Field note

Shaft Grounding Rings: When You Need One and How to Fit It

The question I get most about grounding rings is which end they go on. The question that matters more is whether the motor needs one yet, because a ring on a motor fed by a pigtailed cable and a painted ground is a part that costs less than the bearing, asked to fix a problem that lives in the cable and the ground. The note a grounding ring cannot outrun a bad install is the why behind that. This note is the how: when to add a ring, where it goes, and how to fit one so it works.

Step 1: fix the return path before you buy anything

Shaft voltage comes from the common mode voltage a drive’s PWM output puts on the motor. That current has to get back to the drive, and proper VFD cable and high frequency grounding are the first defense: the motor cable and shield arrangement the drive maker calls for, a continuous protective ground, and bare metal at every bond. That cuts the uncontrolled current paths and can lower the bearing current a lot. It does not remove every source of shaft voltage, because some of it is coupled capacitively inside the motor no matter how good the cable is. Do the cable right first, then decide on bearing protection separately. The cable procedure is in VFD cable.

Then decide on bearing protection on top of it.

Step 2: decide whether the motor needs a ring

The field consensus for general industrial drive work is 3 layers: proper shielded cable, an insulated bearing, and a shaft grounding ring. How much of that a given motor needs depends on its size and what it drives.

MotorWhat to fitWhy
Smaller motors on short, well terminated runsThe cable first, a ring as cheap insuranceShaft voltage stays low when the return path is good
Up to 100 HP (75 kW) on a driveOne ring, either end, drive end preferredDrains shaft to ground current, and the drive end placement protects the coupling and driven equipment too
Over 100 HP (75 kW)Insulate one bearing, usually the non drive end, and put the ring on the opposite endLarger motors add high frequency circulating current through both bearings, which a ring alone does not stop
Over 500 HP (375 kW)Insulated bearing plus a heavier duty ring series built for large shaftsHigher currents and larger shafts
Medium voltage and large frame motorsEngineered bearing protection specified by the motor makerThe DOE motor tip sheet suggests both bearings insulated plus a shaft grounding brush strapped to the drive case above the 500 frame, but the maker’s arrangement comes first
Motors with both bearings insulatedCheck shaft grounding and the driven equipmentInsulating both ends can push the current out through the coupling and the load instead

The placement rules in that table up to 500 HP are AEGIS’s, the ring maker most people have in their stockroom, and they are a ring maker’s recommendations, not a standard every motor has to meet. If your motor maker publishes its own arrangement, use theirs.

Think about what is on the other end of the shaft. Shaft voltage that is not drained at the motor travels down the shaft into the gearbox, the pump or the fan and can pit those bearings instead, and under some conditions the gears. A ring on the drive end drains it before the coupling. If the motor and the driven machine are coupled solidly and the driven machine has its own ground through piping or oil lines, an insulated coupling or a ring on the driven side may also be needed.

Why big motors need more than a ring

Drive induced bearing current comes in 3 kinds, and a ring only answers some of them. Discharge current, the EDM kind, is the shaft voltage arcing through the bearing’s grease film, and it is what a ring drains away. Rotor ground current runs from the shaft out through the driven machine to ground, and a ring or grounding brush at the motor gives it a shorter path home. Circulating current is the one that changes the answer on big motors: it loops down the shaft, out one bearing, through the frame and back in the other bearing, and a ring at one end does nothing to stop a loop that never leaves the motor. Breaking that loop takes an insulated bearing.

The motor makers draw the line in about the same place. ABB ties circulating current to larger motors, IEC frame 280 and up, which is roughly where 100 HP motors live, and puts an insulated bearing on the non drive end for them. Above about 350 kW it adds a common mode filter at the drive, and on any motor over 30 kW it wants symmetrical shielded cable no matter what else is fitted. Nidec insulates the thrust bearing on its inverter duty vertical motors of 100 HP and up, and it will not warranty the bearings of a vertical motor on a drive without that protection. Vertical pump motors deserve the extra look for that reason.

Step 3: fit the ring

These steps follow AEGIS’s installation practice, where the fibers ride directly on the shaft. Other designs change the prep. Inpro/Seal’s CDR, for one, runs its conductive filaments on a sleeve it supplies, so the filaments contact the sleeve instead of the bare shaft and conductive O rings carry the current to it. Follow the prep for the ring you bought.

  1. Lock out the motor and the drive. Prove zero energy.
  2. Pick the mount. External mounts use a bracket kit bolted to the motor end bracket. Split rings go on without uncoupling the motor. Internal mounts bolt or epoxy to the bearing retainer and need the motor opened. Press fit rings go into a machined bore.
  3. Prepare the shaft. The fibers have to ride on bare, conductive metal. Remove paint, coatings and anything nonconductive where the fibers will contact, with emery cloth or Scotch-Brite. AEGIS calls for a surface finish of 130 microinch Ra or better.
  4. Deal with the keyway. Keyway edges are sharp. Either set the ring position so the fibers ride clear of it, or fill it with a fast curing epoxy putty.
  5. Apply the conductive shaft coating. AEGIS supplies a colloidal silver coating for the contact band and recommends it as best practice. Stir it well, brush on a thin, even coat around the shaft and let it dry tack free, then apply a second coat the same way. The ring can go on once the coating is tack free, but the coating has to cure fully before the motor runs: 16 to 20 hours at room temperature, or about 60 minutes at 200 F, and no hotter than that.
  6. Mount on bare metal. Wherever the ring or its bracket meets the motor, the contact has to be bare metal. Do not use a nonconductive thread locker on the mounting screws, because the screws are part of the ground path. If you use conductive epoxy, use the one the ring maker specifies and let it cure fully before running the motor.
  7. Center the ring. The gap should be even all the way around, with the fibers touching the shaft surface. The fibers are meant to overlap the shaft slightly, not be crushed against it.
  8. Seal it in dirty or wet service. In washdown and severe duty, mount the ring inside the motor or add the seal or slinger the maker offers, because grease and dust packed into the fibers insulate them.
  9. Check the ground path. One meter lead on the ring’s metal frame, the other on the motor frame: AEGIS wants less than 1 ohm. Then check the prepared shaft surface, where it wants less than 2 ohms anywhere you test. Those readings prove the basic installation. They do not prove the ring is draining the high frequency discharges, because an ohmmeter at DC cannot see what happens at the drive’s switching frequencies. That is what Step 4 is for.

Step 4: prove it works

A ring that is installed and a ring that is working are 2 different things, and the best practical way to tell them apart is to measure shaft voltage with the motor running on the drive. It is strong evidence, not a complete measurement of every current path through every bearing, but it is the test that catches most bad installs.

Use an oscilloscope with a shaft voltage probe, a brush tipped probe held against the rotating shaft, with the scope ground on the motor frame. AEGIS’s tester is a 100 MHz scope with a 10 to 1 probe. Take a reading before the ring goes on and after. On a motor that needed it, the waveform changes character: the sharp discharge spikes of the bearing film breaking down go away, and the peak voltage drops well down. Record both readings with the drive frequency and carrier setting, because shaft voltage changes with both.

The shaft is turning while you test, so use a purpose built shaft voltage probe in a secure holder, such as a magnetic base, and keep yourself, the leads and the scope clear of the coupling and any exposed shaft. Never hand hold an ordinary scope probe against a rotating shaft. Look for the repeating discharge spikes in the waveform, not just the peak number.

Test as early as you can in the motor’s life. On a new install, after a motor repair, and after a bearing change are the 3 times AEGIS calls out.

Step 5: keep it working

AEGIS says its ring needs little routine maintenance as long as the shaft surface stays conductive and the fibers stay free of packed grease and dirt, and that a new ring should go on every time the bearings are replaced on an inverter driven motor. Where you can get to the shaft, put a shaft voltage reading on the PM route at the same interval as vibration, and always after a motor repair, a bearing change or any sign of electrical bearing damage. Vibration tells you about bearing damage after it has happened. A rising shaft voltage can warn you that the ring or the return path is slipping, though it is no guarantee you will see it before the bearing does. The VFD Maintenance Guide is where that reading fits in a full program.

Where a ring does not help

A ring gives shaft current a path from the shaft to the motor frame, and it keeps doing that even on a flawed install. What it cannot do is fix the flaws: it does not correct poor protective grounding, a badly terminated cable shield or a drive bonded through paint, and it does not repair a bearing that is already damaged. Those have to be fixed on their own. Pull a failed bearing and look at it before you decide. Frosting and washboard fluting on the races point to electrical discharge, and the fix starts at the cable and the ground, but rule out false brinelling and other mechanical wear first, because vibration in a stopped motor can leave marks that look a lot like fluting. A bearing that failed from lubrication or load needs a different fix, and a ring will not change it. The free First Power course on the online training page covers the cable and grounding side hands on.

Frequently Asked Questions

Which end of the motor does a shaft grounding ring go on?

AEGIS recommends one ring on either end for motors up to 100 HP, with the drive end preferred because it also protects the driven equipment. Over 100 HP, insulate one bearing, usually the non drive end, and put the ring on the opposite end, normally the drive end.

Do I need a shaft grounding ring if I have insulated bearings?

On larger motors, usually yes. An insulated bearing blocks current through that bearing, but the shaft voltage is still there and will find the other bearing or the driven equipment. The ring on the opposite end drains it to the frame. Insulating one end and grounding the other is the standard combination above 100 HP.

How do you install a shaft grounding ring?

Clean the shaft to bare metal where the fibers will ride, apply the conductive shaft coating the ring maker supplies, mount the ring centered on the shaft on bare metal with the maker's brackets, epoxy or press fit, check continuity from the ring to the motor frame, then measure shaft voltage with the motor running to confirm it dropped.

How often should a shaft grounding ring be replaced?

AEGIS says its ring needs no maintenance as long as the shaft stays conductive, and that a new ring should go on whenever the bearings are replaced on an inverter driven motor. A shaft voltage reading on the PM route tells you whether it is still working between bearing changes.

Will a grounding ring fix bearing failures on a VFD motor?

It helps, but it works best with the cable and grounding right first. A ring drains shaft voltage that is already there. If the common mode current has no clean path back to the drive, the ring carries more than it was meant to, and on larger motors circulating current can keep damaging the bearings until one of them is insulated.

Online start-up courses, filmed on real drives

One drive per course, filmed uncut with a clock on screen from first power to a saved backup. The install course is free, and the ABB ACS380 and ACS580 start-up course is open now.

See the online courses

Wayward Leaders® is a veteran-owned VFD training practice. We teach maintenance teams and plant electricians to install, commission, and troubleshoot variable frequency drives correctly.

Every class ends with a scored competency assessment. The plant gets a way to prove what each technician can do, not a roster of who sat in the room.

The instruction is field-trained. It is drawn from nearly 8,000 VFD, power, and motor documents and from more than 750 commissioned drives captured through personal field experience and data collection. Carl Lee Tolbert, PhD, CMRP, and ATD Master Trainer™, leads it. He has delivered more than 5,000 hours of VFD instruction across 30 years and trained 8,000 industrial professionals, from International Paper to the U.S. Navy.

The premise is simple: VFDs do not fail. Installations fail them. The curriculum is built backward from that.

Installation, commissioning, troubleshooting, and fault diagnosis guides are published openly at waywardleaders.com.