Safe Torque Off is one part of a safety function, and its job ends when the drive stops making torque. What the machine does after that depends on what the drive was turning. A big fan keeps spinning for minutes, a loaded incline conveyor runs backward, a hoist drops its load unless a brake catches it, and a pump can be turned backward by the water behind it. The SIL or PL on the drive’s data sheet covers the circuit inside the drive. The switch, the safety relay or safety controller, the wiring, the brake, the stopping time, and the test that proves the whole chain works are all part of the machine’s design.
The safety design of a real machine comes out of that machine’s risk assessment and is work for qualified people. Nothing on this page replaces the safety manual for the drive, option module, and firmware in front of you.
What STO does and what it leaves alone
On most drives, Safe Torque Off blocks the gate signals to the output transistors, in hardware, on two independent channels, and it is switched on by removing 24 V from the inputs, so a broken wire or a dead supply looks the same to the drive as a demand to stop. Once STO is active the drive cannot make torque, whatever the firmware or the keypad says, apart from the residual cases the safety manual lists.
The main circuit and the DC bus stay live while STO is active, so it is no protection against shock. It does not brake the motor, so the motor coasts on whatever inertia it carries. It does not hold a load, so anything with gravity, process pressure, or stored tension behind it can still move. It does nothing about an outside force turning the shaft, such as wind on a fan, water through a pump, or the load on a hoist rope.
Permanent magnet motors carry one of those residual cases. After certain double faults in the output stage, the shaft can make a limited rotation that the safety manual defines, commonly given as up to 180 electrical degrees, which at the shaft is 180 degrees divided by the motor’s pole pairs. That is a real movement of a real machine part, and the figure for your drive and motor comes from its manual.
STO used on its own gives a stop category 0: torque is removed at once, and the machine’s mechanics decide what happens next. SS1 ramps the motor down and then applies STO, a category 1 stop. SS2 ramps down and then holds the motor at a monitored standstill with power still on, a category 2 stop, and drops to STO only if that standstill is violated. An emergency stop has to be category 0 or 1, and the risk assessment decides which.
SS1 comes in two common forms, and the difference matters on every high-inertia load. SS1-t only times the stop. The ramp comes from the drive’s ordinary control, which carries no safety rating, and if that ramp fails, STO fires when the timer runs out and the machine coasts the rest of the way. The SS1-t delay has to be longer than the worst-case ramp time, and a guard lock on a fan or a centrifuge should never release on an SS1-t timer alone. SS1-r watches the ramp itself and drops to STO as soon as the motor stops following it.
What happens on each load when torque goes away
| Load | When torque goes away | What to check |
|---|---|---|
| Centrifugal pump | Stops in seconds on its own, but head or a failed check valve can spin it backward | Check valve condition, isolation valves for any work on the pump, reverse rotation before anyone touches the coupling, generated voltage at the leads on a PM motor |
| Process and induction fans | Coasts for minutes on a heavy wheel | Coast time measured at full speed, guard or door locked until a safety-rated standstill signal, braking resistor sized if a controlled stop is chosen |
| Cooling tower and outdoor fans | Can windmill from draft with the drive off | Mechanical lock or brake for work inside, standstill confirmed at the wheel, since the drive reads zero output with the wheel still turning, generated voltage at the leads on a PM motor |
| Level belt conveyor | Short runs stop quickly, and long or overland conveyors can coast a long way on belt and pulley inertia | Stop time at the worst case, pull cord and guard interlocks, restart prevention |
| Incline or decline conveyor | Load can drive the belt backward or forward | Backstop or holdback, spring-set brake, whether the gearbox back drives |
| Screw conveyor | Stops quickly, and jams store energy in the flight | Energy isolation before the cover comes off, restart prevention |
| Mixer or agitator | Coasts with the batch, and can be turned by the product | Lid or hatch interlock held until standstill, isolation for entry |
| Hoist or crane | Load falls unless a brake holds it | Brake command, brake engagement feedback, proven holding torque, speed monitoring rated for loads that can drive the motor |
| Winder or unwinder | Roll inertia coasts, and web tension stays stored | Setup mode design, tension release before hands go in, direction monitoring |
| Extruder | Screw stops, and pressure and heat remain | Stored melt pressure and barrel heat, pressure relief, barrel guarding |
| Crusher or mill | Very long coast, and material can move the rotor | Coast time, locking the rotor for liner or hammer work |
| Centrifuge | Extreme stored energy, long run down | Lid lock held by a safety-rated standstill signal, controlled stop with braking sized for it |
| Packaging machine | Frequent operator access at speed | Safely limited speed for setup, door interlocks, restart behavior after a guard closes |
| Machine tool spindle | High speed, tool contact | Controlled stop timing, safe standstill for tool change, speed limit for setup |
A safety-rated standstill signal means a safety encoder, a standstill monitor, or an encoderless function rated for that job. The drive’s speed display and its status word do not qualify. The table points at what to look at. The functions a machine needs come out of its risk assessment, and two machines with the same load type can land in different places.
Stopping time is the machine’s number
A drive’s STO reaction is a few milliseconds. The machine’s stopping time is whatever the inertia, the load, and the braking add to that, and it is the number that decides where a guard goes, how long a door stays locked, and whether STO alone is good enough.
Stored energy in a rotating load goes up with the square of speed. A fan wheel with 20 kg·m² of inertia referred to the motor shaft holds about 350 kJ at 1780 RPM. At half that speed it holds about 87 kJ, a quarter as much. STO does nothing with that energy. It bleeds off through bearings, windage, and the process, and on a big fan that takes a long time.
A controlled stop pushes that energy back into the drive. On a drive with a plain diode front end, it has to go into a braking resistor, or the bus climbs, the drive trips on overvoltage, and the motor coasts anyway. For a braked stop at constant net torque, stopping time is the inertia times the starting speed in radians per second, divided by the torque. That same 20 kg·m² wheel at 1780 RPM stops in about 19 seconds at 200 N·m of net braking torque and about 37 seconds at 100 N·m. On an unbraked coast, fan drag falls off as the wheel slows, so the tail runs far longer than any straight-line estimate, and a 19 second figure says nothing about how long the same fan coasts under STO.
The braking duty for that 200 N·m stop comes in three numbers, and each one sizes something different. The peak is about 37 kW at the start of the stop, 200 N·m times 186.4 rad/s, which sets the minimum resistance and the chopper rating. The energy is up to about 350 kJ per stop, less windage and losses, which sets the resistor’s thermal rating along with how often the stop repeats. The average is 18.6 kW over the 19 seconds, which is the mechanical power taken off the wheel and is not automatically what the resistor sees. A resistor sized for occasional slowdowns can be too small for a safety stop at full speed. The formula gives a planning number, and the stopwatch on the real machine settles it.
The total response is the sensor, plus the safety relay or safety controller, plus any network time, plus the drive’s reaction, plus the mechanical stop. On almost every machine the last piece dominates. Drive braking cannot be credited after loss of incoming power, so the guard design has to handle a full coast regardless of what stopping function was chosen.
Five machines worth working through
A high-inertia fan
An emergency stop on a large process fan through STO removes torque at once, and the wheel coasts for minutes. If the access door can open during that coast, the person reaching in meets a wheel still turning at speed. The usual answers are a guard lock that releases only on a safety-rated standstill signal, a controlled stop under SS1 with the braking resistor sized for a full-speed stop, or both. Two questions belong on the drawing. What does the guard lock do when power is lost, and does it stay locked through the coast? And if the stop is SS1-t, what keeps the door shut when the ramp fails and the timer runs out with the wheel still turning? Outdoor fans add windmilling, where draft turns the wheel with the drive off, so work inside the housing needs a mechanical lock or brake, and the drive’s catch-a-spinning-load setting has nothing to do with safety.
A loaded incline conveyor
Remove torque from a loaded incline belt and the load can run it backward. The first questions are mechanical. Does the gearbox back drive? Is there a backstop or holdback on the head pulley? Is there a spring-set brake, and does it set when control power is lost? If a brake is part of the safety function, it needs a safety-rated brake command, feedback that the brake engaged, and a way to prove it still holds, because a brake worn past its holding torque still sets and looks normal on a walkdown, and only a holding test shows the difference. Decline conveyors are the same problem in the other direction, with the load trying to run away.
A winder at threading
Threading a winder puts hands near nip points with the machine turning. Safely limited speed monitors speed and drops to STO if it goes over the limit. It does not remove the nip, and an overspeed trip can still leave the roll coasting. Setup at reduced speed works as one design: a mode selector that is part of the safety system, an enabling device the operator holds, the guarding that stays in place at the nip, and a stop response that has been validated on that winder. Encoderless safe speed has limits. On ABB’s version, it is not usable below 2 Hz and is not meant for loads that can drive the motor. Other drives differ, so check the manual for the firmware in front of you. Web tension stays stored after torque is gone, in dancers, nip rolls, and the roll itself, so the threading procedure has to release it before hands go in. Where reverse motion would pull a hand into a nip, safe direction monitoring belongs in the design, and on most drives that needs a safety encoder.
A centrifugal pump with head behind it
A pump stopped by STO comes down fast, so stopping time is rarely the issue. The issue is what the water does next. With a failed or missing check valve, the head on the discharge side can spin the pump backward, and a motor turning backward is a hazard to anyone working on the coupling and a problem for the drive on restart. On a permanent magnet motor, a shaft turned by the water also puts voltage on the motor leads with the drive off and the disconnect locked. Work on the pump needs isolation valves closed and the line relieved, in addition to electrical lockout. On process systems, the pump may also sit inside a process safety system, which brings its own standard and its own people, and the machine side and the process side have to agree on what the safe state is.
A hoist with a hanging load
On a hoist, STO alone drops the load. Three separate things keep it up, and the design has to cover each one. The first is the brake command, the safety-rated output that tells the brake to set, which is what Safe Brake Control provides. The second is feedback that the brake engaged, which Safe Brake Control does not include by itself and has to be added. The third is proven holding torque. A brake indication shows that the mechanism moved, and it does not show that the brake will hold the load, so a brake test has to prove the holding torque and has to be repeated, because wear lengthens the stopping distance and lowers the holding torque without any warning. The design also has to cover the gap where torque disappears before the brake has developed holding force, including on power loss and on faults. Speed monitoring has to be rated for loads that can drive the motor, which on most drives means a safety encoder. The sequence on a vertical load is covered in VFD Controlling a Mechanical Brake on a Vertical Load.
On all five of these machines the hazard is still there after the drive reaches STO, and the brake, the lock, the valve, or the procedure is what removes it.
Hardwired, safety controller, or safety network
Plants run every arrangement side by side. The oldest puts two monitored contactors after the drive, dropped by a safety relay, with the drive treated as an ordinary control device. Output contactors have to be sequenced the way the drive maker’s instructions say, and opening them under load as a routine stop is hard on the drive and the contacts. The next arrangement takes the safety relay output straight into the drive’s two STO channels, which saves the contactors and keeps the drive powered. A safety PLC with safe outputs into STO handles several interlocks, operating modes, and zones on one machine. A safety network carries the command over PROFIsafe, CIP Safety, or Safety over EtherCAT to a compatible safety controller, and the safety layer checks every message for corruption, repeats, and lateness, sending the drive to its safe state if anything is wrong. None of that checking depends on the network underneath being reliable.
An ordinary stop command over EtherNet/IP, Modbus TCP, or PROFINET has none of that checking, however well the network has behaved, and a drive status word is not safety-rated feedback. The reliability side of that comparison is in Is Fieldbus Less Reliable Than Hardwired Control for VFDs? Networked safety and drive safety modules also carry a configuration and usually a signature, which means a replacement drive or module is not ready to run until that configuration is restored and checked.
What gets missed at start-up
These are machine-level checks. Use them alongside the drive maker’s acceptance test.
- Before testing anything with the motor turning, clear the area and have an independent way to remove power, because if the function under test does not work, the motor keeps running. On an overhauling load, do not test STO at speed until the brake logic in step 10 is proven.
- Write down each safety function the machine needs and the PL or SIL the risk assessment calls for before anything gets wired.
- Confirm the drive model, safety options, and firmware match the safety certificate and the design calculation.
- Check the safety wiring against the approved drawings, and make sure the factory STO jumper is gone wherever the design calls for a safety device on those terminals.
- If a safety relay or light curtain feeds STO through outputs with test pulses, confirm the drive is listed for that pulse pattern, since a mismatch is a common commissioning fault.
- Activate STO the way the machine normally does, through the door switch, e-stop, or safety controller, with the motor running at a moderate speed. Confirm the torque removal through the drive’s safety-rated STO indication and the behavior the design specifies, not through an ordinary status word bit.
- With STO active, try to start from the keypad and from the remote source, and confirm the drive starts from neither.
- Confirm that releasing the e-stop, closing the guard, resetting the safety fault, or restoring power does not by itself restart the motor.
- Open each STO channel by itself and confirm that channel alone removes torque, and that the discrepancy is detected and latched by the drive or the safety relay, as the design intends. A circuit that tolerates one open channel without a complaint has lost the redundancy its rating depends on.
- On a hoist or any vertical load, prove the brake command, the brake engagement feedback, and the holding torque.
- Measure stopping time at the worst case: top speed, the most inertia, the least process drag (which is not always the heaviest load), the most worn brake you will accept, and a full coast on loss of power. Repeat the stop, and compare the worst run, plus margin for deterioration, with what the guard and lock design allows.
- Where speed or direction functions are used, test the limit trip, and test what the drive does when the encoder or the safety network is lost.
- Check every other path that can power the motor, including a bypass starter or an alternate supply, and confirm the safety function covers each one.
- Record the results, the configuration and signature, and the periodic test interval, and get them signed. The interval comes from the safety calculation and the drive’s safety manual, not from maintenance habit.
The full start-up sequence these checks belong to is in the VFD Commissioning Guide.
What breaks it after handover
A safety function that passed its acceptance test can be undone by ordinary maintenance, and these changes do not announce themselves with a fault.
| Change in the field | What it does to the safety function |
|---|---|
| STO terminals jumpered to get a machine running | The safety function is gone |
| A run enable or stop input wired in place of STO | Nothing safety-rated is removing torque |
| Replacement drive of a different model or rating | The design calculation no longer describes the machine |
| Safety parameters restored wrong, or not at all | Limits and reactions differ from what was tested |
| Brake wear | Longer stopping distance, less holding torque |
| Encoder replaced or misaligned | Speed and direction monitoring are reading the wrong thing |
| Bigger fan wheel, heavier roll, or more product | The measured stopping time no longer holds |
| Bypass starter added | A second path to the motor that STO does not cover |
| Drive status read as safety feedback | Guard decisions made on a signal with no safety rating |
| Periodic test skipped | A failed channel sits undetected until the second one fails |
| STO used as electrical isolation | Someone works on live conductors and a charged DC bus |
Each of these is a change to the safety function and calls for the start-up checks that apply to it. Bypass packages deserve a specific look, because the bypass contactor is built to run the motor when the drive cannot. The bypass arrangement itself is covered in VFD Bypass vs N+1: A Reliability Comparison.
STO is not lockout
OSHA’s lockout rule does not count push buttons, selector switches, or other control circuit devices as energy isolating devices, and STO is a control circuit function inside a drive whose main circuit stays live. The rule has a narrow exception for minor servicing that is routine, repetitive, and integral to normal production, done under alternative measures that give effective protection, and a properly designed STO or prevention of unexpected start-up function can be one of those measures. Site procedures may be stricter than the rule. Opening the drive, working on the motor leads, or changing a motor is outside that exception and needs lockout at a real disconnect, the manufacturer’s discharge time, and a qualified person verifying the absence of voltage.
On a permanent magnet motor, lockout at the disconnect is not enough if the shaft can turn. A windmilling fan, a backspinning pump, or an overhauling conveyor turns the motor into a generator and puts voltage on the leads, so stop and lock the shaft, or open a motor-side disconnect, before anyone touches them.
The drive ratings you will see
| Drive or option | Published STO rating |
|---|---|
| ABB ACS880 | SIL 3, PL e, Category 3 |
| ABB ACS580 and ACS380 | SIL 3, PL e; category in the hardware manual |
| ABB FSPS-21 and FSCS-21 | SIL 3, PL e; STO and SS1-t over PROFIsafe or CIP Safety |
| Rockwell PowerFlex 525 | PL d, SIL CL 2, Category 3 |
| Yaskawa GA500 | PL e, SIL 3 |
| Yaskawa V1000 | PL d, SIL 2 in its dual-input form; confirm the terminal board fitted |
| Danfoss VLT FC 302 | PL d, SIL 2; category in the safety documentation |
The table follows each maker’s own wording. SIL and SIL CL are not the same claim: SIL CL is the IEC 62061 claim limit for a subsystem, the highest SIL that subsystem can support in a function.
These are ratings of the drive’s part of the function. The ACS880 and the PowerFlex 525 are both Category 3, and one is PL e while the other is PL d, because the PL also depends on diagnostic coverage, the time to a dangerous failure, and the measures against common cause. The parts in front of the drive set limits of their own. A single-channel door switch with no testing puts that part of the function in Category B or 1, which top out at PL b and PL c, and a PL e drive behind it does not lift the function past that.
As of November 2026, the current drive safety standard is IEC 61800-5-2 Ed. 2.1 (2016+AMD1:2026), so anything that leans on a specific edition should be checked against the current text. Machines placed on the EU market or put into service there come under the EU Machinery Regulation from January 20, 2027, in place of the old Machinery Directive.
Field notes for safety work
- A5A0 on an ABB Drive: What Safe Torque Off Is Telling You, the STO codes on ABB drives and what a single open channel means.
- Is Fieldbus Less Reliable Than Hardwired Control for VFDs?, the hardwired and networked comparison, including safety failure rates.
- VFD Controlling a Mechanical Brake on a Vertical Load, holding a suspended load at brake release.
- VFD Controlling a Mechanical Brake on a Horizontal Load, conveyors and transfer cars.
- Why a Brake Motor’s Brake Has to Be Wired Separately on a VFD, the wiring mistake that leaves a brake dragging or never setting.
- VFD Overvoltage Faults, what happens to a controlled stop when the braking energy has nowhere to go.
- VFD Bypass vs N+1: A Reliability Comparison, the bypass arrangements that add a second path to the motor.
- The ABB, PowerFlex 525, and Yaskawa fault field guides, for the STO and safety codes on each brand.
Related guides
The HVAC, water and pump, and data center application guides cover loads where STO is often present, and often jumpered. Segregating safety wiring from motor leads is installation work in the VFD Installation Guide, the acceptance checks sit in the VFD Commissioning Guide, a machine that will not run after a safety trip starts in the VFD Troubleshooting Guide, and the periodic tests go in the VFD Maintenance Guide.
Summary
The drive’s safety rating covers the drive, and the safety function is part of the machine. On every load in this guide the working question is what the machine does once the drive stops making torque. The answer comes from the stopping time measured on that machine, the outside forces that can still move the load, and every other path that can power the motor, and it has to be checked again after any change to that chain. Before the First Fault covers safety circuit testing at commissioning, and the training puts crews on real drives to run these checks.
Frequently Asked Questions
Is a safety-rated VFD enough to make a machine safe?
No. The rating covers the safety circuit inside the drive. The machine's safety function also includes the sensing device, the safety relay or safety controller, the wiring, any brake, and the stopping time, and it has to be designed from the machine's risk assessment and proven by test.
Does Safe Torque Off stop the motor?
STO removes the drive's ability to make torque, and the motor coasts to a stop on its own inertia. A heavy fan or mill can coast for minutes, and a load with gravity or pressure behind it can keep moving. A safety-rated controlled stop needs SS1, and holding a load needs a brake.
Is Safe Torque Off the same as lockout tagout?
No. STO is a control circuit function, and the drive's main circuit and DC bus stay energized. Under OSHA's rule it can serve as an alternative measure only for minor servicing that is routine, repetitive, and integral to normal production, and only where it gives effective protection, and site procedures may be stricter. Work inside the drive or on the motor needs lockout at a real disconnect, the manufacturer's discharge time, and a qualified person verifying the absence of voltage. On a permanent magnet motor whose shaft can turn, the shaft also has to be stopped and locked, or a motor-side disconnect opened.
When is STO alone the wrong stop?
When the coast time is longer than the guard design can allow, when an outside force can move the load, or when the machine has to stop faster than it will on its own. High-inertia fans, centrifuges, incline conveyors, and hoists are the usual cases.
Do hoists need more than STO?
Yes. Removing torque from a hoist with a hanging load drops the load unless a brake holds it. The design needs a safety-rated brake command, feedback that the brake engaged, and a periodic test that proves the holding torque, and it has to cover the moment between torque going away and the brake taking hold. Speed monitoring has to be rated for loads that can drive the motor, which on most drives means a safety encoder.
Can a safety function run over EtherNet/IP or PROFINET?
Only with a safety protocol such as CIP Safety or PROFIsafe, a drive or option rated for it, and a compatible safety controller. An ordinary stop command over the same network is not safety-rated, however reliable the network has been.
What has to be retested after a drive is replaced?
Whatever the machine's validation procedure calls for after a drive replacement. At a minimum, confirm the replacement carries the same safety rating and options, restore and check the safety configuration, and open each STO channel to confirm torque removal and discrepancy detection. Repeat the stopping time check when the validation procedure requires it, and whenever anything about the drive, the braking, or the load changed.
Online start-up courses, filmed on real drives
One drive per course, filmed uncut with a clock on screen from first power to a saved backup. The install course and the after start-up course are free, and the start-up courses for the ABB ACS380 and ACS580 and the Allen-Bradley PowerFlex 525 are open now.