Starting June 1, 2027, a 100 HP through 250 HP induction motor built in or brought into the United States has to meet a higher efficiency level than the one it meets today. NEMA now calls that level Premium 4. It used to be called Super Premium, and in the rest of the world it goes by IE4. Most of what has been written about the change is about the efficiency tables and what the motor will cost. The part that matters more to the people who wire these motors and keep them running is what a lower loss motor does in the first second after the contactor pulls in.
The efficiency step looks small on paper. A 4 pole, 100 HP enclosed motor goes from 95.4 percent to 96.2 percent. Turn it around and look at the losses instead, and they drop from 4.6 percent of the input to 3.8 percent, which is about 17 percent less heat the motor has to get rid of. A good share of that comes out of the rotor, and a rotor with less resistance in it pulls more current when it is standing still.
What the rule covers and what it leaves alone
The Department of Energy put the rule out in June 2023, built on a joint proposal from the motor manufacturers, the efficiency groups, and the utilities. The date that matters on the plant side is June 1, 2027, because the standard applies to motors manufactured or imported on or after that day. A motor built before then can still be sold and installed, and nothing in the rule makes anybody pull a working motor out of service.
Only one band moves up a tier. Below 100 HP the requirement stays at NEMA Premium, and above 250 HP through 500 HP it stays at NEMA Premium as well. The same rule also brings motors from 500 HP up to 750 HP under the standard for the first time, at the Premium level, and it brings in air over motors, the ones cooled by a fan or blower somewhere else in the equipment, with the 100 to 250 HP air over motors going to Premium 4 along with everything else in that band.
Inverter only motors stay exempt. A motor built to run only on a drive, with no way to start it across the line, is outside the standard. A motor that is rated for drive duty but can also run straight off the line is still covered.
Why a lower loss motor starts harder
This is not a new problem. When premium efficiency motors came in, plants started seeing breakers trip the instant a motor was started, with nothing wrong with the motor or the circuit. The cause sits in the first half cycle. A high efficiency motor has a lower power factor at locked rotor, so the very first peak of current can run as high as 2.8 times the locked rotor current you read on a meter. A thermal magnetic breaker or a fuse rides through that. An instantaneous trip motor circuit protector, which reacts in less than one cycle, sees the peak and opens. Premium 4 pushes the same physics one more step.
The design letter on the motor decides how far. A NEMA Design B motor has a ceiling on locked rotor current, and some manufacturers will build Premium 4 motors that still stay under the Design B ceiling. Others will go to the newer Design BE, or Design CE on the high starting torque side, which NEMA wrote with higher locked rotor limits so the efficiency could be reached. ABB, which builds both kinds, says getting to Premium 4 generally takes a design that draws more inrush, and it still offers designs that hold the old Design B limits. So the answer for any one motor is on its data sheet, and it is not safe to assume it from the motor that is coming out.
What the 2026 Code does with BE and CE motors
The 2026 NEC picked up the new designs in Article 430, and the changes land on the parts of the circuit that see locked rotor current. Conductors for a single BE or CE motor on continuous duty still start at 125 percent of the table full load current, the same as any other motor, but there is now a second check on how hot those conductors get while carrying locked rotor current for 5 seconds. That check can push the wire up a size. There is relief from it when the motor is started on a drive or a reduced voltage starter.
There is also a new table of locked rotor current values for BE and CE motors, and it is the one used to pick the disconnect and the controller. The Code carries a note with it saying that starters and controls tested for Design B, C, or D motors may not have been evaluated at the higher BE and CE currents. The group conductor rule and the disconnect rule both point to the new table, and the short circuit and ground fault protection table was revised for these designs too. All of it applies only where your state or city has adopted the 2026 edition, and that happens on a different schedule in every jurisdiction.
Where the drive fits
A drive never puts the motor’s locked rotor current on the line. It starts the motor at low frequency and low voltage and holds the current to its own overload rating, which is typically 110 percent for 60 seconds on a normal duty drive and 150 percent for 60 seconds on a heavy duty drive. The line side never sees the inrush, the instantaneous trip question goes away, and the locked rotor conductor check has relief written into it for exactly this case. A soft starter also brings the inrush down and gets the same reduced voltage relief, though it does nothing for energy once the motor is up to speed.
That does not make the drive mandatory. A Design B Premium 4 motor started across the line goes into the same bucket the old motor came out of, and plenty of 2027 installs will be exactly that. The trap is the replacement. A 150 HP pump motor that has run for 20 years fails in 2028, the replacement that shows up is a BE, and the starter, the overloads, the motor circuit protector, and the wire were all sized for a Design B. Nobody changed the drawing, and the first start trips the protector.
That replacement is the moment to price a drive instead of a like for like swap. On a variable torque load the drive brings energy savings with it, and on any load it takes the starting current question off the table. If the application is going on a drive anyway, an inverter only motor is outside the efficiency rule altogether, with the catch that it cannot be put on a bypass and run across the line when the drive is down.
What to check before a 100 to 250 HP motor gets ordered after mid 2027
- The design letter on the quote or data sheet: B, BE, or CE.
- Locked rotor amps or the code letter from the new motor’s data sheet, not from the motor coming out.
- How the motor is started today: across the line, wye delta, soft starter, or drive.
- The type of protective device on the circuit and its setting, especially an instantaneous trip motor circuit protector.
- The starter and controller ratings against the BE or CE locked rotor values.
- Which edition of the NEC your inspector is enforcing.
With those on paper you will know before the motor arrives whether it drops in or whether the panel needs work. If the panel needs work, that is when a drive belongs in the comparison, and sizing it for the load you actually have is in the VFD Sizing Guide. What a drive saves on each kind of load is in What a VFD Actually Saves Depends on the Load Behind It, and the longer treatment of starting methods is in Before the First Fault. If your team needs to be able to make this call on their own, that is what the training is for.
Frequently Asked Questions
What is NEMA Premium 4?
It is NEMA's name for the efficiency level that used to be called Super Premium, which matches IE4 internationally. Starting June 1, 2027, the Department of Energy requires it on most general purpose induction motors from 100 HP through 250 HP.
Do I have to replace my existing 100 to 250 HP motors in 2027?
No. The rule applies to motors manufactured or imported on or after June 1, 2027. Motors already in service, and motors built before that date, can stay in service or be sold and installed.
Do Premium 4 motors draw more starting current?
Often, yes. Lower losses usually come with a lower resistance rotor, which pulls more current at standstill, and high efficiency motors also have a higher first cycle peak. Some Premium 4 motors still stay inside the Design B locked rotor limits, and others are built as Design BE or CE with higher limits, so check the data sheet for the motor you are buying.
Does a VFD solve the starting current problem with Premium 4 motors?
Yes. A drive starts the motor at low frequency and voltage and limits current to its overload rating, so the line never sees the motor's locked rotor current. A soft starter also reduces inrush, though it does not bring the energy savings a drive can on a variable torque load.
Are motors used with drives exempt from the 2027 rule?
Only inverter only motors, the ones that cannot be started across the line, are exempt. A motor that is rated for drive duty but can also run straight off the line is still covered by the rule.
Online start-up courses, filmed on real drives
One drive per course, filmed uncut with a clock on screen from first power to a saved backup. The install course is free, and the ABB ACS380 and ACS580 start-up course is open now.