A single phase to 3 phase converter for a motor comes in four forms: a variable frequency drive, a rotary phase converter, a static phase converter, or a digital phase converter. For one motor, I would start with the drive, because it builds balanced three-phase, ramps the motor up gently, and gives you speed control along the way. Sizing is where those jobs go wrong. At 230 V, among the makers who publish a single-phase rating, a three-phase drive fed from single-phase delivers somewhere between about 20% and 57% of its three-phase rating, depending on the brand, the frame, and whether a choke or reactor is fitted, and a drive whose maker publishes no number does not quietly deliver some value inside that band, it simply has no supported single-phase rating. A shop with several motors, a welder, or a compressor that starts against a loaded head is better served by a rotary or digital converter. A static converter leaves the motor with about half to two-thirds of its horsepower, which limits it to light loads. Before any of that, though, the supply voltage decides which of these answers you are even working with, so the guide starts there.
Start with the supply voltage
Single-phase comes in three voltage classes, and each one leads to a different conversation with the drive maker.
120 V single-phase
A small group of drives takes 120 V single-phase and puts out 230 V three-phase, so a 230 V motor can run from a 120 V branch circuit that meets the drive’s input and protection requirements. These are mostly 1 HP and under, with a few models reaching about 1.5 HP, and they come from a limited set of brands with fewer features and less performance than the drive lines built for plant work. They show up most often on home shop retrofits, the lathe or mill conversion boards people post online, and for that job they are a reasonable fit. They are not a path to anything bigger, and they are rated for 120 V input from the factory, so the derating question below does not apply to them.
240 V single-phase
This is the common case, whether it is a farm, a rural shop, or a building with single-phase service, and it is where the makers publish the most guidance. Native single-phase drives cover the small sizes, and above that you are derating a three-phase drive on the maker’s published single-phase rating. Most of this guide is about the 240 V class, and the derating tables below are 230 V figures unless they say otherwise.
460 V and 480 V single-phase
The 460 V side splits into two different jobs, a 460 V motor on 240 V single-phase service and a 480 V single-phase service feeding a 460 V motor, and few drive makers publish any guidance for the second one. The default this guide uses everywhere applies here with more force, so assume single-phase input will damage a three-phase drive unless the maker says otherwise in writing for that model, and get the maker’s listing position in writing at the same time, because an inspector can reject the job on listing alone. Both jobs get their own section further down, after the derating physics that explains why they are hard.
Can a VFD convert single-phase to three-phase?
Yes. The drive rectifies whatever comes in to DC, holds that on a bank of capacitors, and builds new three-phase on the output. Because the same electronics build every output leg, the three voltages are balanced with each other, which a rotary converter’s generated leg never quite manages. The output is pulse width modulated rather than a smooth sine wave, so an old motor without inverter-duty insulation, or a well pump at the end of a long lead, still needs the same attention it would on any drive. The open question on any single-phase job is how much current the drive can deliver while it does the conversion.
On 240 V: single-phase input drives versus derating a three-phase drive
Some drives are built for single-phase input, and for those the nameplate rating holds. The native single-phase models I work with stop at about 3 HP at 230 V, and Yaskawa’s GA500 goes to 5 HP on single-phase 200 V input.
Above that size you are derating a three-phase drive, and the makers publish different numbers for it.
| Drive | Single-phase rating, as a share of the three-phase amp or HP rating |
|---|---|
| Rockwell PowerFlex 523/525 | 35% of the three-phase rating |
| AutomationDirect GS20, 230 V models | 50%, shown in brackets in the rating table |
| Yaskawa GA800, 230 V | About 20% of normal duty HP bare, about 50% with Yaskawa’s listed reactor |
| Yaskawa E7, P7, F7 (older, out of production) | Published model by model, DC link choke required on 18 kW and smaller |
| ABB ACS580, 230 V | Separate single-phase table, about 37% to 57% by frame, most frames near half |
| WEG CFW11 HIR versions, 230 V only | Separate single-phase table for special versions of the three-phase models |
ABB shows how much the number moves inside one product line. For its older ACS550 at 230 V, ABB published a flat 50% derate, and for the ACS580 it says that rule no longer applies and publishes a separate single-phase table with its own output and input currents for each frame. A 5 HP motor lands on the 031A frame, a 10 HP drive on three-phase, rated 30.8 A three-phase and 15.2 A single-phase, about 49%. A 10 HP motor lands on the 059A frame, a 20 HP drive on three-phase, rated 59.4 A three-phase and 28 A single-phase, about 47%, and the next frame up, the 075A, carries the same 28 A single-phase rating, so stepping up one frame buys nothing on single-phase. Among the small frames, the 07A5 and 10A6 reach 56% and 57%, while the 017A and 024A just above them drop to about 40%. A percentage taken from one frame will not carry to the next.
Yaskawa’s GA800 table is written in horsepower. Its model 2030 is a 10 HP drive on three-phase, a 2 HP drive on single-phase with no reactor, and a 5 HP drive on single-phase with the reactor Yaskawa lists for it. If the table lists a reactor, the single-phase rating does not exist without it.
The manuals are not always consistent with themselves either. The GS20 manual gives bracketed single-phase ratings for its 230 V three-phase models, then warns in the wiring section against connecting single-phase power to a three-phase model, and also says not to put single-phase on the 460 V and 575 V models at all. When a manual contradicts itself like that, the maker’s application engineers are the ones to settle it before the drive is bought.
My default is to assume single-phase input will damage a three-phase drive unless the maker says otherwise in writing for that model. When the technical data for the exact drive on the wall does list a single-phase rating, I size from that line, and when the manual says nothing about single-phase, I pick a different drive. The common advice to double the drive is a guess that comes up short on several of the drives above, since a PowerFlex 525 at 35% needs about 2.9 times the motor current and a GA800 without its reactor needs about 5 times the motor horsepower.
Factory products exist for the larger single-phase loads, and the ones below are aimed at irrigation and pumping. Danfoss builds a single-phase input VLT AQUA Drive from 1.5 to 30 HP at 230 V and 10 to 50 HP at 480 V, aimed at irrigation and lift stations. ABB’s ACS580 3R irrigation drive package carries single-phase 230 V ratings from 10 to 50 HP. Yaskawa’s Single Phase Converter is a companion front end that feeds DC to a matched Yaskawa drive, up to 60 HP at 230 V and 125 HP at 460 V, and it comes packaged with the iQpump1000 in a NEMA 3R enclosure for outdoor pumping.
A worked example on 240 V
Take a 5 HP, 230 V motor with a 15.2 A nameplate, which matches the NEC Table 430.250 value for that size. Drives are sized from the nameplate amps, or from the service factor amps if the motor runs into its service factor. On a PowerFlex 525 at 35%, the drive needs at least 15.2 / 0.35 = 43.4 A of three-phase rating, which lands on the 25B-B048, a 48.3 A drive rated 15 HP normal duty, so a 15 HP drive runs a 5 HP motor. On a GS20 at 50% it needs at least 30.4 A. On an ACS580, ABB’s single-phase table names the drive directly as the 031A frame, a 10 HP three-phase drive, so the three brands put three different drives on the same motor.
The wire comes next, and it is sized from the drive’s single-phase input current, which runs well above the motor current. ABB lists 30.4 A single-phase input for that 031A frame, twice its 15.2 A output, so the input conductors need at least 30.4 x 1.25 = 38 A of ampacity before any adjustment for temperature or bundling, and the breaker or fuse has to stay within the maximum ABB lists for the drive.
The single-phase penalty sits on top of everything else that sizes a drive. Ambient temperature at the drive, cable length, altitude, carrier frequency, and the load itself all apply the same way they would on a three-phase job, so I run those through the VFD Selection and Sizing Guide first and then size against the maker’s single-phase rating.
Why the drive gets derated
A three-phase rectifier charges the DC bus six times per cycle, so on a 60 Hz supply the bus ripples at 360 Hz with shallow dips between peaks. On single-phase input only 2 of the 3 input legs carry current, the bus charges twice per cycle, and the ripple drops to 120 Hz, which leaves the capacitors carrying the motor for most of every half cycle. They run hotter as a result, and heat is what wears out a capacitor.
The input side carries its share of that stress, since all of the input current now goes through the diodes in the 2 working legs. ABB’s single-phase table shows input current at about 1.4 to 2.2 times the output current depending on the frame, and Yaskawa’s training on its older E7, P7, and F7 drives, now out of production but still the clearest published explanation of the physics, puts input current at about twice the motor current with input power factor around 0.7.
Output voltage comes down as well. On those same E7, P7, and F7 drives, Yaskawa specifies single-phase input at 240 V or 480 V, plus 10% and minus 5%, which is tighter than its three-phase tolerance, and expects about 207 V at the motor with 228 V coming in. The bus sags further as load climbs, so the motor sees less voltage the harder it works. For a job that needs full horsepower at base speed on a low supply, Yaskawa suggests a 208 V motor, and on those drives it limits overload on single-phase to 120% of the single-phase rating, for starting only. Other drives will differ, which is one more reason to read the single-phase section for the exact model.
460 V motors and 480 V single-phase service
First, the terms. Utilities call the supply 480 V, motor nameplates say 460 V, and drive makers label the same class 460 V or 480 V depending on the brand, so a Yaskawa “460 V” drive and a Danfoss “480 V” drive belong to the same class. With that settled, a single-phase 460 V question is really one of two jobs.
Case A: 240 V single-phase service, 460 V motor
This is the common farm and shop job. An ordinary drive with a diode rectifier cannot put out more voltage than it takes in, so a drive on 240 V single-phase cannot run a 460 V motor directly. In order, the options are these.
- If the motor is dual voltage, rewire it for 230 V and buy a drive with a published 230 V single-phase rating. This is the best-supported answer by a wide margin, and the worked examples in this guide show what it costs.
- For a 460 V only motor, consider a different motor first.
- A purpose-built phase-converting drive that boosts the voltage. Phase Technologies describes its 1LH line as phase converting and voltage doubling, with an active front end, so it can run a 460 V motor from a 230 V source without a transformer. Ask for the listing on the exact model.
- A step-up transformer, keeping in mind that a transformer changes voltage and does nothing about phase. A 240 V to 480 V single-phase transformer ahead of a drive moves you from Case A to Case B, so you still need a drive with a published 480 V single-phase rating, and the 240 V service still carries the full single-phase current plus the transformer’s inrush. People buy the transformer and think the job is done.
- A phase converter feeding a standard drive, covered under Case B.
A 230 V drive feeding a 230 to 460 V transformer on its output is a common field improvisation. It belongs on a job only with the drive maker’s written approval, using a transformer rated for drive duty and kept within that maker’s limits.
Case B: 480 V single-phase service, 460 V motor
This one is less common, but it is real on irrigation services. Because the voltage matches, people assume any 480 V drive will do. A matching nameplate voltage does not create a single-phase rating, and the failure on this job is the same two-leg diode current and 120 Hz bus ripple as on 240 V, not low voltage.
On 480 V, the first answer is a product built and listed for this exact job. A listing is what the inspector, the insurer, and the warranty all lean on, and a one-off arrangement has none of that behind it. Years ago I built an external pre-charge design so ABB ACS600 drives could run on 460 V single-phase for mining customers. It worked, and it kept working until ABB decided it would no longer warranty the non-standard design. A setup the drive maker has not listed or approved lasts only as long as the maker is willing to stand behind it.
Here are the routes, sorted by the kind of answer each one is.
| Route | Options | Rating basis | Listing at 480 V single-phase | Main caveat |
|---|---|---|---|---|
| Single-phase input drive | Danfoss single-phase input VLT AQUA, 10 to 50 HP; Phase Technologies phase-converting drives | Published single-phase rating, no derate | Danfoss: UL listed. Phase Technologies: ask | Order the single-phase input variant. AQUA is a pump and fan drive. Larger footprint |
| Matched front end plus drive | Yaskawa Single Phase Converter with a matched Yaskawa drive, up to 125 HP at 460 V | Rating of the matched package | Ask Yaskawa | Not permission to feed a bare 480 V GA800 from two legs. Extra cabinet |
| Derated three-phase drive with published guidance | ABB 580 series; certain Schneider ATV320 and ATV630 catalog numbers | The maker’s 480 V single-phase table | ABB says it offers no UL listed single-phase solution at 480 V. Schneider: ask | Heavy oversize. Specific catalog numbers only |
| External DC bus supply | Bonitron into a drive with DC bus terminals | The approved DC-fed configuration | Bonitron’s unit is UL listed; Schneider calls the pairing with its ATV320 untested and unlisted | Fans, regen, and DC mode, covered below |
| Converter plus standard drive | Digital (Phase Perfect) or rotary converter feeding a normally sized 480 V drive | Converter sizing plus a normal drive | Phase Perfect: ETL listed to UL 61800-5-1 | Both makers must accept it. The idler starts first |
| Converter only, fixed frequency | Phase Perfect 480 V, rotary | Converter sizing | Converter’s own listing | No speed control. The right answer for CNC cabinets and several machines |
| Legacy | Yaskawa E7, P7, F7 | Model by model table | Not applicable | Out of production. Existing installations only |
Only a few products are built for this job, and everything else is either a heavy derate or a combination the drive maker may not stand behind.
Danfoss builds its single-phase input VLT AQUA Drive as a UL listed phase-converting drive, from 10 to 50 HP at 480 V, aimed at irrigation and lift stations. Phase Technologies’ Phase Perfect digital converters are ETL listed to UL 61800-5-1 and turn 480 V single-phase into balanced three-phase for whatever is downstream, and the same company makes phase-converting drives that take 240 V or 480 V single-phase in. Those products are aimed squarely at irrigation and other rural loads with no three-phase on the pole, and they come from a smaller field than the major drive lines, so before specifying one I would ask the supplier for field history in a climate like yours, the warranty and service terms, and the physical footprint, since these packages run larger than a standard drive of the same rating.
Yaskawa’s Single Phase Converter deserves its own mention, because it is the drive maker’s version of the DC bus supply idea covered below. It takes single-phase in and makes DC for a matched Yaskawa drive, it runs up to 125 HP at 460 V and 60 HP at 230 V, and Yaskawa pairs it with its iQpump1000 in NEMA 3R configured packages built for outdoor irrigation and well pumping. Because Yaskawa builds both halves, the question of whether the drive maker stands behind the combination is already answered for the combinations Yaskawa offers. It is not permission to feed a bare 480 V GA800 from two legs, and the GA800 single-phase table I checked is the 240 V one, so ask Yaskawa directly about any 480 V model.
Schneider rates certain ATV320 and ATV630 catalog numbers for 480 V single-phase supply. That is a rating on specific three-phase catalog numbers, not a single-phase product family, so there is no separate order code to hunt for.
ABB’s 480 V single-phase note for its 580 series sizes the drive by DC bus capacitance and lands on drives roughly 2 to 5 times the motor’s full-load current, comparing the drive’s current rating to the motor’s. The oversize gets worse as the motor gets bigger, which is the opposite of what most people expect. A 10 HP motor lands on the 052A, a 40 HP drive at about 3.7 times the motor current, and a 50 HP motor lands on the 302A at about 4.6 times. ABB’s table runs to 60 or 75 HP depending on line voltage and motor efficiency and sends anything larger to the factory, and ABB says in that note that it is written for non-UL listed applications because ABB does not offer a UL listed single-phase solution at 480 V. That growing oversize is the main reason the purpose-built products win at the larger sizes, though the point where they cross over is something to check against real quotes. Yaskawa also published 480 V single-phase ratings for its older E7, P7, and F7 drives, which matter now only for existing installations.
A third-party single-phase DC bus supply such as Bonitron’s is another route, and I have used one on a 460 V single-phase job. It takes the single-phase line, makes the DC bus voltage itself, and feeds a standard three-phase drive through the drive’s DC bus terminals, so the drive’s own rectifier is out of the picture and the rating comes from the approved DC-fed configuration. Bonitron lists its M3712 as UL listed with integrated precharge, which matters, because on some drives the DC terminals sit after the drive’s own soft-charge circuit and an improvised rectifier bridge would dump the line straight into discharged capacitors. The sizes are limited, the drive has to have accessible DC bus terminals, and Bonitron recommends a line reactor ahead of it. Four more limits come with this route. On larger frames the cooling fans or a fan transformer can be fed from the drive’s AC input terminals, so a DC-fed drive can run with dead fans, and that is the most likely field failure on this route. A diode supply cannot take energy back, so an overhauling or high-inertia load needs a braking chopper and resistor on the drive, or the bus climbs until it trips. Some drives need a DC supply mode setting or will fault on missing AC, and the drive’s DC input range has to cover the bus voltage at your actual line voltage. And single-phase input current is still high, so the conductors are still sized from the supply’s single-phase input current.
The drive maker may not have tested or listed the combination either. Schneider says as much about its ATV320, that a properly sized Bonitron unit could work but the pairing is untested and carries no UL listing, so get the drive maker’s position in writing before you build it.
A phase converter feeding a normally sized 480 V drive is the practical path when no maker will approve single-phase into the drive you want. The same conditions apply as anywhere else in this guide: the idler starts before the drive under NEC 455.21, control power comes off the utility legs, and both makers accept the combination in writing. Some converter warranties exclude drive loads, and a loaded start through a rotary converter feeding a drive is where the trips happen.
Some answers are simply no, and naming them saves people from hunting: the GS20 460 V and 575 V models, which AutomationDirect says not to put on single-phase; the PowerFlex 520 series at 480 V until Rockwell confirms that voltage class in writing, since its 35% statement does not split by voltage class; any frame whose manual says nothing about single-phase input; matrix converter drives such as Yaskawa’s U1000; standard active front end drives unless the maker rates them for single-phase; and a static converter ahead of any drive.
Hazards that show up on 480 V single-phase
These matter more at 480 V than anything in the 240 V material.
Source grounding comes first. A 480 V single-phase supply might be a 240/480 V three-wire service with a grounded center tap, two legs of a delta that could be corner grounded or ungrounded, or something else again. Drives ship with EMC filter capacitors and surge protection referenced to ground and set up for a solidly grounded wye, so confirm exactly what the utility delivers and then follow that drive manual’s instructions for that grounding arrangement. Some manuals call for removing EMC or varistor screws and some restrict the arrangement outright, so there is no blanket rule to give here beyond reading the manual for the exact drive.
The input terminals matter more at this size too. At 3 to 5 times oversize you reach large 480 V frames quickly, and on those frames the cooling fans and control transformers can hang off particular input phases, so the wrong pair of legs can mean a dark keypad or a dead fan, not just a phase loss trip. L1 and L2 is common but not universal, so land the legs where the manual says.
Output voltage sags on 480 V the same way it does on 240 V. On the older E7 family, Yaskawa expected about 414 V at the motor with 456 V coming in, falling further under load, and a 460 V pump at full flow draws more current on that lower voltage. Use the exact drive maker’s output voltage figure rather than assuming 480 V in means 460 V at the motor, and log the supply before you size anything, since rural lines often swing outside a plus 10%, minus 5% window.
Power factor and harmonics become a utility question at this size. A single-phase diode front end runs around 0.7 power factor, which at 50 HP is a co-op issue as much as a drive issue. Yaskawa claims 0.99 power factor and under 10% current distortion for its Single Phase Converter at rated load, and other purpose-built products make similar claims that are worth confirming with the maker before they go in a proposal. If a maker’s 480 V single-phase table lists a reactor, the rating does not exist without it.
Wells are a common 480 V single-phase job, and 460 V PWM into a long submersible drop cable is where reflected wave damage happens. Fit the output filter or reactor the drive and pump makers call for at that lead length, and respect the pump maker’s minimum speed for thrust bearing loading.
The other derates still stack on top. A 5 times frame in a hot pump house still takes the ambient, altitude, carrier frequency, and cable length derates from the VFD Selection and Sizing Guide.
Utilities that deliver 480 V single-phase usually do it for irrigation, and they often have their own converter and starting kVA rules, so ask for those specifically, including whether the utility counts the drive, the converter, or both.
A worked example on 460 V
Take a 10 HP, 460 V motor at 14 A, the NEC Table 430.250 value. On ABB’s 480 V single-phase table it lands on the ACS580 052A frame, which is rated 52 A three-phase and sold as a 40 HP drive, about 3.7 times the motor current. ABB’s note sizes that drive by DC bus capacitance and does not list a single-phase input current for it, so the input current, the conductor size, and the breaker all have to come from ABB in writing before the feeder is designed, and the installation still carries no UL listing for single-phase at 480 V.
Now take the same motor if it is a 230/460 V dual voltage motor and rewire it for 230 V, where it draws 28 A. ABB’s 230 V single-phase table puts it on the 059A frame with a published single-phase input current of 55 A, so the conductors need at least 55 x 1.25 = 69 A of ampacity, from a drive whose 230 V single-phase rating is part of the standard listed product. One path ends with a catalog drive on a 240 V service and every number published. The other ends with a 40 HP frame, a listing question, and an input current nobody has written down yet. A PowerFlex 525 at its 35% figure is the wrong tool for the 460 V version of this motor, which is exactly the mistake this section is here to prevent.
Input terminals and input phase loss
The two incoming legs go on the input terminals the manual names for single-phase. ABB says L1 and L2 on the ACS580, Yaskawa said L1 and L2 on its E7 family, and WEG names R/L1 and S/L2 on its HIR versions. On larger frames, cooling fans and control supplies can hang off particular phases, so the wrong pair can leave part of the drive without power.
A three-phase drive has no way of knowing that single-phase input was intended, and it may trip on input phase loss the first time it is powered that way. The makers handle this differently. On its E7, P7, and F7 drives, Yaskawa says input phase loss protection must stay enabled on single-phase, that a phase loss trip generally means the drive is undersized for the load, and that disabling the protection voids the warranty. WEG ships its HIR versions of the CFW11 with the phase loss fault turned off from the factory and specifies 0.70 input power factor on single-phase. ABB’s 580 series monitors DC bus ripple and has a DC voltage stabilizer function for single-phase supplies that ride unsteady.
Given that spread, the phase loss setting should be whatever the maker’s single-phase instructions call for on that drive. When a properly derated drive keeps tripping on phase loss, I check the load current and the incoming voltage before I touch the setting.
VFD vs rotary vs static vs digital converter
| Static | Rotary | Digital | VFD | |
|---|---|---|---|---|
| How it works | Capacitors start the motor, then it runs on 2 legs | An idler motor generates the third leg | Electronics build a balanced third leg | Rectifies to DC and builds new three-phase |
| Motor power | Phase-A-Matic: wye about 2/3 of rated HP, delta about 50% | Full, if the idler is sized right | Full | Full, within the drive’s single-phase rating |
| Voltage balance | Poor | 2% to 5% typical | 2% or better | Balanced |
| Several motors | No | Yes | Yes | Normally one |
| Welder, loaded compressor, CNC | No | Yes, if sized and approved for the machine | Yes, if sized and approved for the machine | Compressor if sized for the start, welder and CNC no |
| Soft start and speed control | No | No | No | Yes |
A CNC machine does not belong on an external drive because its cabinet already holds its own drives and control transformers, and they expect a fixed 60 Hz supply at a fixed voltage.
Rotary phase converter vs VFD
A rotary converter is a three-phase idler motor started from single-phase, with a capacitor panel to tune it, and once the idler is spinning it generates the third leg for as many machines as it is sized to carry. NEC 455.21 requires the rotary converter to be started before the equipment it feeds is powered, so the idler comes up first.
Voltage balance is the weakness. The generated leg never quite matches the two utility legs, and it shifts with load, so the motors on a rotary converter see some voltage unbalance all the time. A voltage unbalance shows up in the motor as a current unbalance about 6 to 10 times larger, and winding temperature rise goes up by about 2 times the square of the percent voltage unbalance, which works out to about 8% at 2% unbalance and about 18% at 3%. NEMA MG1 starts derating motors above 1% voltage unbalance, so the 2% to 5% typical of a rotary converter costs real capacity. For one motor that runs hard, a drive’s balanced output keeps that heat out of the windings.
A rotary converter suits a shop with a mill, a lathe, a saw, and a compressor that never all run at once. When I check one, I measure all three line-to-line voltages at the machine with the machine loaded, since a reading at the converter with nothing running tells you very little. Control power should come from L1 and L2, never from the generated leg.
Phase converter for a welder
A three-phase welder needs a rotary or digital converter sized for it. A drive’s output is meant for motors and will not feed a welder’s transformer, and a static converter will not run a welder at all.
3 phase converter for an air compressor
A compressor that starts against a loaded head needs extra margin from any of these. Phase-A-Matic sizes a rotary idler at 1.5 times the largest motor in general and 2 times for a compressor that starts loaded. A drive can run it too if it is sized for that start, although overload headroom on single-phase input is smaller than on three-phase, and a loaded start is where an undersized drive trips. Before sizing around a loaded start, confirm the unloader works, because a working unloader takes most of that start away. A splash-lubricated reciprocating compressor also has a minimum speed, so I run those at fixed speed with a soft ramp unless the compressor maker gives a minimum I can program.
Static phase converter
A static converter is a capacitor box that starts the motor on a phantom third leg and then drops out, leaving the motor running on 2 legs. Phase-A-Matic, which builds them, says a wye-wound motor delivers about 2/3 of its rated HP that way and a delta-wound motor about 50%, and it lists pumps, blowers, compressors, most hydraulics, CNC machines, welders, motors under 1200 RPM, and three-phase drives among the loads a static converter should not run. A VFD should never be fed from one.
Wire, breaker, and the NEC
The drive’s input conductors are sized at 125% of the drive’s rated input current under NEC 430.122(A). On single-phase input that means the single-phase input current, which runs well above both the three-phase input figure and the motor nameplate, as the worked examples show. Drives that permit single-phase input usually carry a separate single-phase table for input current and protection. If a drive publishes no single-phase input current, there is no proper number to apply 430.122(A) to, and an inspector may require conductors sized from the oversized drive’s three-phase input nameplate, which is one more reason to buy drives with published single-phase tables. Under 430.130, the breaker or fuse also has to stay within the maximum the drive maker lists, which is a ceiling the selection has to respect rather than a sizing method on its own.
Phase converters fall under Article 455. For variable loads, supply conductors are sized at 125% of the converter’s nameplate single-phase input current under 455.6(A)(1), and fixed loads follow a different rule in the same section. Section 455.9 keeps single-phase loads off the manufactured phase. The code text does not settle whether a drive used as a converter counts as a phase converter, so that question goes to your inspector, along with a check of the section numbers against the edition your inspector enforces.
If the circuit feeding the drive is GFCI protected, as more garage, basement, and outdoor circuits now are, expect nuisance trips from the drive’s normal leakage current, and sort out the protection with the inspector before the drive goes in.
Call the co-op first
On a rural single-phase line, the utility decides how big a motor you can run, and its limit is often lower than people expect. As of November 2026, NorthWestern Energy in Montana caps single-phase motors at 10 HP, and MidAmerican in Iowa wants approval for single-phase motors over 5 HP and for converter-fed three-phase motors over 5 HP. Nodak Electric in North Dakota and MiEnergy in Minnesota and Iowa cap 240 V single-phase starting current at 260 A, which by the NEC locked-rotor table is roughly a 7.5 to 10 HP single-phase motor started across the line, and MiEnergy also limits converter-fed motors to 40 HP. These rules change, so confirm them with your utility before you buy, and ask whether it counts a VFD as a converter.
A drive is easier on a line like that because it ramps the motor up and holds starting current to a fraction of what an across-the-line start pulls, which puts far less strain on a weak line than a rotary idler coming on all at once.
The other choice is bringing three-phase in, and the price of that is the reason this question comes up so often. As of November 2026, Xcel Energy’s South Dakota tariff charges $17 a foot for line extension, about $90,000 a mile, and AgWeb reported an Iowa farm near Dallas Center that passed on a $67,000 half mile of line and ran a rotary converter for under $16,000.
What I see go wrong
The mistake I run into first is a three-phase drive wired to two legs and sized off the motor nameplate, as though single-phase input made no difference. A drive set up that way can run fine on a cool morning with a light load and start tripping in July, because it was sized for a supply it never had.
Close behind that is defeating phase loss to clear the trip, when on a drive like Yaskawa’s E7 family the trip usually means too much load for the single-phase rating or a supply voltage problem. Wire and breakers sized off the motor full-load amps come up short for the same reason, since single-phase input current runs up to about twice the motor current on the drives in this guide.
On the output side, I find things hung on a drive that have no business there, such as a control transformer, lights, or a second motor with its own starter. Each motor on a multi-motor drive needs its own overload, and a pressure switch belongs on the drive’s run input, never in the motor leads between the drive and the motor.
Converter jobs tend to go wrong at the idler, when it is too small for a loaded compressor or a welder, at the control circuit, when it is fed from the manufactured leg, and at the utility, when nobody calls the co-op until the lights dim at the neighbor’s place. The supply checks for all of these, including measuring voltage at the drive terminals and catching the 208 V versus 240 V mix-up, are covered in the VFD Installation Guide and the VFD Pre-Startup Checklist.
Related guides and reading
These pick up where this guide stops.
- VFD Pump Control, the application guide for wells, boosters, and lift stations, which covers the pump side of most single-phase irrigation jobs.
- VFD Selection and Sizing Guide, for the installation and application factors that stack on top of any single-phase derate.
- VFD Installation Guide, for supply checks, grounding, and cable.
- VFD Commissioning Guide, for first power-up once the drive is in.
- VFD Troubleshooting Guide, for phase loss, DC bus, and overcurrent trips after start-up.
- VFD Pre-Startup Checklist, the field version of those checks.
- Online start-up courses, one drive per course, filmed uncut on the real drive. The PowerFlex 525 course is filmed on a 120 V single-phase input model.
Summary
A drive will turn single-phase into balanced three-phase at the current its maker publishes for single-phase input, which at 230 V, among the makers who publish a number, runs from about 20% to 57% of the three-phase rating. At 460 V, rewiring a dual voltage motor to 230 V is usually the best answer, and on a true 480 V single-phase service the first answer is a product built and listed for it. I size the drive from the maker’s number with the application factors on top, size the wire from the drive’s single-phase input current, and call the co-op before anything gets ordered. The VFD Selection and Sizing Guide walks through the full sizing method, Before the First Fault covers supply, sizing, and setup in more depth, and the training covers drives on rural and single-phase service for crews who set them up.
Frequently Asked Questions
Can I run a 3-phase VFD on single-phase power?
Yes, if the maker publishes a single-phase rating for that model, and then only up to that rating. At 230 V, among the makers who publish one, it runs from about 20% to 57% of the three-phase rating depending on the brand, the frame, and whether a choke or reactor is fitted. If the manual says nothing about single-phase input, assume it will damage the drive and pick a different one.
How much do I derate a VFD for single-phase input?
Use the maker's table for the exact drive. Rockwell lists 35% for the PowerFlex 525, AutomationDirect shows 50% on its 230 V GS20 models, Yaskawa's GA800 at 230 V is about 20% without its reactor and 50% with it, and ABB's single-phase table for the ACS580 at 230 V runs about 37% to 57% by frame, with most frames near half.
Is a VFD better than a phase converter?
For one motor, usually yes, since the output is balanced, the motor soft starts, and you get speed control. For several machines, a welder, or a CNC machine, a rotary or digital converter sized and approved for the machine is the better fit.
Can I run a 3-phase motor on 120 V single-phase?
Yes, for small motors, with a drive built to take 120 V single-phase and put out 230 V three-phase. These are mostly 1 HP and under, with a few reaching about 1.5 HP, from a limited set of brands, and they suit home shop machines better than plant work.
Can I run a 460 V motor on 240 V single-phase?
Not directly from an ordinary drive, because it cannot put out more voltage than it takes in. If the motor is dual voltage, rewire it for 230 V and use a drive with a published 230 V single-phase rating, which is the best-supported answer. For a 460 V only motor, the options are a different motor, a phase-converting drive built to boost the voltage, or a step-up transformer feeding a drive that has its own published 480 V single-phase rating.
Can I run a 3-phase VFD on 480 V single-phase?
Start with a product built for 480 V single-phase input, such as Danfoss's UL listed single-phase AQUA Drive, Yaskawa's Single Phase Converter packaged with a matched Yaskawa drive, or a Phase Perfect digital converter ahead of a normal drive, and confirm the listing for the exact configuration. Below that are maker sizing notes for unlisted installations, such as ABB's for its 580 series at roughly 2 to 5 times the motor current, and DC bus supplies such as Bonitron's, which the drive maker may not have tested or listed. If the manual publishes no 480 V single-phase rating, assume it will damage the drive.
Can you run a single-phase motor on a VFD?
Not on a standard VFD. Drives are built for three-phase motors, and capacitor-start single-phase motors have a starting switch that does not work at reduced speed. A few small drives make single-phase output for fan and pump motors, though the usual answer is to change the motor to three-phase.
Can I run a welder or air compressor on a phase converter?
A welder needs a rotary or digital converter sized and approved for it. A compressor that starts loaded needs an idler about twice the compressor motor's horsepower on a rotary converter, or a drive sized for the loaded start.
Will my co-op let me run a big motor on single-phase?
Some utilities limit single-phase motors to 5 or 10 HP, or cap starting current at 260 A on a 240 V service. Call before you buy, and ask whether the co-op counts a VFD as a converter and whether a drive's soft start changes the answer.