The supply fan on a VAV air handler runs at 95% speed all afternoon. The building is comfortable, so nobody calls. The duct static setpoint is still where the start-up tech left it, 2 inches, and the sensor sits a few feet past the fan where the air is still churning. Down the hall, the return fan on the same unit hunts up and down every few minutes, and the front doors whistle. Both drives are working. The settings around them were never finished.
This note covers the three fans on a typical air handler. The general start-up tests are in the HVAC VFD commissioning checklist.
Supply fan: duct static and its reset
On a VAV system, the supply fan drive holds duct static pressure, and the VAV boxes take the air they need from that pressure. Either the BAS runs the PID loop and sends the drive a speed command, or the drive runs its own loop from the sensor. Write down which one owns it.
The sensor. Put it where the design shows. The commercial energy code language is that the sensor sits where the controller setpoint can be 1.2 inches w.c. or less, with one sensor on each major branch if that pushes it past a big duct split. About two-thirds of the way down the main supply duct is the traditional starting point for meeting that. A sensor right at the fan discharge reads turbulence and has to hold enough pressure for the entire duct run, so on a fixed setpoint the fan runs faster than it needs to. Check the sensor tubing too: a kinked or loose tube reads low, and the fan chases it to full speed.
The setpoint. A fixed setpoint is picked for the worst hour of the year, so for the rest of the year it makes more static pressure than the system needs. The better approach resets it from the zone that needs the most pressure, lowering the setpoint until one VAV damper is nearly wide open. Guideline 36 does this with trim and respond: the BAS trims the setpoint down a little at a time, and when zones send pressure requests it raises the setpoint by an amount tied to how many requests come in. The fan then runs at the lowest speed that still gives every zone its air. That reset lives in the BAS, so ask the controls contractor which method the job uses and watch the setpoint actually move.
Rogue zones. One VAV box that is wide open all day holds the reset at the top, and the fan never slows down. The code language expects the controls to flag a zone that keeps driving the reset, alarm on it, and let an operator take it out of the reset. Diagnose the zone before anyone takes it out. The fix belongs in the zone, and the zone still needs its air while it is being fixed.
The safety. A duct high static limit is separate from the control loop. It stops the fan when pressure climbs past what the ductwork can take, such as when a fire or smoke damper slams shut, or when the static sensor fails low and the loop drives the fan to full speed. Wire it the way the approved control and life safety design shows, and test it.
Return fan: three ways to control it
The return fan pulls air back from the building, and what it holds decides how the building pressure behaves. ASHRAE Guideline 36 covers three approaches:
| Method | How it works | What to watch |
|---|---|---|
| Speed tracking | The return fan follows the supply fan’s speed with an offset | Simple and needs no airflow stations. The offset is set at balancing, so check building pressure at more than one load |
| Airflow tracking | Airflow stations measure supply and return, and the return fan holds a fixed difference | Only as good as the airflow measurement, and field airflow readings are often off |
| Direct building pressure | A building pressure sensor drives the control | Watches the building itself, so it responds to doors, exhaust and other relief paths |
Between the last two, the practical difference is that airflow tracking leans on airflow measurements that are seldom accurate in the field, while direct pressure control senses the building and adjusts relief to match. On a direct pressure system, the building pressure sensor and its outdoor reference port matter as much as the drive. Put the outdoor reference where wind does not swing it.
Keep the return fan and the relief path straight. On some jobs the return fan holds return or relief plenum pressure while the relief damper or a relief fan holds building pressure. On others the return fan follows building pressure directly. Each arrangement has its own loops, and they are tuned differently.
Whichever method the job uses, find it in the sequence before you tune anything. Return fan hunting often comes from two loops fighting: the return fan loop and the relief or outdoor air damper loop. Trend return fan speed, relief damper position, outdoor air damper position and building pressure together through a load change. If the dampers and the fan are chasing each other, retuning the fan alone moves the hunting around.
Exhaust fans
General and toilet exhaust fans on drives usually hold a space pressure or a fixed airflow. Check three things:
- The minimum. Code and design minimum exhaust come first. Set the drive’s minimum speed so the fan never drops below it.
- The emergency sequence. Some exhaust fans have a role in smoke control or in a lab or kitchen emergency. Find out what the fan does in each mode and test it with the people who own that sequence.
- Interlocks. If the exhaust fan has to prove a damper open before it runs, or has to run whenever the supply fan runs, wire and test those interlocks.
Drive setup on air handler fans
- Ramps. Fan wheels carry a lot of inertia. My starting point is 60 seconds, and 90 seconds or more on fans of 100 HP and up, then I adjust from what the fan and drive show: motor current against the current limit on the way up, DC bus voltage on the way down. Check the fan maker’s requirements too. Too fast on the way up trips overcurrent, and too fast on the way down regenerates and trips overvoltage. The note on overvoltage faults covers the decel side.
- Flying start. A return or exhaust fan that is stopped while the supply fan runs can windmill, sometimes backward. Turn on flying start where the design expects the drive to start into a spinning fan, or start the fans together. A fan turning backward is harder to catch than one coasting forward, so test the start with the fan actually windmilling the way it does on the job.
- Minimum and maximum speed. Set them from the design’s minimum supply airflow, the outdoor air ventilation the sequence has to hold at that airflow, and the fan and motor limits. Minimum supply air and minimum outdoor air are related but they are not the same number. Write down where each one came from.
- Damper interlocks. Hold the fan until the damper proves open. On ABB jobs, the ACH580 has start interlocks and a run permissive, and its damper control can power the actuator on a start command, wait for the end switch, and only then ramp the fan.
- Sensor and communication loss. Decide what the fan does if the static sensor fails or the BAS goes quiet. A supply fan running to full speed on a dead sensor can blow ductwork apart if the high static switch is not wired.
- Belt loss. A broken belt shows up as a motor running with almost no load. Drives with an underload or load curve function can flag it. ABB’s guidance for the ACH580 is to watch motor torque instead of current, because below about 66% speed a loaded and an unloaded motor draw nearly the same current, while torque still separates them. Set the limit from torque readings taken across the real speed range after the fan is balanced.
- Fan arrays. Several small fans on one drive, or one drive per fan, change the setup. The note on ECM vs VFD for HVAC fans covers arrays.
What it saves
Slowing a fan saves power compared with throttling one at full speed, and resetting the static setpoint saves more on top of that. When Lawrence Berkeley National Laboratory looked at Guideline 36 sequences on 17 projects, they measured HVAC energy savings from 2% to 49%, with a median of 18%. The drive makes those sequences possible, and the sequence decides how much the building saves. The note on what a VFD saves covers the fan math.
Before you leave the site
Write down the duct static sensor location and the setpoint or reset range, which method controls the return fan and its setpoints, the building pressure sensor location if there is one, each fan’s minimum and maximum speed, the ramps, flying start, the interlocks tested, and what each fan does on sensor and comm loss. Watch the supply and return fans together for a while at a couple of load conditions, so hunting shows up before you leave instead of after.
Setting up fan control on an ABB 580 drive is covered in the ABB 580 start-up class at The Tolbert School. The HVAC drives guide covers the rest of the building.
Frequently Asked Questions
What does the supply fan VFD control on a VAV air handler?
Duct static pressure, measured by a sensor in the main supply duct. The BAS or the drive holds the pressure at a setpoint, and the VAV boxes take what they need from it. A reset that lowers the setpoint until the most open VAV damper is nearly wide open lets the fan run slower for much of the day.
Where should the duct static pressure sensor go?
Where the design puts it. Energy code language asks for a location where the setpoint can be 1.2 inches w.c. or less, with a sensor on each major branch if needed, and about two-thirds of the way down the main supply duct is the traditional starting point. A sensor right at the fan discharge sees turbulence and has to hold pressure for the whole duct run.
How is a return fan controlled on a VAV system?
Three common ways: speed tracking, where the return fan follows the supply fan speed with an offset; airflow tracking, where airflow stations hold a fixed difference between supply and return airflow; and direct building pressure control. ASHRAE Guideline 36 includes all three. Tracking depends on accurate airflow measurement, and direct pressure control watches the building itself.
Why does my supply fan run at full speed all the time?
Common causes are a failed or miswired duct static sensor reading low, a setpoint that was never reset from its start-up value, a sensor tube that is kinked or disconnected, or a rogue zone whose VAV damper is wide open all day and holds the reset up. Check the sensor reading against a gauge first.
Do return fans need flying start on a VFD?
Often. A return or exhaust fan that is stopped while the supply fan runs can windmill, sometimes backward. Starting it from zero speed can trip the drive on overcurrent. Flying start, a start sequence that brings the fans up together, or a damper that stops the backflow solves it.