Field note

Cooling Tower VFD Setup: Speed Limits, Resonance and De-Ice

The tower runs fine all summer at full speed. In April the load drops, the temperature loop settles the fan at a speed it never ran at before, and the deck starts to shake. Or the fan on a gear drive spends the night at a few hertz because nobody set a minimum, and the gearbox runs below the speed it was built for. A tower fan on a drive needs a short list of settings the tower maker cares about, and the defaults in the drive do not know any of them.

This note covers the tower side. The general HVAC start-up tests are in the HVAC VFD commissioning checklist, and the install and megger checks are in the pre-startup checklist.

Start with the tower manual

The tower maker writes the rules for its fan, gearbox and structure, and those rules beat any drive default. Before you change anything in the drive, find the tower’s operation and maintenance manual and look for four things: minimum speed, the resonance procedure, reverse or de-ice limits, and the motor requirement. BAC’s manual, for example, requires inverter duty motors built to NEMA MG 1 Part 31 on any unit controlled by a VFD.

Minimum speed depends on the drive type

Tower makerDrive typeMinimum speed in the maker’s document
BACBelt drive10:1 turndown (6 Hz)
BACGear drive4:1 turndown (15 Hz), and standard gear drives not below 450 RPM motor speed
BACGear drive with oil pumpNo minimum speed
EVAPCOOpen towers, closed circuit coolers, evaporative condensers25% of motor speed

EVAPCO adds that running below 25% buys very little in fan energy or capacity control, so a low minimum gains you almost nothing. Set the drive’s minimum speed to the tower maker’s number and write down where it came from.

The motor side is easy on a tower. A fan unloads as it slows, so the motor makes less heat at the same time its shaft fan moves less air. Low speed overheating is a problem on constant torque loads like conveyors.

Find the resonance bands and lock them out

Every tower has speeds where the fan, the drive train or the structure resonates. A fan running at a constant speed has never found them. A fan on a drive can sit on one of them for hours. BAC’s manual says to find these bands at start-up and lock them out, and it gives the procedure:

  1. Check the ambient vibration with the fan off. BAC says to find and fix the cause if it is above 0.05 inches per second before going on.
  2. Raise the speed slowly from the minimum to full speed, about 1 RPM every 5 to 10 seconds, while watching vibration.
  3. When vibration approaches 0.35 inches per second, zero to peak, zero in on that speed and record it as the start of a band. Keep going until vibration drops back and record the end.
  4. Program each band into the drive as a skip frequency and write the bands on the start-up record.

BAC’s VFD vibration troubleshooting sheet gives a faster version: step from 15 Hz up to 50 or 60 Hz in 1 or 2 Hz steps, about 20 seconds at each step, and block any frequency where the unit vibrates. Other makers have their own procedure. Use the one written for the tower in front of you, and use a vibration meter, because a hand on the rail cannot read 0.35.

Control mode, ramps and the temperature loop

Set the motor control the way the tower package calls for. Marley’s packaged tower drive, built on an ABB ACS800, tells the installer to set the motor control to DTC. A standalone drive on a tower fan is set up for a variable torque load: the normal duty rating allows about 110% current for 60 seconds, which is enough for a fan.

Fans carry a lot of inertia in the wheel. A starting point for ramps on fans is 60 seconds, and 90 seconds or more on fans of 100 HP and up. A ramp that is too fast trips overcurrent on the way up, and on the way down it turns the motor into a generator and trips overvoltage. The note on overvoltage faults covers the decel side.

The tower holds condenser water supply temperature. Find out whether the BAS runs that loop and sends a speed command, or the drive runs it. Marley’s package runs a temperature PID loop inside the drive in Auto. If the speed reference from the BAS is lost on that package, it runs the fan at 14 Hz until the signal returns. BAC also says capacity should be controlled with the fans, not by changing the water flow to the tower.

Cable to the fan deck

Tower motors sit on the deck and the drive usually sits in a mechanical room or at grade, so the motor leads are long. Marley’s package manual recommends a motor output filter when the actual wire length from drive to motor is over 100 feet, because the drive is sensitive to cable capacitance and can trip on it. The same manual says no lightning arrestors or power factor correction capacitors on the drive output, and no mineral insulated cable.

Without a package rule, a reasonable starting point is an output reactor under about 250 feet and a dV/dt filter from 250 to about 500 feet, with a sine wave filter beyond that or on a motor that is not inverter rated. A tower maker’s number for its own package wins. The notes on reflected wave and long motor leads and dV/dt filter vs load reactor go deeper.

Reverse and de-ice

Running the fan in reverse is the usual de-icing method, and BAC limits it: no longer than 20 minutes, only after other methods of fan control fail, and the fan comes to a complete stop before it restarts in the other direction. Marley’s packaged drive ships with de-ice turned off, and when it is turned on it reverses the fan at half speed for a set time before going back to normal. Set the time and speed to the tower manual, and set the drive so it stops the fan fully before every direction change.

Trips and what usually causes them

SymptomUsual causeCheck
Vibration at one speed every dayA resonance band that was never locked outRun the sweep and add the skip band
Overcurrent on startFan windmilling from wind or the next cell, sometimes backwardFlying start, start sequencing, or dampers between cells
Overvoltage on decelRamp too fast for the fan inertiaLonger decel ramp, then look at braking if the process needs a fast stop
Trips with long leads, worse when wetCable capacitance or insulationFilter for the length, megger the cable and motor
Fan stuck at one low speedLost speed reference, drive running its fallback speedThe BAS signal and the comm loss setting
Gearbox noise at low speedRunning below the gear minimumMinimum speed against the tower manual

Before you leave the site

Write down the minimum speed and its source, every skip band, the ramps, the de-ice settings, the cable length and filter, and the megger readings. Save the parameter file. The sweep takes time, and the next tech should never have to guess where the bands are.

Setting these up on an ABB drive is covered in the ABB 580 start-up class at The Tolbert School. The HVAC drives guide covers the rest of the building.

Frequently Asked Questions

What is the minimum speed for a cooling tower fan on a VFD?

It depends on the tower maker and the drive type. BAC's maintenance manual gives 10:1 (6 Hz) for belt drive and 4:1 (15 Hz) for gear drive, with no minimum on units that have the gear oil pump, and says not to run standard gear drives below 450 RPM motor speed. EVAPCO recommends 25% of motor speed. Use the number in the manual for your tower.

How do you find the resonant speeds on a cooling tower?

Sweep the fan slowly through its speed range while watching vibration. BAC's manual calls for about 1 RPM increase every 5 to 10 seconds, and when vibration approaches 0.35 inches per second zero to peak, you zero in on that speed and record the bounds of the band. Lock each band out in the drive as a skip frequency.

How long can a cooling tower fan run in reverse for de-icing?

BAC says no longer than 20 minutes, and only after other methods of fan control have failed. Let the fan come to a complete stop before reversing. Packaged tower drives often have a de-ice function with its own time and speed settings, so check the tower manual.

Does a cooling tower VFD need an inverter duty motor?

BAC requires inverter duty motors built to NEMA MG 1 Part 31 on towers controlled by a VFD. Long cable runs to the fan deck make the insulation matter more, so check the filter requirement for your cable length too.

Why does my cooling tower drive trip on overcurrent at start?

A common cause is a fan that is already turning, windmilled by wind or by the neighboring cell, sometimes backward. The drive tries to start it from zero speed and trips. Flying start, coordinated start sequencing, or dampers between cells fix it.

Online start-up courses, filmed on real drives

One drive per course, filmed uncut with a clock on screen from first power to a saved backup. The install course is free, and the ABB ACS380 and ACS580 start-up course is open now.

See the online courses

Wayward Leaders® is a veteran-owned VFD training practice. We teach maintenance teams and plant electricians to install, commission, and troubleshoot variable frequency drives correctly.

Every class ends with a scored competency assessment. The plant gets a way to prove what each technician can do, not a roster of who sat in the room.

The instruction is field-trained. It is drawn from nearly 8,000 VFD, power, and motor documents and from more than 750 commissioned drives captured through personal field experience and data collection. Carl Lee Tolbert, PhD, CMRP, and ATD Master Trainer™, leads it. He has delivered more than 5,000 hours of VFD instruction across 30 years and trained 8,000 industrial professionals, from International Paper to the U.S. Navy.

The premise is simple: VFDs do not fail. Installations fail them. The curriculum is built backward from that.

Installation, commissioning, troubleshooting, and fault diagnosis guides are published openly at waywardleaders.com.