An air handler drive fails on a Friday. The stockroom has a 580 in the right frame size and voltage, and the label says ACS580 instead of ACH580. The two look alike from the front. Whether the ACS580 can run that air handler over the weekend depends on what the ACH580 was doing besides turning the fan, and that is where the two drives differ.
Same hardware family, different control program
ABB treats the ACS580, ACH580 and ACQ580 as one hardware family. Its installation guides for flange mounting kits and sun shields cover all three together, and some of those guides call the family ACX580. The difference is the control program. The ACS580 runs ABB’s standard control program, written for general purpose machines. The ACH580 runs the HVAC control program, written for fans, pumps and building automation. The ACQ580 runs a pump control program for water and wastewater.
The power section is familiar and the setup is different. Two drives that look the same on the shelf can arrive at an HVAC job with very different features.
Side by side
| Feature | ACH580 (HVAC control program) | ACS580 (standard control program) |
|---|---|---|
| Embedded fieldbus | BACnet MS/TP, N2 and Modbus RTU | Modbus RTU only |
| BACnet/IP | FBIP-21 adapter | Not on ABB’s FBIP-21 list |
| Starting setup | HVAC default and PID single motor configurations | 12 macros, including Hand/Auto, PID, PFC, torque control and compressor |
| Keypad | Hand-Off-Auto panel | Standard assistant panel |
| Smoke control | Override, parameter group 70 | No Override group |
| Interlocks and permissives | Dedicated HVAC start interlocks and run permissives | Run enable and start enable logic |
| Dampers | Advanced damper control, group 84 | No damper control group |
| External PID loops | 4 (groups 71 to 74) | 1 (group 71) |
| Multiple pumps or fans | Intelligent pump control and PFC | PFC |
| Bypass package | E-Clipse electronic bypass | Its own package options |
Both programs carry process PID, timed functions, energy efficiency calculators, a load analyzer, a user load curve and a communication loss action. Those are not reasons to pick one over the other.
What the ACH580 adds for a building
BACnet in the box. A BAS job usually calls for BACnet MS/TP, and the ACH580 has it built in along with N2 and Modbus RTU. ABB’s BACnet/IP adapter, the FBIP-21, is listed for the ACH480 and ACH580. The ACS580 has Modbus RTU built in and adapters for protocols such as Modbus TCP and EtherNet/IP, and BACnet is not on its list. Setting up the ACH580 on a trunk is covered in ACH580 BACnet MS/TP setup and troubleshooting.
Hand-Off-Auto at the door. Building operators expect Hand, Off and Auto buttons on the keypad, and many sequences of operations are written around them. The ACH580 panel has them.
Override in the drive. The ACH580 firmware has an Override group for smoke control sequences. When Override activates, the drive ramps to the override speed. The ACS580 standard program has no Override group. The note on VFD fire mode and smoke control override covers what Override ignores and which faults still stop it.
Interlocks, permissives and dampers. The ACS580 can stop on a run enable input and hold off a start until an enable is present, so it is not blind to safeties. The ACH580 goes further for HVAC work: dedicated start interlocks and run permissives, an example in ABB’s manual of holding the fan until a damper end switch closes, and an advanced damper control group.
Four PID loops. The ACH580 has four external PID loops besides its process PID. They can drive other devices, such as a valve, through the drive’s outputs, which helps on small jobs with no full BAS. The ACS580 has one.
An electronic bypass. The E-Clipse bypass is a separate controller, and it changes how the drive sits on the network. ABB describes the bypass controller as the communication proxy for the application, so the BAS talks to the bypass, and the bypass talks to the drive. Bypass control and status stay available to the BAS even with no working drive. The bypass refuses to transfer when the drive faulted on a motor related problem, and its pass-through I/O keeps dampers, lag pump starts and interlocks working with the drive pulled out. The bypass also has its own Override 1 and Override 2 modes, separate from the drive’s Override group. Override 1 is fixed: it runs the motor across the line, follows high priority safeties and ignores low priority ones. Override 2 is configurable, so whoever sets it up chooses which faults, safeties and enables it keeps watching. Both always honor the bypass motor overload.
It is still a 2-contactor bypass. The motor runs at full speed in bypass, and it takes a current and torque transient when it jumps from its running speed to 60 Hz. Where a bypass is specified, this kind is the better one. Where the load cannot go down at all, a running spare does better than any bypass, as the note on VFD bypass vs N+1 shows.
Ultra low harmonic versions. ABB offers ultra low harmonic versions of the ACH580, the -31 and -34, for jobs where the harmonic study calls for them.
Can the ACS580 go in on Friday?
| What the ACH580 was doing | Can an ACS580 stand in? |
|---|---|
| Hardwired start, stop and speed signal | Possibly, after the ratings, I/O and setup check out |
| Running its own duct static PID loop | Possibly, with the PID and feedback rebuilt and tested |
| On a BACnet MS/TP or N2 network | Not directly. It needs a verified integration solution or BAS changes |
| Holding the fan on dampers and interlocks | Only if the sequence can be rebuilt in its I/O or the BAS and tested |
| Part of a smoke control sequence | No. That takes engineering and life safety approval |
| Behind an E-Clipse bypass | No. The bypass is the network proxy and the package has to be evaluated as a whole |
When the network matters, remember the points list too. The BAS was mapped to the ACH580’s objects, including groups the ACS580 does not have, so even a working connection needs the mapping redone.
Before an ACS580 goes in
- Ratings. Current rating at the motor’s nameplate amps, overload duty, enclosure, short circuit rating for the panel, and the motor type.
- Communication. What protocol the BAS uses, and how the ACS580 will reach it. Plan this before the swap.
- Smoke control. If the old drive or its bypass was part of smoke control, stop and talk to the owner and the life safety contractor.
- I/O. Every input and output the old drive used: start, stop, speed, interlocks, damper end switch, alarms and status.
- The setup. Keep the old backup as a reference for what the drive was doing. The control programs differ, so do not plan on loading it into the ACS580. If you want to move a backup or a control program between the two, call ABB technical support first and ask whether it is supported on that hardware and firmware. Otherwise set the replacement up from the sequence of operations and the start-up record.
- The tests. Motor operation and current, acceleration, Hand/Off/Auto and which command wins, what happens on loss of communication and on sensor failure, restart into a windmilling fan, and a final point check at the BAS. The HVAC VFD commissioning checklist covers each of these.
What the ACS580 does well
The ACS580 is a capable drive for standalone fans, pumps and other equipment that does not need the ACH580’s HVAC features. Its macros include torque control and compressor control, and its standard program is built for general purpose machines. When the job involves a BAS, damper sequencing or smoke control, the ACH580 is the better starting point.
Which one to order
For a fan or pump in a building automation system, order the ACH580. It speaks the BAS protocols, the operators get a Hand-Off-Auto keypad, and the Override, interlock and damper functions are already in the program. Order the ACS580 for general purpose machines and standalone equipment with no BAS, damper or smoke control role. Write the model on the spare parts list for each drive so the next Friday failure gets the right one.
Setting up either drive is covered in the ABB 580 start-up class at The Tolbert School. The HVAC drives guide covers what the drive controls on each HVAC load.
Frequently Asked Questions
What is the difference between the ABB ACH580 and ACS580?
They belong to the same 580 hardware family and run different control programs. The ACH580 runs ABB's HVAC control program, with BACnet MS/TP, N2 and Modbus RTU embedded, a Hand-Off-Auto keypad, an Override group for smoke control, HVAC interlocks and run permissives, advanced damper control and four external PID loops. The ACS580 runs the standard control program, with general purpose macros, run enable logic, one external PID loop and Modbus RTU as its only embedded protocol.
Can an ACS580 replace an ACH580?
Sometimes. On a fan with a hardwired start and speed signal and no smoke control role, it can, once the ratings and I/O check out and the setup is rebuilt and tested. On a BACnet or N2 network, in a smoke control sequence, or behind an E-Clipse bypass, it is not a like-for-like replacement.
Does the ACS580 have BACnet?
Not embedded. The ACS580 has Modbus RTU built in, and ABB lists its FBIP-21 BACnet/IP adapter for the ACH480 and ACH580, not the ACS580. Putting an ACS580 on a BACnet network takes a verified integration solution, such as a protocol gateway, or changes to the BAS.
Does the ACS580 have fire mode?
The ACS580 standard control program has no Override group. The ACH580 has one in its firmware, parameter group 70. The E-Clipse bypass package adds its own Override 1 and Override 2 modes, which belong to the bypass controller, not to the drive.
Can I load an ACH580 parameter backup into an ACS580?
Do not count on it. The two run different control programs, and groups such as Override, the extra external PID loops and advanced damper control are not in the ACS580's standard program. Whether a backup or a control program can be moved between the two in the field is a question for ABB technical support. Until they say otherwise, keep the old backup as a reference, set the ACS580 up from the sequence of operations and the start-up record, and test every point at the BAS.
Online start-up courses, filmed on real drives
One drive per course, filmed uncut with a clock on screen from first power to a saved backup. The install course is free, and the ABB ACS380 and ACS580 start-up course is open now.