Field note

HVAC VFD Commissioning Checklist: 12 Tests Before Handover

The air handler runs at turnover. The drive is on, the fan is turning, the BAS graphic shows a speed. Then summer comes and the supply fan hunts all afternoon, or a tower fan rattles its gearbox at one speed every evening, or the drive goes to full speed every time a controller reboots. Each of those traces back to a test nobody ran before handover.

This list starts where the install checks stop. Wiring, grounding, torque, the megger test and first power are covered in the pre-startup checklist and the commissioning guide. Do those first. The 12 tests below are the ones an HVAC job adds on top.

Who owns the loop

1. Write down which device runs the PID loop. On some jobs the BAS reads the sensor, runs the loop and sends the drive a speed command. On others the BAS sends a setpoint and the drive runs its own PID loop from a sensor wired to it. Either setup works, and trouble starts when both are set up to run a loop, or when the person tuning the BAS thinks the drive is in speed mode and it is in PID mode. Find out which one the sequence of operations calls for, confirm the drive is set up that way, and write it on the start-up record.

2. Check the sensor scaling at both ends. The duct static sensor, the DP sensor or the temperature sensor has a range, and the device reading it has to agree. ABB’s own start-up review checklist calls out analog inputs set to voltage or current with the right switch setting and scaled for the process. Read the sensor’s actual value on a gauge or meter and compare it with what the drive and the BAS display. A 0 to 5 inch sensor read as 0 to 2 inches will run a fan to a pressure nobody asked for. Where the duct static sensor sits matters as much as its scaling, and the note on AHU supply, return and exhaust fan VFDs covers placement and the reset.

3. Watch the loop run. Put the system in Auto and watch the speed for several minutes at a few load conditions. A loop that swings the fan up and down every few seconds is mistuned, or both devices are running a loop. A loop that never settles at low load may be hitting the minimum speed. Fix it now, while you are standing there, because a hunting fan reads as a comfort complaint months later and nobody connects it to the drive.

Speed limits, ramps and restart

4. Set minimum and maximum speed to the equipment, not the defaults. The minimum comes from the fan or pump, the outdoor air requirement, the chiller’s minimum flow and the tower maker’s limits. The maximum comes from the fan wheel and the motor. ABB’s start-up review checklist lists both the speed reference limits and the speed limits as separate items, and both matter. Record where each number came from.

5. Check the ramps. A chilled water pump that ramps too fast can drop flow through the chiller faster than the chiller tolerates. A large fan that ramps down too fast can regenerate and trip the drive on overvoltage. Set the ramps to the equipment, then start and stop the unit from Auto and watch it.

6. Test restart. Find out what the sequence wants after a power loss: an automatic restart, a start only when the BAS calls, or a wait. Then test what the drive does when power returns. Return and exhaust fans often windmill from other fans in the system, sometimes backward, so check that the drive can start into a spinning fan if that is what the design expects. The commissioning checklist has a line for each of these.

Cooling towers

7. Run the resonance sweep the tower maker describes. Every tower has speeds where the fan, the shaft or the structure resonates. BAC’s VFD vibration troubleshooting sheet steps the fan from 15 Hz up to 50 or 60 Hz in 1 or 2 Hz steps, waits about 20 seconds at each one, and blocks any band where the unit vibrates. Some BAC manuals give a vibration number for that sweep. Use the procedure written for the tower in front of you, program the bands into the drive as skip frequencies, and write them down. Marley’s own drive package manual has a line on its start-up form to record critical speed lockouts, so it is a normal part of tower start-up. The note on cooling tower VFD setup walks through the full sweep, minimum speeds and de-ice limits.

8. Set the tower’s control mode, cold weather and de-ice settings from its manual. Tower makers say what drive setup they want for their gearboxes and fans, and it is not the same across makers or packages. Marley’s packaged drive manual, built on an ABB drive, tells the installer to set the motor control to DTC. On that package de-ice comes disabled from the factory and has to be turned on, and when it runs the fan reverses at half speed for a set time. Read the tower manual before you change anything in the drive, and set any reverse or de-ice function to the limits it gives.

The BAS

9. Read back every point. Speed command, actual speed, run status, current, kW, fault, Hand/Off/Auto status, and anything else the points list calls for. Check each value at the BAS against what the drive’s keypad shows at the same moment. A point that reads zero or never changes is mapped wrong. The address, baud rate and protocol settings that cause most of these problems are covered in the note on VFD communication faults, and the ACH580 setup is in ACH580 BACnet MS/TP setup and troubleshooting.

10. Test the failures on purpose. Pull the sensor wire and see what the drive or the BAS does. Pull the communication cable on a running unit and watch it. The drive should do what the sequence says: hold last speed, go to a preset speed, or stop. Marley’s packaged drive is a good example of a defined answer: when its remote speed reference is lost, it runs the fan at 14 Hz until the signal comes back. Whatever the answer is on your job, it should be a decision someone made and you tested.

Bypass and smoke control

11. Test the bypass and the smoke control sequence with the people who own them. This is where specs and equipment disagree. On ABB’s E-Clipse bypass, Override 1 is fixed: it runs the motor across the line, follows high priority safeties and ignores low priority ones. Override 2 is configurable, so whoever sets it up chooses which faults, safeties and enables it keeps watching. Both always honor the bypass motor overload. If the owner spec says every interlock stays live in fire mode, check the installed setup against that sentence. Test the sequence the fire marshal approved, with the life safety contractor there, and never by jumping out a safety yourself. The note on VFD fire mode and smoke control override covers what each mode ignores and what still stops it.

While you are at the bypass, run the motor across the line once. It starts at full voltage and runs at 60 Hz, so check that the duct and the dampers can take full speed before anyone relies on it in an emergency.

Then test the transfer itself. When a drive faults with the fan running at 40 Hz, the bypass puts the coasting motor on the line at 60 Hz, and that jump is a current and torque transient. Watch the upstream breaker and the coupling the first time it happens. An electronic bypass such as ABB’s E-Clipse has its own controller that can refuse to transfer when the drive has detected a motor fault, keeps the BAS points alive while in bypass, and keeps damper and interlock I/O working with the drive pulled out for repair. Those features need to be set up and tested like everything else. On a fan or pump that cannot go down, a running spare avoids the transfer altogether, and the note on VFD bypass vs N+1 has the reliability numbers behind that choice.

The record

12. Leave a record the next tech can use. For each drive, write down the numbers below, save the parameter file, and note anything that does not match the drawings.

RecordWhy
Who owns the loop, setpoint and sensor rangeThe first question on every callback
Minimum and maximum speed, and where each came fromStops the next person from guessing
Ramps, restart setting and comm loss actionProves the failures were tested
Skip frequency bands on towersThe sweep takes time; nobody should redo it blind
Speed, current and kW at a known operating pointA baseline for trending
Megger readings and test voltageThe reference for the next insulation test
Saved parameter file and firmware versionLets you rebuild the drive after a failure

Put a copy in the panel, a copy in the owner’s maintenance system, and keep one yourself.

Before you leave the site

Put every drive back in Auto. A drive left in Hand after testing runs at whatever speed you left it, ignores the BAS, and looks fine on the graphic until someone notices the fan never slows down. Walk the units one more time with the BAS operator watching the graphics, and get their name on the record.

The setup behind tests 1 through 10 on an ABB ACH580 is covered step by step in the ABB 580 start-up class at The Tolbert School. The HVAC drives guide covers what the drive controls on each load and what it really saves.

Frequently Asked Questions

What should be tested when commissioning an HVAC VFD?

After the install checks and the megger test, test who owns the control loop, the sensor scaling, the minimum and maximum speeds, the ramps and restart behavior, the resonance sweep on cooling towers, every BAS point, the response to sensor failure and communication loss, Hand mode, and the bypass and smoke control sequence. Record the results so the next tech has a baseline.

Should the BAS or the VFD run the PID loop?

Either can work. What matters is that only one of them runs it, and that everyone knows which one. If both are set up to run a loop, they fight each other and the fan or pump hunts. Write down which device owns the loop, what signal sets speed, and what happens when the sensor or the network fails.

How do you find the skip frequencies on a cooling tower fan?

Run the speed sweep the tower maker's manual describes. BAC's VFD vibration troubleshooting sheet steps from 15 Hz up to 50 or 60 Hz in 1 or 2 Hz steps, waiting about 20 seconds at each step, and blocks any band where the unit vibrates. Some BAC manuals give a vibration limit for the sweep; use the one written for your unit.

What should an HVAC drive do on loss of communication?

Whatever the sequence of operations says: hold last speed, go to a preset speed, or stop. Find out which one the design calls for, set it, and then test it by pulling the communication cable on a running unit.

Does fire mode on a VFD bypass all the safeties?

It depends on the package and how it was set up. On ABB's E-Clipse bypass, Override 1 is fixed and follows high priority safeties while ignoring low priority ones, and Override 2 is configurable. Both always honor the bypass motor overload. Test the installed setup against the smoke control sequence the fire marshal approved.

Online start-up courses, filmed on real drives

One drive per course, filmed uncut with a clock on screen from first power to a saved backup. The install course is free, and the ABB ACS380 and ACS580 start-up course is open now.

See the online courses

Wayward Leaders® is a veteran-owned VFD training practice. We teach maintenance teams and plant electricians to install, commission, and troubleshoot variable frequency drives correctly.

Every class ends with a scored competency assessment. The plant gets a way to prove what each technician can do, not a roster of who sat in the room.

The instruction is field-trained. It is drawn from nearly 8,000 VFD, power, and motor documents and from more than 750 commissioned drives captured through personal field experience and data collection. Carl Lee Tolbert, PhD, CMRP, and ATD Master Trainer™, leads it. He has delivered more than 5,000 hours of VFD instruction across 30 years and trained 8,000 industrial professionals, from International Paper to the U.S. Navy.

The premise is simple: VFDs do not fail. Installations fail them. The curriculum is built backward from that.

Installation, commissioning, troubleshooting, and fault diagnosis guides are published openly at waywardleaders.com.