The Optidrive E3 has one of the shortest fault lists in the compact drive market, 25 numbered trips, and most of the ones you meet on a running machine are about the supply, the motor cable, the motor, or heat rather than about the drive itself. The rest cover communications, memory, and setup. Two things the manual spreads across different chapters make the drive easy to read: which trips the drive will clear and restart on its own, and what it logged in the seconds before it stopped.
Before you clear anything
The E3 keeps its last 4 trips and a short record of what led into the last one, so a reset does not destroy the history. What it does clear is the active display, and the log holds less than you might expect. Before anyone touches the Stop key, write down the trip, what the motor was doing when it stopped, and what changed recently. Starting, accelerating, running steady, decelerating, and sitting at power up are five different answers, and the log will not tell you which one it was.
Timing narrows the field faster than a meter does. A trip on acceleration points at ramp time, inertia, and current limit. A trip at steady state points at load, cooling, and sizing. A trip on deceleration points at regeneration. A trip at power up points at wiring and the supply.
Isolate the drive and wait the full 10 minutes Invertek specifies before working on it, verify the DC bus is discharged, and match PPE to the arc flash rating. The Stop key does not remove lethal voltage from this drive.
One fault list, two numbering styles
The E3 reports a trip two ways. The keypad shows a short code such as O-I or U-Volt on its 6 digit, 7 segment display. Over Modbus and in the trip log, the same trip is a number from 00 to 51. A technician at the drive reads the display code and a PLC reads the number, so the table below carries both, exactly as page 39 of the manual prints them.
The list is short because the drive is simple. There is no alarm code tier on the E3 and no safe torque off input on the IP20 unit. Every code on this page stops the motor. The drive does give a few warnings before it trips, but they show as flashing segments on the display rather than as codes, which the next section covers.
How the E3 tells you something is wrong
A tripped E3 shows the fault code on its display and stops the output. The motor coasts. The trip clears with the Stop key on the keypad, but only after the cause is gone, and for three trips the drive also enforces its own waiting period.
That waiting period matters. After an output overcurrent (03 or 15) or a motor overload (04), the E3 will not accept a reset until an internal delay has run out. Invertek built it in to let the power devices recover. If you are pressing Stop and nothing happens after an O-I, the drive is not broken, it is making you wait.
Before a trip, the display itself warns you, using the segments of the digits rather than a code. Section 5.7 of the manual lists three patterns. Segments a through f flashing together means overload: motor current is above P-08. Segments a and f flashing alternately means mains loss: the incoming AC has been removed. Segment a flashing alone means fire mode is active. A drive showing the overload pattern is running up its thermal model toward an I.t-trp, and that is worth catching while the motor is still turning.
The quick table
| No. | Display | Description |
|---|---|---|
| 00 | no-Flt | No fault |
| 01 | OI-b | Brake channel overcurrent |
| 02 | OL-br | Brake resistor overload |
| 03 | O-I | Output overcurrent, instantaneous |
| 04 | I.t-trp | Motor thermal overload (I2t) |
| 06 | O-Volt | Overvoltage on DC bus |
| 07 | U-Volt | Undervoltage on DC bus |
| 08 | O-t | Heatsink over temperature |
| 09 | U-t | Under temperature |
| 10 | P-dEF | Factory default parameters loaded |
| 11 | E-trip | External trip |
| 12 | SC-ObS | Optibus comms loss |
| 13 | FLt-dc | DC bus ripple too high |
| 14 | P-LOSS | Input phase loss |
| 15 | h O-I | Output overcurrent, fast hardware trip |
| 16 | th-Flt | Faulty thermistor on heatsink |
| 17 | dAtA-F | Internal memory fault (IO) |
| 18 | 4-20 F | 4 to 20 mA signal lost |
| 19 | dAtA-E | Internal memory fault (DSP) |
| 21 | F-Ptc | Motor PTC thermistor trip |
| 22 | FAN-F | Cooling fan fault, IP66 only |
| 23 | O-hEAt | Drive internal temperature too high |
| 26 | OUT-F | Output fault |
| 41 | AtF-02 | Autotune fault |
| 50 | SC-F01 | Modbus comms loss |
| 51 | SC-F02 | CAN comms loss |
Seven segment displays cannot draw every letter cleanly, so upper and lower case on the drive can look slightly different from print. The fire mode section of the manual also writes a few of these names its own way, Th-FLt, P-Loss, SC-trp, and Out-F among them, and names a phase imbalance trip, Ph-Ib, that does not appear on page 39. The table above is the page 39 form.
The most common E3 call has no trip code at all: the display shows StoP and the motor will not turn. Four things cause most of these. Terminal 1 to terminal 2 is the enable on digital input 1, and the manual says it must still be provided when P-12 is set for keypad, Modbus, or CAN control, so a drive switched to keypad mode with nothing on terminal 2 ignores the Start key. Only P-01 to P-14 show until the access code, 101 by default, is entered in P-14, so a tech who cannot find P-15 or the trip log has not unlocked them. A value in P-10, motor rated speed, switches P-01 and the other speed settings to rpm, so a 60 typed into P-01 afterward means 60 rpm. And a P-15 setting that does not match the wiring diagram for that setting gives a motor that runs only while Start is held, or not at all. Pick the P-15 value and its diagram as a pair.
When the manuals disagree
The E3 has changed under its manuals. The IP20 user guide version 1.05 is written for firmware 3.11, while Invertek’s Advanced Technical Manual, issue 06, is written for firmware 3.08. Invertek’s firmware history adds features along the way: P-30 options at 3.02, new P-15 and P-36 options at 3.05, and more P-15 keypad functions by 3.08. An older drive may not offer the setting a newer manual describes. P00-28 shows the firmware version once P-14 has been unlocked.
Invertek’s own sources also disagree on small things. The user guide says all six segments flash when current is above P-08, while Invertek’s online FAQ describes flashing decimal points. Invertek’s commissioning video says to hold Up, Down, and Stop for a second or so to load defaults, and the guide says more than 2 seconds. When the drive and the paper disagree, read P00-28, use the guide written for that firmware, and believe the drive.
The fault details
03 O-I and 15 h O-I, output overcurrent
What it means. Current on the drive output went past what the power stage will tolerate. Invertek splits it two ways. Fault 03, O-I, is the instantaneous overcurrent that the manual ties to excess load or shock load on the motor. Fault 15, h O-I, is the fast hardware trip, and the manual points it straight at short circuits on the motor and motor cable.
Most likely cause. For O-I, a jam, a seized bearing, a load that slammed instead of settled, or an acceleration ramp in P-03 asking for more current than the inertia allows. For h O-I, a short circuit in the wiring or the motor: a damaged cable, a failed winding, or a strand bridging two lugs in the motor terminal box, the peckerhead.
The fix, in order. Read which of the two you have before anything else, because they send you to different places. On h O-I, isolate, wait out the 10 minutes, disconnect the motor leads at the drive, and megger the cable and the motor phase to ground, T1, T2 and T3 to PE, never through the drive. Use 500 V DC on a motor rated under 240 V, which covers the 230 V E3s, and 1000 V DC on a 400 to 480 V motor, unless the motor manufacturer calls for something else. Under 1 megohm is a fail, 1 to 10 megohms means investigate, usually moisture or tired insulation, and over 10 megohms is generally healthy. The IEEE 43 minimum for a random wound motor is 5 megohms corrected to 40 C, which sits inside that investigate band, and why the 4.4 megohm number is wrong covers how to correct a cold reading. The 3 readings should sit within about 50 percent of each other, and one phase well below the others points at that winding or that conductor. Compare against earlier readings on the same motor if anyone kept them, since a falling trend says more than a single number. Ring the windings phase to phase for resistance balance rather than meggering across them. On O-I, turn the shaft by hand, look at what the load was doing in the instant before the trip, then lengthen P-03 and confirm P-08 matches the motor nameplate.
Worth knowing. Both of these trips carry the built in reset delay, so pressing Stop immediately after the trip does nothing. Wait it out. Resetting into a short as fast as the drive allows is how a repairable drive becomes a replaced one.
When to stop. If h O-I comes back with the motor leads disconnected at the drive terminals, an internal drive problem becomes the strong possibility, and the next step is qualified diagnosis or a call to the supplier rather than more resets.
04 I.t-trp, motor thermal overload
What it means. The drive delivered more than 100 percent of the current set in P-08 for long enough to threaten the motor. This is a thermal model, not an instantaneous trip. The manual’s own example is 150 percent for 60 seconds.
Most likely cause. A genuinely overloaded motor, a wrong value in P-08, or mechanical drag that has been building for months and only now crossed the line.
The fix, in order. Read the motor nameplate and confirm P-08 matches it, since a wrong P-08 causes this trip more often than a bad motor does and costs nothing to check. Then measure the real running current against nameplate and go look at the machine if it is high.
Worth knowing. P-60 holds two settings that decide how this trip behaves. Index 1 retains the overload accumulator through a power cycle when set to 1, which stops a technician from clearing a hot motor’s thermal history by cycling power. Index 2 sets the reaction: 0 trips on I.t-trp, and 1 reduces the current limit to 100 percent of P-08 once the accumulator reaches 90 percent, letting the motor keep turning at reduced torque instead of stopping. The Pump and Fan application presets set index 2 to current limit reduction, while the General preset leaves it at trip. If an E3 on a fan seems to lose torque in August instead of tripping, that is the setting working as designed. The flashing overload segments described above come on while the accumulator is building, before either reaction.
When to stop. A motor whose running current keeps creeping up over weeks deserves a look at the machine and the process. It may be mechanical drag, a process load that changed, or something else, and the drive is giving you the early notice either way.
06 O-Volt, overvoltage on DC bus
What it means. DC bus voltage went above the maximum. On deceleration that means the load is pushing energy back into the bus faster than the drive can absorb it.
Most likely cause. Regeneration on a deceleration ramp that is too short for the inertia. At steady state or at idle, the supply is running high.
The fix, in order. If it trips on deceleration, lengthen P-04 first, which costs nothing and confirms the diagnosis. If the process will not tolerate a longer ramp, the energy needs a path, which on the E3 means an external brake resistor and the brake chopper enabled with P-34. If it trips at steady state, measure the incoming supply against the drive’s tolerance and check the transformer tap.
Worth knowing. Size 1 E3 drives have no brake chopper at all. P-34 is marked not size 1 in the manual. On a frame 1 unit that keeps overvolting on stop, the only tools are a longer ramp, P-05 set to ramp with AC flux braking, or a different drive.
07 U-Volt, undervoltage on DC bus
What it means. The incoming supply is too low to hold the DC bus up.
Most likely cause. Invertek is plain about this one: it trips routinely every time power is removed, so a U-Volt at shutdown is normal. A U-Volt while running is a sag, a soft supply, or a loose connection somewhere in the feed.
The fix, in order. If it happens during running, measure the supply under load rather than at rest, then check every component in the power feed line, as the manual puts it: disconnect, fuses, contactor, and terminals. Torque the line side terminations while you are there.
Worth knowing. P00-12, run time since last trip, ignores undervoltage. The drive does not count a U-Volt as a real trip when it resets that clock, which tells you how Invertek thinks about it. The mains loss segment pattern, a and f flashing alternately, shows the moment incoming AC goes away, which helps separate a supply dropout from a bus that sagged under load.
01 OI-b and 02 OL-br, the brake channel faults
What it means. Fault 01, OI-b, is overcurrent in the brake chopper channel. Fault 02, OL-br, is the drive tripping to protect the brake resistor from overload.
Most likely cause. For OI-b, a shorted or wrongly sized resistor, or damaged resistor wiring. For OL-br, braking too often or too hard for the resistor.
The fix, in order. Check the resistor condition and its connection wiring, which is the manual’s whole instruction for OI-b, and measure its resistance against the minimum the drive allows. For OL-br, look at P-34. Settings 1 and 3 enable the chopper with software protection sized for a 200 W continuous resistor. If the installed resistor is larger and protected by its own thermal switch, settings 2 or 4 drop the software protection, and the external thermal device becomes the protection instead.
When to stop. A resistor sized for the real duty, with protection set to match, that still trips the drive is a resistor or chopper problem.
13 FLt-dc and 14 P-LOSS, the supply trips
What it means. Fault 14, P-LOSS, is input phase loss. Fault 13, FLt-dc, is DC bus ripple that is too high, which is how the drive sees a missing or weak phase. The manual gives both the same remedy.
Most likely cause. A blown input fuse, a loose line side terminal, a failed contactor pole, or a utility imbalance.
The fix, in order. Measure all three phases at the drive input terminals rather than at the disconnect, so the wiring between them is part of the test. Check the input fuses individually.
Worth knowing. This is the trip to understand on a single phase supply. An E3 rated for 3 phase 230 V will run from single phase at 50 percent of its rated output current, which is how the bench unit here runs at 1.15 A. A drive set up that way and loaded past its single phase rating will throw ripple and phase loss trips that are the installation telling the truth, not a fault in the drive. The single phase derate is a sizing decision, and it needs to be made on purpose. P00-18 logs bus ripple at 22 ms intervals before a trip, which shows whether the ripple built under load or arrived with a supply event.
08 O-t, 23 O-hEAt and 09 U-t, temperature
What it means. Fault 08, O-t, is heatsink over temperature. Fault 23, O-hEAt, is the drive’s internal ambient running too hot. Fault 09, U-t, is the opposite problem, the drive is below its minimum operating temperature.
Most likely cause. For O-t and O-hEAt, a hot enclosure, blocked airflow, dirty fins, or a switching frequency set higher than the enclosure can carry. For U-t, an unheated outdoor or cold storage enclosure after a cold night.
The fix, in order. Measure the air at the drive intake with the panel closed, not the room, since a closed panel can run 10 to 20 degrees C hotter than the space around it. Clean the heatsink and confirm the drive has its clearances. Then look at P-17, the maximum effective switching frequency.
Worth knowing. The E3 tries to protect itself before it trips. When the heatsink runs hot, it reduces the switching frequency, and P-17 shows “rEd” when viewed, with the actual reduced value in P00-32. If you see rEd on a drive that has not tripped yet, the cabinet is near its limit. P00-16 and P00-19 log heatsink and internal temperature at 30 second intervals before a trip, which will show you whether the heat built slowly or arrived at once.
11 E-trip and 21 F-Ptc, external and motor thermistor trips
What it means. Fault 11, E-trip, is the external trip input on digital input 3, a normally closed contact that opened. Fault 21, F-Ptc, is a motor PTC thermistor over temperature.
Most likely cause. Something in the interlock chain did exactly what it was installed to do. On many E3 installs that something is a motor thermistor. The manual supports a PTC with a 2.5 kilohm trip level, and wiring one takes two settings: a P-15 macro that assigns input 3 to external trip, and P-47 set to ptc-th.
The fix, in order. Find what opened before clearing anything. If a motor thermistor is wired in, check the motor temperature first, as the manual says, then the thermistor wiring. A cold motor that still trips has a broken wire, a loose terminal, or the wrong P-15 macro or P-47 setting.
Worth knowing. The P-47 setting changes what the display shows. With a plain contact on input 3, an open input shows E-trip. With P-47 set to ptc-th, the same input trips showing ptc-th. A technician who sees ptc-th is looking at a motor thermistor, not a door switch, and should start at the motor.
18 4-20 F, analog signal lost
What it means. An analog input set up for 4 to 20 mA saw its signal fall below 3 mA. The drive trips 500 ms after the signal drops.
Most likely cause. A broken reference wire, a failed transmitter, a loose terminal, or the supply to the transmitter dropping out.
The fix, in order. Measure the signal at the drive terminals rather than at the transmitter so the wire is part of the test. Check the terminal screws. Then confirm P-16 or P-47 matches the signal that is actually wired.
Worth knowing. The input format decides whether a lost signal trips at all. P-16 and P-47 offer t 4-20 and t 20-4, which trip on 4-20 F, and r 4-20 and r 20-4, which keep the drive running at Preset Speed 1 in P-20 when the signal falls below 3 mA. A drive set to an r format that loses its transmitter will sit at P-20 with nothing on the display to say why. Whether that is right depends on the process, so it should be chosen deliberately. A 0 to 20 mA transmitter on an input set for 4 to 20 mA will read as a lost signal every time it sits near zero.
26 OUT-F, output fault
What it means. Something is wrong on the drive output: a phase missing, or motor phase currents that are not balanced.
Most likely cause. A loose or broken motor lead, an open winding, or a contactor or disconnect between the drive and the motor with a bad pole.
The fix, in order. Torque the output terminations at both ends, check any contactor or disconnect between drive and motor, then ring the motor windings phase to phase.
Worth knowing. OUT-F is one of the trips the E3 will auto reset and restart in fire mode, along with O-Volt, U-Volt, h O-I, and O-I. Outside fire mode, it follows the normal P-30 restart rules.
41 AtF-02, autotune fault
What it means. The motor parameters measured by the autotune are not correct.
The fix, in order. Check the motor cable and connections for continuity and confirm all three motor phases are present and balanced, which is the manual’s instruction. Then confirm the nameplate values in P-07, P-08, and P-09 before running the tune again.
50 SC-F01, 51 SC-F02 and 12 SC-ObS, the communication trips
What it means. Fault 50, SC-F01, is Modbus RTU comms loss. Fault 51, SC-F02, is CAN comms loss. Fault 12, SC-ObS, is loss of Optibus, the link between the drive and Invertek’s own keypads, PC tools, and other drives. The display tells you which network dropped before you open anything.
Most likely cause. Cable, connector, termination, or a master that stopped polling. On Modbus, the manual adds a condition that catches people: at least one register has to be polled cyclically inside the timeout set in P-36 index 3.
The fix, in order. Confirm the master is online and actually polling this drive. Check the RJ45 cable and the network wiring. Confirm P-36 index 1 address and index 2 baud rate against the master, and that each drive on the network has its own address. Then look at P-36 index 3 and decide deliberately how long a gap the process can tolerate.
Worth knowing. P-36 index 3 sets both the timeout and what happens when it runs out. Settings shown with a t, such as t 3000, trip the drive with a coast stop. Settings shown with an r, such as r 3000, ramp the motor to a stop without tripping. The choices run from 30 ms to 60 seconds, and 0 disables the check entirely. A drive set to an r value can lose its master and stop with nothing in the trip log, which looks like a mystery stop until somebody reads P-36.
P-63 decides which Modbus messages reset the timeout. At 0, any valid message on the network keeps every drive alive, even messages addressed to another drive. At 1, only messages addressed to this drive count. A drive on a shared RS 485 run that never trips on comms loss, even when its own data has stopped, is usually sitting at P-63 = 0.
10 P-dEF, 16 th-Flt, 17 dAtA-F, 19 dAtA-E and 22 FAN-F, the internal faults
What it means. Fault 10, P-dEF, means factory default parameters were loaded. Fault 16, th-Flt, is a faulty heatsink thermistor. Faults 17 and 19, dAtA-F and dAtA-E, are internal memory faults in the I/O processor and the DSP. Fault 22, FAN-F, is a cooling fan fault, which exists only on IP66 units.
The fix, in order. For P-dEF, reload the saved parameters, assuming someone saved them. Holding Up, Down, and Stop together for more than 2 seconds defaults the drive, so a P-dEF on a drive nobody meant to reset is worth asking about. A reset also may not give you Invertek’s factory values. Invertek’s Advanced Technical Manual says a user default set saved in OptiTools Studio survives the reset, so on a used drive clear the user defaults in Studio first. For dAtA-F and dAtA-E, press Stop, and if the fault persists the drive goes back to the supplier, which is the manual’s whole instruction. For FAN-F, check and replace the fan. For th-Flt, the drive has lost its ability to measure its own heatsink temperature, and that is a service item.
The faults you prevent are the ones you never read
The E3 keeps a small but useful record, and almost nobody opens it. P00-13 holds the 4 most recent trips with a time stamp. Behind that sit five short logs of the values just before the trip: DC bus voltage in P00-15 at 256 ms samples, heatsink temperature in P00-16 at 30 second samples, motor current in P00-17 at 256 ms samples, DC bus ripple in P00-18 at 22 ms samples, and internal drive temperature in P00-19 at 30 second samples. Each holds the 8 most recent values.
That is a 2 second picture of current and bus voltage leading into the trip, which is enough to tell a shock load from a slow climb and a supply sag from a regeneration spike. A U-Volt with a falling bus and flat current is the supply. An O-Volt with the bus climbing while current falls during deceleration is regeneration.
Behind those are the counters, P00-33 through P00-38, which count how many times the drive has seen O-I, overvoltage, undervoltage, heatsink over temperature, brake chopper overcurrent, and O-hEAt over its life. Two other counters, P00-39 and P00-40, count Modbus and CAN errors. A drive that has seen 40 overvoltage trips in a year has been telling somebody about its deceleration ramp for a long time. P00-10 and P00-43 give run time since manufacture and powered time, which help date the problem.
To read them, hold the Navigate key for more than 2 seconds, scroll to P-00, and press Navigate again to step through the read only values, as section 5.4 of the manual describes. P-14 and the access code in P-37, 101 by default, unlock the Extended and Advanced parameter groups, which you need to change settings such as P-30, P-36, or P-60.
Reading and clearing faults
Press Stop to reset a trip once the cause is gone. After O-I, h O-I, or I.t-trp, wait out the built in delay first.
Over Modbus RTU, bit 2 of the control word in holding register 1 resets the active fault. The trip number shows in the high byte of the status word and in its own register, 2016, so a PLC can log the actual code rather than a single tripped bit. Register 2005 adds the state of the digital inputs and outputs, including a flag for each analog input that drops below 3 mA in 4 to 20 mA mode. Read it alongside 2016 and you know whether the enable on DI1 was present when the drive stopped.
Automatic restart lives in P-30 index 1. The default, Edge-r, means the drive will not restart after a power on or reset until digital input 1 is opened and closed again. Auto-0 starts the drive at power on if input 1 is already closed. Auto-1 through Auto-5 give the drive up to 5 restart attempts at 20 second intervals after a trip. When the last attempt fails, the drive trips and waits for a manual reset, and the attempt counter only clears on a power down. Invertek’s own safety section says not to enable automatic reset where it could create a dangerous situation, and a drive that restarts itself is attached to a machine that starts itself.
Fire mode changes all of this. With P-15 set to 15, 16, or 17 and the fire mode input active, the drive ignores the heatsink over and under temperature trips, the heatsink thermistor fault, the external trip, the 4 to 20 mA loss, phase imbalance, input phase loss, communications loss, and the motor overload, and it auto resets and restarts on overvoltage, undervoltage, both overcurrent trips, and the output fault. It runs until it physically cannot, and a drive in fire mode cannot be reset until fire mode is turned off. That is the right behavior for a smoke extract fan and the wrong behavior for anything else, so a fire mode input wired on a process drive is worth a hard look. Segment a flashing alone on the display tells you fire mode is active.
The flashing segments warn whoever is standing at the drive. To warn a PLC or a stack light, use the relay. P-18 assigns the relay output, and setting 5 closes it when motor current passes the threshold in P-19. Setting P-19 a little under the motor rating gives the controller the same overload warning the segments give the operator. Confirm on your own drive how P-19 scales against P-08 before relying on a specific number.
Where this fits
Most of what appears on this page was decided before the drive was first powered: the supply it was fed from, the single phase derate, the cable to the motor, the cabinet it lives in, and the value somebody typed into P-08. The VFD Installation Guide and the VFD Troubleshooting Guide cover the work that keeps those decisions from showing up later as trips.
The same treatment for other platforms is in the ABB Drive Fault Field Guide, the PowerFlex 525 Fault Field Guide, and the Yaskawa Fault Field Guide, and every brand is listed on the guides page. For the competency behind the codes, that is what the VFD training does, and Before the First Fault is the field record the approach came out of.
Fault codes, display strings, parameter references, and behavior on this page are taken from the Invertek Optidrive ODE-3 IP20 User Guide, 82-E3I20-IN version 1.05, and the Optidrive E3 Fieldbus User Guide version 1.02. Confirm against the guide revision that matches the firmware in front of you. Invertek and Optidrive are trademarks of Invertek Drives Ltd, used here for identification.
Frequently Asked Questions
Why won't my Optidrive E3 reset after an O-I trip?
After an output overcurrent (03 or 15) or a motor overload (04), the E3 enforces a built in delay before it will accept a reset, to let the power devices recover. Wait it out, then find the cause before pressing Stop, because resetting into a short damages the drive.
What is the difference between O-I and h O-I on an Optidrive E3?
O-I, fault 03, is instantaneous overcurrent that Invertek ties to excess or shock load on the motor. h O-I, fault 15, is the fast hardware trip that Invertek ties to short circuits on the motor and cable. O-I sends you to the machine and the ramp. h O-I sends you to an insulation test on the cable and motor.
Does the Optidrive E3 have safe torque off?
The IP20 E3 covered in the 82-E3I20-IN user guide has no STO input and no STO fault code. Its stop function does not remove hazardous voltage, so isolation and the 10 minute wait apply before any work.
Does the Optidrive E3 warn before it trips?
Yes, on the display. All six segments a through f flashing together means motor current is above P-08 and the overload model is building. Segments a and f flashing alternately means mains loss. Segment a flashing alone means fire mode is active. For a remote warning, set the relay with P-18 = 5 and a current threshold in P-19.
What do SC-F01, SC-F02 and SC-ObS mean on an Optidrive E3?
They are the three communication trips. SC-F01, fault 50, is Modbus RTU comms loss. SC-F02, fault 51, is CAN comms loss. SC-ObS, fault 12, is loss of Optibus, the link to Invertek keypads, PC tools, and other drives.
Why won't my Optidrive E3 start from the keypad?
Terminal 1 to terminal 2 is the enable on digital input 1, and it must be closed even when P-12 selects keypad, Modbus, or CAN control. Link the terminals or wire a switch, then press Start.
Where does the Optidrive E3 store its fault history?
P00-13 holds the last 4 trips with a time stamp, and P00-15 through P00-19 hold the 8 values of bus voltage, heatsink temperature, motor current, bus ripple, and internal temperature leading up to the last trip. Reach them by holding Navigate for more than 2 seconds and selecting P-00.
Why does my E3 keep tripping on 4-20 F?
The analog input fell below 3 mA for 500 ms, or the input format in P-16 or P-47 does not match the signal wired to it. Measure at the drive terminals, check the screws, and confirm the format. The r formats run at Preset Speed 1 instead of tripping.