to 1426 V peak, so a 1600 V winding clears it, but the standard itself never names 1600 V.

Is a 1600 V inverter duty motor good enough on a 575 V drive?

Not by Part 31. A 575 V motor is held to 1783 V peak, and a 1600 V winding falls about 183 V short. Ask the motor maker for the actual peak withstand at that voltage and check it against the drive maker's cable length table before the motor is ordered.

Why do drive cable length tables list 1488 V?

Because 1488 V is 3.1 times 480 V, the Part 31 number applied to a 480 V system. Rockwell's tables use it as one of the winding insulation columns and describe it as the typical inverter duty rating.

Does carrier frequency set my maximum cable length?

In the Rockwell tables, carrier frequency is a row label and the allowed length is read across columns of motor winding insulation rating. On a PowerFlex 4M at 7.5 kW and 400 V, moving from a 1000 V winding to a 1488 V winding takes the limit from 25 feet to 1200 feet on the same carrier setting.

Will an output reactor fix a long run to an underrated motor?

It reduces the peak without removing it. On a 460 V system with 200 feet of cable, a spike around 1200 V typically comes down to roughly 800 to 900 V with a reactor, and reactors are generally effective out to about 250 feet. Past that, a dV/dt or sine wave filter, a better rated motor, or both are the usual answer, and the drive maker's table at the motor's real rating is where to start.

The annual report: The State of the VFD 2026

Nineteen drive brands assessed, thirteen scored on what they will actually put on the public record. Free, in a Plant Edition for specification work and a Channel Edition for quoting.

Get the report

Wayward Leaders® is a veteran-owned VFD training practice. We teach maintenance teams and plant electricians to install, commission, and troubleshoot variable frequency drives correctly.

Every class ends with a scored competency assessment. The plant gets a way to prove what each technician can do, not a roster of who sat in the room.

The instruction is field-trained. It is drawn from nearly 8,000 VFD, power, and motor documents and from more than 750 commissioned drives captured through personal field experience and data collection. Carl Lee Tolbert, PhD, CMRP, and ATD Master Trainer™, leads it. He has delivered more than 5,000 hours of VFD instruction across 30 years and trained 8,000 industrial professionals, from International Paper to the U.S. Navy.

The premise is simple: VFDs do not fail. Installations fail them. The curriculum is built backward from that.

Installation, commissioning, troubleshooting, and fault diagnosis guides are published openly at waywardleaders.com.