Field note

VFD Fire Mode and Smoke Control Override for HVAC

The building passes its smoke control test on the first try, and the fire alarm contractor packs up. A week later the BAS operator finds two air handlers sitting in Off. Somebody had them in Hand when the override was triggered, and when the override cleared they went to Off, which is exactly what those drives are built to do. Nobody walked the units afterward.

Every HVAC drive maker has a fire mode, and each one calls it something different: Override on ABB, Fire Mode on Danfoss and Eaton, Emergency Override on Yaskawa, Essential Service Mode on Siemens. In each case the drive is asked to do the opposite of its normal job. Normally it protects the motor and itself first. In fire mode it runs the fan for the people in the building and gives up some or all of its own protection to do that. How much it gives up is where the brands differ, and that is what this note covers.

Who owns the sequence

The drive does not decide anything in a fire. The smoke control design, written to NFPA 92 and the local code where they apply, says which fans run, at what speed, in which direction, and which dampers open. The fire alarm or smoke control panel sends the command. Many buildings also have a firefighter’s smoke control station that lets the fire department command fans and dampers by hand, and the design sets which command wins: the station, the automatic smoke control sequence, or the BAS. The authority having jurisdiction, usually the fire marshal, accepts the system after a test. The drive tech’s job is to make the drive do exactly what the design says, prove it, and write it down.

Before setting anything, get the smoke control sequence for each fan. If it is not on the drawings, ask the engineer of record.

Fire mode is not a smoke control listing

Three things get mixed up on jobs:

  • A fire mode feature. Every drive in this note has one. It is a firmware setting.
  • A maker saying a product is designed to comply. ABB, for one, says the Smoke Control override on its E-Clipse bypass is non-programmable and designed to comply with UL 864/UUKL, the listing smoke control equipment is checked against.
  • An actual listing. A specific product or system configuration that holds a smoke control listing, installed the way the listing requires.

A fire mode menu in a drive does not make it suitable for a listed smoke control system. The engineer, the code, the listing and the AHJ decide what equipment is acceptable, so ask before a drive goes into a smoke control role.

What every fire mode decides

Whatever the brand, the same questions have to be answered for each fan:

  • The trigger. Which input starts it, and whether that input is also the run command.
  • Speed and direction. A preset speed, an analog signal, a PID loop holding a pressure, and forward or reverse.
  • What it ignores. The BAS, the keypad, stop commands, and which faults.
  • What still stops it. Which faults still trip the drive, and which safeties (damper end switches, high static, freezestats) are still allowed to stop the fan.
  • Fault resets. How many restart attempts it makes, or whether it retries forever.
  • The warranty. What the maker says about a drive that ran through a fault in fire mode.
  • Coming out. What mode the drive returns to when the input opens.
  • The BAS. Whether the BAS can see that fire mode is active.

How the brands differ

Brand and modeFaults that still stop itSafeties and interlocksWarranty
ABB ACH580, OverrideHigh priority faults, including overcurrent, short circuit, earth leakage, DC overvoltage, motor overload and STOOnly the run permissive and start interlocks selected for OverrideCritical Override might void it if not used correctly
Danfoss FC 102, Fire ModeCritical alarms, with the trip or retry behavior set by the alarm handling settingCheck the manual for the firmware on the jobRunning through an ignored alarm voids it, and the event is logged
Yaskawa HV600, Emergency OverrideHeatsink overheat, with automatic restart when it cools; motor overload is ignoredCustomer safety and BAS interlock inputs ignored unless set otherwiseCheck the manual
Siemens G120P, Essential Service ModeFaults that would directly destroy the inverter or motor, retried by automatic restart until the attempts run outCheck the manualActivating it voids all warranty claims
Eaton H-Max, Fire ModeNormal protective trips suppressed, per Eaton’s application noteAll interlocks and enable signals disabledCheck the manual

ABB ACH580. A digital input turns Override on and also acts as the start command. The speed can come from a preset Override frequency, constant speeds, an analog input, a raise and lower floating point, or PID, with a direction setting. Once in Override the drive ignores fieldbus start, stop and speed commands, the Hand, Off and Auto keys, and parameter changes, while the BAS can still read it. It reads only the safeties selected for Override: the run permissive and up to four start interlocks. High priority faults still stop it, and every other fault is reset when Override starts and ignored. The Override mode can be Normal, which follows the programmed reset attempts, or Critical, which allows unlimited resets. If Safe torque off opens, the drive leaves Override and does not go back in when STO closes. ABB’s firmware manual says a drive that was in Hand goes to Off when Override ends. ABB’s documents have not always described the return the same way, so check it against the firmware on the job and watch what the unit does in the test.

Danfoss FC 102. Fire Mode has its own reference and feedback sources, so it can hold a pressure with its PID loop or follow an analog signal. The alarm handling setting picks one of three behaviors: keep running and ignore most alarms with unlimited automatic resets on critical ones, trip on critical alarms and wait for a manual reset, or a test setting where every alarm acts normally. Danfoss warns that the first choice may damage the drive. The drive logs warranty-affecting alarms and every fire mode activation and deactivation. After fire mode, a “Fire mode was active” warning stays until power is cycled, and if an alarm was ignored a separate warning says operating that way voids the unit warranty. Danfoss’s own application paper describes the drive sacrificing itself and running “to dead” to keep the fans going.

Yaskawa HV600. Emergency Override can run at a set speed, follow the normal Auto reference, or run its own PID loop with its own setpoint. During it the drive ignores a long list of faults and alarms, including motor overload, external faults and communication errors, and it allows unlimited automatic restart attempts. It does not suppress heatsink overheat. It trips and restarts on its own when the heatsink cools. The customer safety and BAS interlock inputs can each be ignored, required to be OK, or required to be open for Emergency Override to run, and both default to ignored. A test setting runs Emergency Override with every drive fault still active.

Siemens G120P. Essential Service Mode ignores faults that do not directly destroy the inverter or the motor. Faults it cannot ignore are cleared by the automatic restart function, and when the restart attempts run out, the drive faults and can switch the motor to bypass if the package has one. Siemens is blunt about the cost: activating it voids all warranty claims for the inverter, it can cause extreme temperatures and even open fire, and the drive keeps a password-protected log of ESM activity that only service staff can read.

Eaton H-Max. Out of the box, Digital Input 5 is fire mode and the drive runs at 60 Hz when it closes. Eaton’s application note says fire mode disables all interlocks, enable signals and faults. The speed source can be changed to a preset speed, the keypad, fieldbus or an analog input. The keypad flashes Fire Mode Active while it runs. Suppressing trips does not let a drive survive a failed power section, a loss of incoming power or an upstream breaker opening. It means the drive stops protecting itself. Of the five, this is the default that most needs to be checked against the sequence. With interlocks disabled, a damper end switch wired to the drive does nothing in fire mode, so a fan can run against a closed damper unless the design handles that protection somewhere else. Trace where every end switch is wired on the actual job.

These descriptions come from each maker’s HVAC drive manuals and application notes. Firmware changes, so check the manual for the firmware on the job before setting anything.

Fire mode with a bypass

A bypass adds a second path to the motor, and makers handle fire mode through it differently.

ABB E-Clipse. The bypass controller has two override modes. Override 1, Smoke Control, is a fixed input that cannot be reprogrammed. It runs the motor across the line through the bypass contactor and ignores the keypads, external stop commands and anything over communications. It ignores low priority safeties such as freezestats and return duct smoke detectors, still responds to high priority safeties such as the high static switch and damper end switch proofs, and always responds to the bypass motor overload. Override 2, Advanced Override, can run the motor on the drive or in bypass, can be started by its input or over communications, and from the factory ignores all external safeties and run enables, though it can be programmed to honor them for the local AHJ. A BACnet object shows when either override is active.

Yaskawa HV600 bypass. A contact closure transfers the motor to bypass for emergency override, and Yaskawa states that the motor overload and the safety interlock circuit are overridden during it. That is the opposite of the E-Clipse, which keeps the overload in.

Danfoss drive bypass. The FC 102 can drive an external bypass contactor through a relay output, switching the motor across the line when the drive trips or when fire mode is set to coast. Once in fire mode, the drive bypass cannot be turned off until the fire mode signal or the power is removed. Danfoss also notes that with the drive bypass function turned on, a drive with Safe Stop is no longer safety certified.

Siemens. If the drive is in bypass when Essential Service Mode starts, it switches back to inverter operation so the fire mode setpoint takes control. Bypass is the fallback after the restart attempts run out.

The overload question

The table shows the split. ABB keeps the motor overload in, in the drive and in the E-Clipse bypass. On the E-Clipse the overload settings are entered in the drive and used by both, but the protection is done by the drive when it runs the motor and by the bypass controller’s electronic overload when the motor runs across the line. Yaskawa ignores it in the drive and overrides it in the bypass. Eaton disables all faults. Danfoss and Siemens depend on how the alarm is classed and how the restarts are set.

Some specs say every interlock and the overload stay live in fire mode. Some say the opposite. Either way, that is a decision for the engineer and the AHJ, and the setup has to match what the equipment can actually do. Whatever the answer, set the motor full load amps and overload class from the nameplate before any smoke control test.

Bypass outside of a fire

Bypass gets used far more for a failed drive than for a fire, and it changes how the fan behaves.

Full speed. In bypass the motor runs across the line at full speed. A VAV supply fan in bypass stops holding duct static and pushes whatever the system curve gives it, which is why the high static switch matters as much in bypass as in fire mode. The design should say how the system runs in bypass.

The transfer. When a running motor transfers from the drive to the line, it has to pull from its coasting speed up to line frequency, and that inrush and torque hit lands on the motor, the coupling and the upstream breaker. The ABB E-Clipse, for example, uses two contactors, a bypass contactor and a drive output contactor, interlocked so line power never reaches the drive’s output. Test transfers the way the maker’s procedure says, not by flipping the selector back and forth.

What the bypass refuses. The E-Clipse controller will not transfer into bypass when the drive has tripped on a motor related fault, so it does not slam line power onto a damaged motor. A basic contactor bypass has no such check. Know which kind is on the job before an operator learns to flip to bypass every time the drive trips.

An intelligent bypass makes a failed drive easier to live with. It does not change the fact that one motor and one fan carry the whole load at full speed until the drive is fixed. For critical air handlers and pumps, the note on VFD bypass vs N+1 compares bypass with a running spare.

Testing it

Smoke control acceptance follows a written test procedure that the engineer and the AHJ approve, run with the fire alarm contractor, the controls contractor and the smoke control team. The drive tech’s part is to show that each drive does what the sequence says. Never test by jumping out a safety or pulling a wire on a running system on your own.

Danfoss and Yaskawa both have a test setting that runs fire mode with every fault still active. Use it for the first runs, and confirm the setting is back to its fire setting before the witnessed test. For each fan, the procedure should prove:

  • The command. The smoke control command, from the panel and from the firefighter’s station if there is one, starts the right fan.
  • Speed and direction. The fan runs at the speed and in the direction the sequence calls for. Look at the fan, not just the display.
  • Command priority. The BAS and the keypad cannot stop the fan in fire mode, and the firefighter’s station wins where the design says it does.
  • Safeties. Each safety the sequence says should stop the fan does, and each one that should not stop it does not, using the test method in the approved procedure.
  • Bypass. If there is a bypass, the override command produces the transfer the design expects, so everyone sees which contactor closes and which safeties still drop the motor. Watch duct static and the high static switch.
  • Feedback. The smoke control panel, the firefighter’s station and the BAS all show the fan and fire mode status they are supposed to.
  • Return to normal. Clearing fire mode puts every unit back in its intended mode and command source, and any fire mode warnings are cleared, which on some brands takes a power cycle.

A drive showing 45 Hz does not prove the stairwell holds its pressure difference or the smoke zone gets its airflow. The smoke control team measures that against the design. The drive is one part of the system.

Then walk every unit, put it in Auto, and confirm the BAS sees it in Auto. Do not leave that to the fire alarm contractor. Write down each fan’s fire mode setting, speed, direction, the safeties it honors, the fault and reset setting, and who witnessed the test.

After a real fire mode event

If a drive ran in fire mode during an actual event, write down what happened and pull the drive’s fault and fire mode log if it keeps one. A drive that ran through faults it would normally trip on may have been damaged, and on some brands its warranty is gone. Whether it goes back into service, gets inspected or gets replaced is a decision for the owner and the manufacturer. The general start-up tests are in the HVAC VFD commissioning checklist, and the fan side of the job is in AHU supply, return and exhaust fan VFDs.

Setting up Override and bypass on an ABB 580 drive is covered in the ABB 580 start-up class at The Tolbert School. The HVAC drives guide covers the rest of the building.

Frequently Asked Questions

What is fire mode on a VFD?

A mode the fire alarm or smoke control panel triggers, usually with a contact closure, that forces the fan to run at a set speed while the drive ignores the BAS, the keypad and many of its own trips. Each maker names it differently: Override on ABB, Fire Mode on Danfoss and Eaton, Emergency Override on Yaskawa, and Essential Service Mode on Siemens. The smoke control design and the authority having jurisdiction decide what the fan should do.

Does a VFD in fire mode ignore every fault?

It depends on the brand. ABB's ACH580 still stops on high priority faults such as overcurrent, short circuit, earth leakage and motor overload. Danfoss still trips on critical alarms. Yaskawa's HV600 ignores motor overload but still trips on heatsink overheat and restarts when it cools. Eaton's H-Max application note says fire mode disables all interlocks, enable signals and faults.

Does fire mode void the VFD warranty?

It can. Siemens says activating Essential Service Mode voids all warranty claims for the inverter. Danfoss says that running in fire mode after an alarm it would normally trip on voids the unit warranty, and logs the event. ABB says using Critical Override might void the warranty if it is not used correctly.

What happens to the motor overload in fire mode?

On ABB's ACH580 and E-Clipse bypass, the motor overload stays in. On Yaskawa's HV600, motor overload is ignored during Emergency Override in the drive, and the bypass emergency override overrides the motor overload and the safety interlock circuit. Check the brand and the setup against what the engineer and the AHJ approved.

Why did my drive go to Off after a fire mode test?

ABB's ACH580 firmware manual says a drive that was in Hand when Override started goes to Off when Override ends. Other brands follow their own Hand-Off-Auto settings when fire mode ends, and firmware can change the behavior. Put every unit in Auto before the test and walk every unit after it.

Online start-up courses, filmed on real drives

One drive per course, filmed uncut with a clock on screen from first power to a saved backup. The install course is free, and the ABB ACS380 and ACS580 start-up course is open now.

See the online courses

Wayward Leaders® is a veteran-owned VFD training practice. We teach maintenance teams and plant electricians to install, commission, and troubleshoot variable frequency drives correctly.

Every class ends with a scored competency assessment. The plant gets a way to prove what each technician can do, not a roster of who sat in the room.

The instruction is field-trained. It is drawn from nearly 8,000 VFD, power, and motor documents and from more than 750 commissioned drives captured through personal field experience and data collection. Carl Lee Tolbert, PhD, CMRP, and ATD Master Trainer™, leads it. He has delivered more than 5,000 hours of VFD instruction across 30 years and trained 8,000 industrial professionals, from International Paper to the U.S. Navy.

The premise is simple: VFDs do not fail. Installations fail them. The curriculum is built backward from that.

Installation, commissioning, troubleshooting, and fault diagnosis guides are published openly at waywardleaders.com.