The chilled water pump drive sits at 58 Hz all day in April. Nobody touched the setpoint after start-up, and the DP sensor is mounted in the mechanical room, so the drive holds enough pressure to push water around the whole building at peak load whether the building needs it or not. Two blocks over, a plant with variable primary flow trips a chiller every morning when the pumps slow down faster than the chiller tolerates. Both drives are sized right, programmed, and running without a fault. The problem is how the water system around them is controlled.
Closed loop and open loop behave differently
A chilled water loop is closed and full of water. The water going up the riser balances the water coming down, so the pump is not lifting anything to the roof. It overcomes friction in the pipe and the pressure drop through coils, valves and the chiller evaporator. Friction falls quickly as flow drops, so a chilled water pump can follow the speed curve a long way down, and it is one of the best places in a building for a drive.
A condenser water loop runs through an open cooling tower. The pump has to lift water from the tower basin up to the distribution at the top of the tower, and that lift is the same at every speed. Slowing the pump cuts friction and leaves the lift untouched, so the savings are smaller and the minimum useful speed is higher.
Where the DP sensor goes, and what it holds
On a variable flow chilled water loop, the drive holds loop differential pressure. The BAS runs the loop and sends a speed command, or the drive runs its own PID loop from the sensor. Two things set how hard the pump works:
- Where the sensor is. It belongs at the hydraulically critical location the design identifies, meaning the circuit that needs the most pressure to get its flow. That is often near the far end of the loop, though a closer coil with a high pressure drop or a different valve can be the critical one, and larger systems may need more than one sensor. A sensor at the plant has to cover the friction of the whole loop too, so its setpoint runs high and the pump runs faster all year.
- What the setpoint is. A fixed setpoint is picked for the worst hour of the year. A valve position reset, sometimes called critical valve reset, lowers the setpoint until the most open coil valve is nearly full open, so the pump runs at the lowest speed that still satisfies every coil. That reset lives in the BAS sequence, not in the drive. Check after start-up that the reset never starves the critical coil.
Primary-secondary and variable primary
In a primary-secondary plant, the primary pumps hold the required flow through each operating chiller, and variable speed secondary pumps follow the building’s demand. The primary pumps can have drives too, set to a fixed commissioned speed that delivers the chiller’s flow, instead of running at 60 Hz against a throttled balancing valve. Their job is the chiller’s flow, not the loop pressure.
In a variable primary flow plant, the chiller pumps themselves follow the building’s demand and move water through the chillers and out to the coils, with no separate distribution pumps. Flow varies through the chiller evaporators too. Trane’s modeled comparison for a 470 ton medical office building in Atlanta put annual pumping energy at 52,588 kWh for constant flow, 32,819 kWh for primary-secondary, and 26,614 kWh for variable primary. The same paper found chiller power about the same either way, so the savings are in the pumps.
The baseline matters. Against constant flow, variable primary saved 49.4% of the pumping energy in that example. Against primary-secondary, which is what it usually competes with, it saved 18.9%. Ask what the baseline was whenever someone quotes a pump savings percentage.
Variable primary asks more of the controls and the operators. Trane does not recommend it where chilled water temperature is critical, such as clean rooms and process cooling, and says operator training is mandatory.
The chiller sets the limits
On a variable primary plant, and on any plant where flow through the chiller changes, the chiller’s limits come first.
- Minimum flow. Use the minimum from the chiller submittal, with any adjustment for glycol. Below it, heat transfer drops, leaving water temperature control suffers, and the chiller can trip on low refrigerant temperature or flow protection. Depending on the evaporator, very low flow can also turn laminar in the tubes.
- A bypass. Because there is a minimum, the loop needs a bypass with a control valve that keeps enough water returning to the operating chillers when the coil valves close down. Three-way valves at some coils can do the same job, at a cost in pump savings.
- Rate of change. Trane’s published guidance for its chillers is that flow should change by no more than 10 percent of design flow per minute for tight temperature control, and that 30 percent per minute is usually acceptable for comfort cooling. Other makers publish their own limits. The drive’s ramp alone does not set this. The pump curve, the coil valves, the bypass and the number of chillers running all move the flow too.
A pump at minimum speed does not prove minimum flow
A drive running at 35 Hz tells you the pump speed, not the gallons per minute through the evaporator. Prove the flow:
| Method | What it tells you | The catch |
|---|---|---|
| Flow meter | The actual flow | It has to be installed and calibrated correctly |
| Pressure drop across the evaporator | An estimate of flow from the chiller maker’s pressure drop curve | Fouling, sensor accuracy and glycol throw it off |
| Flow switch | That flow is above a set threshold | It does not give the actual flow |
Test the bypass the same way. Run it at low building demand, and again while a second chiller is enabled and disabled. When another evaporator comes online, the flow redistributes, and if the pumps and the bypass respond slowly, the chiller that was already running can drop below its minimum for a while. Watch the flow through each running chiller during staging, and check that the bypass control loop stays stable.
Condenser water pumps
Whether the condenser pumps can vary their flow is the chiller maker’s call. Some chillers need close to fixed condenser flow, and others allow variable condenser flow within limits. Read the chiller submittal before anyone programs a condenser pump to slow down.
Condenser pumping also has to be judged as part of the whole plant. Lower condenser flow saves pump power, and it can raise the chiller’s condensing pressure and its power draw. Tower performance changes with water flow too. So the most efficient condenser pump speed is not always the lowest speed the chiller allows, and the answer comes from looking at pump, chiller and tower power together.
The tower has its own limits. Check the tower maker’s allowed water flow range for its distribution system. BAC’s maintenance manual says not to control cooling capacity on its towers by changing the water flow; the fans do that job. That is guidance on tower capacity control, and it does not rule out an engineered variable flow condenser system. Between the chiller limits, the tower’s flow range and the fixed lift to the top of the tower, a condenser pump’s drive often has a narrow working range. The note on cooling tower VFD setup covers the tower fan side.
Setting up the drive
- Minimum speed. Set it from the verified chiller minimum flow (or the bypass design), the pump maker’s minimum flow, and, on condenser pumps, the speed that still lifts water to the tower with flow to spare. Write down where the number came from.
- Ramps. Set acceleration and deceleration to the control sequence and the chiller’s allowed rate of flow change, then verify the actual flow during start-up, load changes and chiller staging.
- More than one pump. Staging pumps on and off, and alternating which pump leads, can be done in the BAS or in the drive. On ABB jobs the ACH580 has intelligent pump control and PFC for this. Pick one place to do it, then fail a pump while the system is under load, and watch which controller brings the next pump on and how fast flow recovers against the chiller’s rate of change limit.
- Sensor and communication loss. Decide with the engineer what each pump does if the DP sensor fails or the BAS goes quiet, and test both. A chilled water pump that stops can trip the chillers on low flow.
- The motor and cable. Pumps unload as they slow, so motor heating at low speed is a smaller problem than on a constant torque load. The usual drive checks still apply: inverter rated motor, cable length and filters, bearings and grounding.
What it really saves
The affinity laws describe an ideal pump on a system with no lift. Real jobs come in under them because of setpoints, minimum speeds, drive and motor losses at part load, and on condenser loops, the lift to the tower and the chiller’s response. The pump guide DOE published with the Hydraulic Institute and Europump reports 30 to 50% savings on many variable speed pump installations. A chilled water loop with the sensor in the right place and a reset setpoint can sit at the good end of that range. A condenser loop with a high lift and a fixed flow chiller may save little.
Before you leave the site
Record:
- The DP sensor location, scaling and setpoint or reset range, and what the pumps do if it fails.
- The chiller minimum flow, how flow was verified, and the flow at design and minimum conditions.
- Flow through each running chiller during staging up and down, and the bypass behavior.
- Each pump’s minimum speed and where it came from, the ramps, the staging method and the failure test result.
- Chilled water supply and return temperatures and the loop delta T.
- The condenser flow and the tower’s flow range.
- The comm loss action, and the saved drive settings.
A low loop delta T pushes more water than the coils need and keeps extra chillers running, even when every drive and pressure loop is working, so it is worth recording on day one. The HVAC VFD commissioning checklist covers the rest of the start-up, and the water and pump drives guide covers wells, boosters and lift stations, where the lift changes the picture again.
Setting up pump control on an ABB 580 drive is covered in the ABB 580 start-up class at The Tolbert School. The HVAC drives guide covers the rest of the building.
Frequently Asked Questions
Does a chilled water pump on a VFD save energy?
Usually, and more than a pump that lifts water. A closed chilled water loop is full of water, so the pump only overcomes friction and the pressure drop through coils, valves and the chiller. The savings depend on the setpoint, where the DP sensor sits, the chiller's minimum flow and the hours at part load.
Where should the differential pressure sensor go on a chilled water loop?
At the hydraulically critical location the design identifies, which is the circuit that needs the most pressure. That is often near the far end of the loop, though a closer coil with a high pressure drop can be the critical one. Larger systems may need more than one sensor.
How fast can chilled water flow change through a chiller?
It depends on the chiller. Trane's published guidance for variable primary flow is no more than 10 percent of design flow per minute for tight temperature control, and 30 percent per minute for comfort cooling. Other makers publish their own limits. Check the limit for the chiller on your job and verify actual flow during staging.
How do you verify minimum flow through a chiller?
With a flow meter if the plant has one, or by reading the pressure drop across the evaporator and checking it against the chiller maker's pressure drop curve. A flow switch only says flow is above a threshold. A pump running at its minimum speed does not prove the chiller is getting its minimum flow.
Can condenser water pumps run on a VFD?
Many can, but the chiller maker decides, and the plant has to be looked at as a whole. Lower condenser flow saves pump power and can raise chiller power, so the most efficient pump speed is not always the lowest one the chiller allows.