A data center uses drives on its cooling, and the cooling has one job a comfort system doesn’t: it has to come back on its own after the power drops. The CRAH units in the white space pull room air across chilled water coils, on EC fans or VFDs. Behind them, the chiller plant and the CDUs that feed liquid cooled racks run their pumps and fans on drives. A drive tech gets called for the start-up, for the commissioning tests, and for the restart that didn’t happen.
Where the drives actually are
EC fans are taking over in new CRAHs and a lot of fan walls. The drive work in a data center has moved to the plant and to liquid cooling: chilled water and condenser pumps, cooling tower fans, large air handlers and fan arrays with induction or PM motors, chillers with their own compressor drives, and the pumps inside the CDUs. The note on what a CRAH unit is goes through what spins inside the cabinet and where the drives sit behind it.
After the power drops
When utility power fails, a Level 1, Type 10 emergency power system allows up to 10 seconds without acceptable power at the transfer switch. Not every site is built that way, and getting power back does not by itself bring the cooling back. Every cooling drive that loses power has to restart on its own, catch a fan that is still spinning, get its run command back, and take its slot in the restart order so the generator does not see every drive at once. The chillers take minutes to come back, so thermal storage or UPS backed equipment covers the gap on sites that have them.
That restart chain is where jobs go wrong. A drive can restart perfectly and still sit stopped because a contactor or a BMS start relay dropped out during the transfer. The CRAH note goes through the chain link by link, with the restart settings to check on the unit controller and the drive.
Liquid cooling changes the clock
Air cooled rooms usually had at least a minute of cooling outage to work with. Liquid cooled servers start throttling much sooner after they lose flow, and some cold plate systems give less than 10 seconds. A CDU pump that waits for the generator can leave the chips without flow for longer than they can stand. Designers answer it with UPS power for the pumps, ride-through built into the CDU, or two power feeds. The note on CDU data center pumps covers how the pumps are controlled, how the redundancy really works, and what to check in the pump drive.
N+1 is a capacity rule
N+1 means one more unit of capacity than the load needs. Some rooms run every unit at part speed and share the load, and others hold a standby unit. Either way, every unit has to be set and tested to do its job when a neighbor fails. Redundant drives have largely replaced bypass, because a bypass runs the motor across the line at full speed and hits the generator with inrush. The field note VFD Bypass vs N+1 runs the reliability numbers.
Generator power and the BMS
A generator is a much weaker source than a utility transformer, so the same drives make far more voltage distortion on it. IEEE 519 limits apply at the utility point of common coupling, so on an islanded generator the design has to work to the weaker of what the generator and the connected equipment can stand. Passive filters can push a lightly loaded generator into leading power factor. And when the BMS network goes quiet, a cooling drive has to keep cooling. The note on VFD harmonics on generator power and BMS comm loss covers the sizing, the filters, the comm loss settings by brand and the tests that prove them.
What the drive tech owns at commissioning
Data center jobs run commissioning in levels, L1 factory testing through L5 integrated systems testing. The drive work shows up at every level: firmware and parameter files at the factory, storage and capacitor age at delivery, megger and terminations at start-up, comm loss, power loss and failover tests at functional testing, and a full utility to generator transfer at the end with every fan and pump coming back as the sequence calls for. The note on data center commissioning levels goes level by level through what the drive tech owns.
The drives you will see
All three of these HVAC drive lines have BACnet and a smoke control or fire mode override built in. For data center work the differences that matter are ride-through, restart, harmonic options and redundancy.
- ABB ACH580. ABB’s HVAC drive in the 580 family, with undervoltage control for ride-through, automatic restart and flying start, ultra low harmonic versions, and the E-Clipse bypass in the US. ABB says the redundant drive effectively replaces the bypass in today’s redundant drive systems. The note on ACH580 vs ACS580 covers what the HVAC program adds.
- Yaskawa HV600. Rated for up to 2 seconds of power loss ride-through, with an add-on momentary power loss unit on the smaller models. The HV600 Redundant automatically transfers control of the motor to the second HV600 if one fails.
- Danfoss VLT HVAC Drive FC 102. Kinetic back-up keeps the drive running as long as there is energy in the system and restores operation when the mains return, with flying start to catch a spinning motor.
The settings that decide whether these drives bring cooling back after a power loss are different on every brand, and sometimes on every firmware revision, so check the manual for the drive on the job.
Field notes for data center work
Each of these goes deeper on one part of a data center drive job.
- What Is a CRAH Unit? A Drive Tech’s Look Inside. CRAH vs CRAC, what spins inside, EC fans vs VFDs, fan walls, and the core of it: what happens after utility power drops. Why ride-through won’t cover a transfer, the five links in the restart chain from the unit controller to the run command, staggered restarts, why the chillers are the slow part, and how to test it.
- CDU Data Center Pumps: What a Drive Tech Checks. What a CDU does between the facility water and the server loop, what’s inside, how differential pressure and flow control behave, what to check in the pump drive, redundancy as a capacity question, how long liquid cooled chips can wait, power options from UPS to dual feeds, and the 800 VDC CDUs starting to appear.
- Data Center Commissioning Levels: L1 to L5 for Drive Techs. Where the levels come from and how they vary by job, then the drive tech’s work at each one: submittals, factory acceptance, delivery and capacitor age, start-up, functional tests, the integrated systems test and handover, with the common failures mapped to the level that should catch them.
- VFD Harmonics on Generator Power and BMS Comm Loss. Why a generator turns the same drive load into far more voltage distortion, what IEEE 519 says about an islanded building, generator sizing and harmonic options, passive filter traps, load steps and power-up limits, and how to set and test what a cooling drive does when the BMS goes quiet.
- VFDs on Generator Power: Sizing, Filters and Transfer. The general rules behind the data center notes: generator sizing for drives by maker, excitation and the regulator, AC reactors versus DC chokes, the capacitor rule for passive filters, grounding on both sources, transfer methods and power-up limits, load acceptance, load rejection overvoltage and regen.
- VFDs on an 800 VDC Data Center Bus. Why a 480 V class drive doesn’t belong on an 800 VDC bus, the voltage envelope from the OCP Mt Diablo spec, which 600 V and 690 V class drives list a DC input range that fits, what the inverter can deliver to the motor, the common DC bus rules that carry over, grounding and leakage, braking on a one way bus, and the questions to put to the drive maker.
- VFD Bypass vs N+1: A Reliability Comparison. A 900,000 run Monte Carlo comparison of 2-contactor bypass, 3-contactor bypass and N+1 lead/lag for data center cooling, with cost and break-even numbers.
- Chilled Water and Condenser Water Pump VFDs and Cooling Tower VFD Setup. The plant behind the CRAHs: loop differential pressure, chiller minimum flow, proving flow, tower speed limits, resonance and de-ice.
- ECM vs VFD for HVAC Fans: How to Choose. How EC fans and VFDs compare on power, harmonics, controls, service and fan arrays.
- VFD Fire Mode and Smoke Control Override for HVAC. How the drive brands handle fire mode, which matters where a data center’s fire sequence stops some fans and runs others.
- ACH580 BACnet MS/TP Setup and Troubleshooting and VFD Communication Faults. Addressing, wiring, comm loss action and reading the error counters, then the routing, termination and switch problems behind comm timeouts.
- Is Fieldbus Less Reliable Than Hardwired Control? and The Off-Shift Test. Whether the BMS should be in the control path at all, and an availability model of hardwired against networked drive control on nights and holidays.
- You Cannot Buy IEEE 519 Compliance From a Drive. How the harmonic limits work at the utility point of common coupling, and what to write in a spec instead of 5 percent at every drive.
- VFD Parameter Backups: Keypad, Memory Module, Clone. The three kinds of backup, how each fails, and why a restore needs testing before handover.
- Reflected Wave and Long Motor Leads and VFD Cable: How to Choose It and Terminate the Shield. Long runs to rooftop and tower motors, the output filter choice, and the cable and shield work the restart depends on.
- VFD Overtemperature Fault: Why Drives Overheat. Filters, fans, ambient, carrier frequency and enclosure ventilation, for drives in hot mechanical rooms and on the roof.
Training
For tradespeople moving into data center work, see data center training. The install basics that start-up depends on (shielded cable, grounding and megger) are in the free First Power class, and ride-through, flying start and comm loss setup on the ACH580 are in the ABB 580 start-up class, both at The Tolbert School.
Related guides
The chilled water pumps behind every CRAH are covered in the water and pump drives guide, and the same drives from the comfort cooling side are in the HVAC drives guide. New to drives? Start with What Is a VFD?.
Frequently Asked Questions
What is the difference between a CRAC and a CRAH?
A CRAC has its own compressor and refrigerant. A CRAH uses chilled water from a central plant and has no compressor.
Does a CRAH unit have a VFD?
Some do. New CRAHs and many fan upgrades use EC fans, where the speed control is built into the motor. VFDs stay common on older units, on fan walls with induction or PM motors, and on many of the pumps and fans in the plant that feeds the CRAH.
What happens to data center cooling when the power goes out?
Unless the cooling equipment is on UPS power, it stops. Getting power back is the first step. Then the unit controllers, fans and pumps have to restart in the intended order, and the chilled water plant has to come back to usable capacity. Liquid cooled equipment gives far less time than air cooling did, which is why CDU pumps are often put on UPS.
Do data centers use VFD bypass?
Less than they used to. With N+1 units, the other units carry the load, and drive makers now sell redundant drives in place of bypass.
What should a drive do on BMS comm loss in a data center?
Whatever the approved sequence says, which usually means keep cooling: hold the last speed, go to a preset speed validated for the cooling demand, or hand control to a hardwired or local fallback. Set the timeout to ride through a controller reboot and prove it with comm loss tests at commissioning, including power-up with the BMS already gone.
What are data center commissioning levels?
A staged way of proving the site works. ASHRAE describes five: L1 factory acceptance, L2 delivery and installation, L3 pre-functional checks, L4 functional performance testing, and L5 integrated systems testing. The job's commissioning plan sets what each level includes.