A CDU (coolant distribution unit) is the pump skid that moves coolant through the server cold plates in a liquid cooled data center. In a liquid to liquid system it sits between the facility water and the server loop, with a heat exchanger between them. Its pumps run at variable speed, usually holding a differential pressure, while a valve on the building side holds the coolant supply temperature. The pumps are redundant for a reason: ASHRAE puts the time for liquid cooled servers to start throttling after losing flow on the order of 30 seconds at full load.
This note covers what the spec sheets don’t: how the pumps are controlled, what to check in the pump drive, how the redundancy really works, and what happens to flow when the power drops.
What a CDU does
Two fluid loops meet inside a liquid to liquid CDU. ASHRAE’s names for them are the ones the makers use on their spec sheets:
- FWS, the facility water system. The building’s water, from chillers, cooling towers or dry coolers, depending on the design.
- TCS, the technology cooling system. The loop the CDU pumps through the racks, the manifolds and the cold plates on the chips. It is often treated water and sometimes a glycol mix: Motivair rates its CDUs with 25 percent propylene glycol on the server side.
A plate heat exchanger moves the heat from the TCS to the FWS and keeps the two loops apart. That separation lets the server side run cleaner fluid at a controlled pressure and temperature than the building’s water could give it. On the TCS side the CDU has the pumps, the filters, an expansion tank or reservoir, and the sensors. On the FWS side it has a control valve.
CDUs come in a few shapes. In-rack units sit inside a server rack and feed that rack, and some of them control on local flow or temperature instead of a loop differential pressure. In-row units sit at the end of a row or in the row like a rack and feed many racks through manifolds. The larger standalone units now run into the megawatts. Liquid to air CDUs reject the heat into the room with fans instead of to facility water, which helps on a retrofit with no water to the white space. On those, skip the FWS parts of this note, and add the fans to everything said here about power and restart.
What’s inside the CDU
The pumps. Two or three of them is common. Vertiv’s CoolChip CDU 600 and 2300 have twin pumps, and the CDU 1350 has three. CoolIT’s CHx1500 has two hot swappable pumps. Each pump has its own motor and its own speed control: integrated variable speed drives on nVent’s CDU800, redundant variable speed drives on Motivair’s units, VSD centrifugal pumps on Rittal’s in-row CDU, and an inverter and speed controller per pump on Vertiv’s. Vertiv also puts a check valve and isolation valves on each pump, so one pump can be serviced while the other runs.
The FWS control valve. It throttles facility water through the heat exchanger to hold the TCS supply temperature at its setpoint. On Vertiv’s spec the controller can also raise that setpoint to stay above the room’s dew point so the pipes do not sweat.
The filters. The channels in a cold plate are small, so the TCS gets fine filtration on the full flow. Vertiv lists 25 or 50 micron filters on the TCS side, one per pump, with a differential pressure alarm when they need cleaning. CoolIT lists 25 micron hot swappable filters with a 50 micron option. Some designs add a side stream filter that polishes a small part of the flow much finer: the nVent CDU built on Google’s Deschutes spec lists 0.2 micron side stream filtration on top of its main filters.
The sensors. Pressure on the TCS supply and return, temperature on both loops, and flow. Vertiv uses redundant pressure sensors on the TCS supply and return and triple redundant temperature sensors on the TCS supply. Those sensors run the pumps and the valve, so a bad one can starve the racks as surely as a bad pump.
The controller. It owns the pump speed, the valve, pump rotation, alarms, and how the CDU talks to the building management system. CoolIT’s controller can run up to 20 units as a group.
How the pumps are controlled
On Vertiv’s CDUs the pump speed is regulated to a setpoint by the CDU controller, and in differential pressure mode it uses the TCS supply and return pressure sensors. That is the common pattern on in-row units: the pumps hold a pressure difference across the server loop, the server manifolds and the cold plates take the flow they need, and the valve on the FWS side holds the supply temperature. Some CDUs can run on flow instead, and the two modes behave differently when part of the loop closes.
- In differential pressure mode, closing a branch or a quick disconnect leaves the other branches at about the same pressure difference. Total flow drops and the pumps slow down.
- In flow mode, the controller holds total flow. Close a branch and the remaining branches get more flow, and the loop pressure climbs toward its limit.
That is what a drive tech is on site to watch, so find out which mode the job uses and why before anyone adds racks or closes valves. Then check the same things as on any pressure loop:
- The sensors. Scaling, location, and which sensor wins when the redundant pair disagrees. In differential pressure mode a reading that drifts high makes the pumps run slow. A supply transmitter drifting high does that, and a return transmitter drifting high does the opposite, so find which transmitter is drifting before you trust the trend.
- Where the sensors sit against the filters. If the supply pressure sensor is after the filters, a loading filter adds head inside the span the controller measures, and the pumps speed up to hold the setpoint while they have speed left. If the sensor is before the filters, the controller never sees the filter. Speed stays flat while flow to the racks falls, which is the more dangerous case. Find out where the sensor is.
- The pump limits. Minimum and maximum speed from the pump curve and the server loop’s pressure limits, not from the motor. Cold plates and quick disconnects have pressure ratings, and the CDU maker sets the TCS pressure limits to protect them. A glycol loop is thicker than water, which shifts the pump curve and the speeds you end up with.
- Minimum flow. A large CDU feeding a few racks on day one, or a loop with most quick disconnects closed, can push the pumps toward dead head. The CDU needs a bypass, a minimum flow limit or the maker’s low demand logic, or the pumps churn and wear their seals.
- The valve and the pump together. If supply temperature is off, check the FWS side, the facility water temperature and the valve, before blaming the pumps.
What to check in the pump drive
Whatever the drive is called on the spec sheet, a few things decide how the pumps behave on a bad day.
Who owns the speed loop. On some CDUs the controller runs the PID and sends each drive a speed reference, over an analog signal or a network. On others the drive runs its own PID from the sensor. The two behave differently when the network drops, when the controller reboots and when power comes back. Find out which it is, and find out who owns the restart. If the drive and the controller both try to restart a pump, they can fight each other.
What the drive does through a power interruption. There are four things it can do: ride through on undervoltage control or kinetic buffering, coast and restart on its own, catch the still spinning pump with flying start, or trip and wait for someone to reset it. The last one defeats the redundancy. Check which one the drive is set for, and how long the real interruption is, including the open transition time of any ATS. On ABB’s ACQ580 and ACH580 that means the undervoltage control, automatic restart and start mode settings, checked against the firmware manual for the drive’s control program and revision.
The ramp after a restart. A fast ramp gets flow back sooner. It can also push the loop past its pressure limits or slam the check valves. Set it with the CDU maker’s pressure limits in hand, and watch it on the loss of power test.
Two pumps running together. Check whether they share one speed reference or run separate loops, what their minimum speed is, and whether they hunt against each other.
DC input. Where a CDU takes DC, as Rittal’s in-row CDU can at 240 to 380 V DC, the pump drives run from a DC bus with no AC rectifier on that input. Ride-through, precharge and harmonics are different questions there, and the CDU maker’s manual is the place to answer them.
Redundancy is a capacity question
N is the pumping capacity the loop needs at its design flow and head. N+1 adds one spare. N+N, or 2N, adds a full second set. Vertiv calls its twin pump CDUs N+N, with one pump running and one on standby, or both running together. Plenty of engineers would call one duty pump with one full size standby N+1 or 1+1, so read the maker’s words against the pump curve. Vertiv’s three pump CDU 1350 runs N+1, and in that mode the pumps change over automatically every week to even out run time. CoolIT’s CHx1500 is N+N with hot swappable pumps. Above the single unit, sites add whole CDUs: Motivair’s design for AMD’s Helios racks uses three MCDU-70s per AI pod in an N+1 arrangement.
Running both pumps together is only redundant if either pump can carry the design flow and head alone. If both are needed at full load, there is no spare at full load.
Redundancy only counts if the swap works. The standby or remaining pump has to pick up the flow before the servers notice, and the check valve on the failed pump has to close so the running pump does not just push coolant backward through it. Prove it at commissioning with an approved test of automatic failover, with limits and abort criteria agreed first. A normal stop command may not run the same logic as a drive fault, so ask the CDU maker how to make the test look like a real failure. Test it both ways: the standby taking over from a running pump, and one pump dropping while both run. Then watch the weekly changeover once, if the CDU has one, because a changeover that dips flow every week is a problem on every rack it feeds.
How long the chips can wait
Air cooled rooms gave the cooling a little time. ASHRAE says the thermal ride-through of air cooled data centers typically allowed at least 1 minute, and often several minutes, of cooling outage. Liquid cooling allows much less. ASHRAE gives the time for hybrid and liquid cooled servers to start throttling after losing liquid flow as on the order of 30 seconds at full CPU load. Separately, Uptime Institute says a cooling failure in water or single phase dielectric cold plate systems may give less than 10 seconds of ride-through. Those are two different measures from two different sources, and throttling is not shutdown or damage. The IT vendor’s minimum flow and interruption limits for the equipment on the job are the numbers that count.
Now put that next to the power system. Under NFPA 110, a Level 1, Type 10 emergency power system allows up to 10 seconds without acceptable power at the transfer switch. Not every data center’s generator plant is built that way, so find out what the site has. And Type 10 says when power comes back, not flow. Flow comes back after the power, the drive restart or flying start, the ramp, the check valves opening and the loop pressure building. ASHRAE notes that cooling standby power practice has typically not put chillers, pumps and other cooling components on UPS, and warns that the existing approach is likely to fail to protect liquid cooled systems.
The makers and designers are answering that in a few ways:
- UPS power for the pumps. Motivair’s design for the Helios racks puts the CDUs and the facility pumps on UPS power, with five minutes of thermal storage at maximum cooling capacity for that design. Uptime Institute names a UPS on the coolant pumps as one of the options operators should consider.
- Ride-through built into the CDU. CoolIT says its CHx1500 has an integrated ultracapacitor for interruption free operation.
- Two power feeds. Vertiv offers an optional factory fitted ATS that runs on supply A, switches to supply B if A fails, and switches back when A returns. CoolIT offers an optional ATS too. The nVent CDU built on Google’s Deschutes spec has fully redundant power feeds for each pump circuit.
Each of those has a question for the drive tech. With an ATS inside the CDU, what do the pump drives do during the switch time? With an ultracapacitor, how long does it carry the pumps at the actual load, and what is the maker’s discharge procedure? Treat it as charged until that procedure says otherwise. With UPS power, is the CDU controller on the same UPS as the pumps, so the pumps do not run blind? And on any CDU, what happens when power comes back after a full loss? Vertiv’s spec says that after a reboot the pumps return to the last known speed and the FWS valve to its last known position. That is the specified behavior. After a long outage the IT load, the facility water temperature or a failed pump may have changed, so verify on the loss of power test that it restores cooling within the system’s limits.
The FWS side matters too. A CDU on UPS power keeps the server loop moving, but the heat exchanger still needs facility water. If the facility pumps and chillers are on generator only, the TCS temperature climbs until they come back, and the thermal storage, if there is any, has to cover that gap. The note on CRAH units and the generator transfer goes through that restart chain on the air side.
Power, harmonics and what else to check
Input power. Know what feeds each pump: one feed, two feeds through an ATS, or a separate feed per pump circuit. Check the supply voltage against the nameplate. Rittal’s in-row CDU, for example, lists AC input options and a 240 to 380 V DC option, so read the spec for the unit in front of you.
800 VDC is starting to reach the CDU. Delta announced an 800 VDC powered 2.5 MW in-row CDU in November 2026, with three 800 VDC 25 kW hot swappable pumps in a 3+0 configuration, which means no spare pump inside that unit. Nidec lists an 800 VDC input option on its 3.2 MW in-row CDU and marks it as under evaluation. Vertiv lists 480 V three phase AC input on its CoolChip CDU 1350. On a DC fed pump the drive questions change: which voltage class the pump drive is, how it precharges from a live bus, how each tap is fused, and where the energy goes when the pump slows down. A 480 V class drive’s published DC input limits stop short of an 800 V bus, and its overvoltage trip sits close to it, so a DC fed pump needs a drive rated for that bus in writing. That subject gets its own note.
Harmonics. A few large CDUs add up to a lot of drive load on one bus. On generator power the drives draw about the same harmonic current, but the generator’s higher source impedance turns it into more voltage distortion. Some designs answer it at the drive: nVent’s Deschutes based CDU uses ultra low harmonic VFDs and lists IEEE 519 on its spec. That describes the drive. Compliance at the site’s point of common coupling is still decided by the site’s harmonic study.
Leak detection. Vertiv’s CDUs have a drip tray and internal leak detection that can be set to alarm only, or to alarm and shut down, with an optional leak cable along the server loop. That setting deserves a conversation with the owner before start-up. A CDU that shuts its pumps on a small drip stops cooling to every rack it feeds. A CDU that only alarms keeps cooling while the leak goes on. The owner picks, it gets written down, and it gets tested.
Communication. The CDUs in this note report to the building management system over the network with protocols such as SNMP and Modbus. Verify that a loss of BMS communication leaves the CDU in its approved local control mode and does not bypass its protective shutdowns.
The rest of the start-up list is the same as any pump drive: rotation on each pump, terminations, speed limits, ramps, and alarm and fault points read back at the BMS. Megger only where the pump motors are field wired, with the motor leads lifted off the drive, and follow the CDU maker’s procedure. Meggering through a drive can damage its output stage, and factory wired skid motors may not be meant to be meggered in the field at all. Air in the loop matters as much as the wiring: a CDU filled without venting can starve a rack or run a pump dry. The maker’s fill and venting procedure comes before the pumps run at speed.
Before you leave the site
On every CDU, record:
- The pump arrangement (N+N or N+1 in the maker’s terms, run and standby or all running), whether one pump can carry the design flow and head alone, and the changeover schedule.
- The control mode (differential pressure or flow), the setpoint, and the pressure limits the CDU maker set for the server loop.
- Which sensors run the pumps, their scaling, where the supply pressure sensor sits against the filters, and what the controller does when a redundant pair disagrees.
- Who owns the speed PID and the restart, the CDU controller or the drive.
- The drive’s restart, ride-through and flying start settings, and the ramp times.
- The minimum flow protection or bypass for light loads.
- The filter rating and the filter differential pressure alarm point, with the pump speed and filter reading at handover as a baseline.
- What feeds each pump and the controller: single feed, ATS, two feeds, UPS, ultracapacitor.
- During the approved pump failure and loss of power tests, a trend of TCS flow, differential pressure and supply temperature, with the minimum flow, the time below the required minimum and the time to stable recovery, compared with the agreed IT cooling limits.
- The leak detection action the owner chose, and the comm loss behavior.
- What the FWS side needs to keep running, and how long the thermal storage, if any, covers it.
The data center drives guide covers the rest of the drive work in a data center, and the water and pump drives guide covers pump control in more depth. Pump drive setup on the ACQ580 and ACH580 is covered in the ABB 580 start-up class at The Tolbert School.
Frequently Asked Questions
What is a CDU in a data center?
A coolant distribution unit. In a liquid to liquid system it sits between the building's facility water and the coolant loop that runs to the servers, usually through a plate heat exchanger. Its pumps push coolant through the server cold plates, a valve on the facility side holds the coolant supply temperature, and filters keep the small channels in the cold plates clean. Liquid to air CDUs reject the heat into the room with fans instead.
What is the difference between the FWS and the TCS?
The FWS (facility water system) is the building's water, from chillers, towers or dry coolers. The TCS (technology cooling system) is the loop the CDU pumps through the IT equipment, often water and sometimes a glycol mix. The CDU's heat exchanger keeps the two separate, so the fluid quality, pressure and temperature on the server side can be held tighter than the building's water.
Do CDU pumps use VFDs?
The pumps run at variable speed, and how the drive is packaged varies. nVent lists integrated variable speed drives on its CDU800, Motivair lists redundant variable speed drives, Rittal lists VSD centrifugal pumps, and Vertiv's CoolChip spec gives each pump its own inverter and speed controller. On large CDUs and the facility pumps behind them, the drives are often VFDs a drive tech will recognize.
How fast does liquid cooled IT equipment react to lost coolant flow?
Fast. ASHRAE gives the time for hybrid and liquid cooled servers to start throttling after loss of liquid flow as on the order of 30 seconds at full CPU load. Uptime Institute says a cooling failure in some cold plate systems may give less than 10 seconds of ride-through. Those are different measures from different sources, and throttling is not shutdown or damage, but both are far shorter than the minutes an air cooled room usually had. The IT vendor's minimum flow and interruption limits for the actual equipment are the numbers to design and test against.
Should CDU pumps be on UPS power?
It is one of the main answers designers use. A standby generator can take up to 10 seconds to pick up the load, and coolant flow comes back later than power because the pumps still have to restart and come up to speed. Some CDUs also carry their own ride-through, such as an ultracapacitor. The design engineer decides, and the start-up tech proves it works with an approved loss of power test.