The GS20 tells you when a fault happened as well as what happened. Overcurrent, overvoltage, and low voltage each come in four codes, one for acceleration, one for deceleration, one for steady speed, and one for stop. The timing question that takes ten minutes on most drives is answered before you open the panel. Add a warning tier that keeps the motor running, a check that looks for output shorts before the drive starts, and a snapshot of what the drive was doing at the trip, and this is one of the more talkative drives in its price class, if somebody reads it.
Before you clear anything
The GS20 keeps its last 6 faults and a snapshot of the most recent one, so a reset does not erase the history. Write down the code and what the machine was doing anyway, because the snapshot only covers the last trip and the next one overwrites it.
Timing is the most useful clue in drive work, and on this drive the code usually carries it. ocA, ovA, and LvA happened on acceleration, which points at ramp time, inertia, and current limit. The d versions happened on deceleration, which points at regeneration. The n versions happened at steady speed, which points at load, cooling, and sizing. The S versions happened at stop, which points at wiring, the supply, or the drive’s own detection circuits.
Lock out and tag out before the enclosure comes open. The manual’s inspection schedule says to wait at least 10 minutes after all display lamps go out, then measure between DC+ and DC- and confirm the bus is below 25 V DC before touching anything inside. Match PPE to the arc flash rating. Any live voltage measurement on this page is for a qualified person with the right meter and PPE. Retorquing terminals is always done de-energized.
Warnings, faults, and configurable responses
The GS20 manual splits its codes into two tables, warning codes and fault codes, and each code carries a keypad display and an ID number. The display is what the technician reads. The ID is what a PLC reads in the fault record over Modbus.
A warning shows on the keypad, is not written to the fault record, and clears itself when the condition goes away. Most warnings leave the motor running, but not all of them. The analog loss warning, AnL, can be set to ramp the motor to a stop while it shows, so a warning is not always permission to keep running. A fault shuts the output off, the motor coasts or ramps depending on the setting, and the fault is recorded. Most faults wait for a reset. A few clear on their own: bb clears as soon as the base block input releases, and STo clears itself when P06.44 is set to 1.
What catches people is that several conditions can be a warning or a fault, and a parameter decides which. Over slip (oSL), the Modbus time out (CE10), output phase loss, and the PTC input offer warn and keep running, fault and ramp to stop, fault and coast to stop, or no action. The others each have their own list. Over torque (ot1 through ot4) adds a choice of watching only at constant speed or during the whole run. The analog loss setting can hold the last frequency or ramp to stop under a warning. PID feedback loss can hold the last frequency. Two identical GS20s in the same plant can treat the same lost signal several different ways, so when a GS20 does something unexpected on a lost signal, read the setting before you blame the drive.
The quick table
The faults you meet on a running machine. ID is the fault number in the fault record.
| Display | ID | Fault |
|---|---|---|
| ocA | 1 | Overcurrent during acceleration |
| ocd | 2 | Overcurrent during deceleration |
| ocn | 3 | Overcurrent during steady operation |
| GFF | 4 | Ground fault |
| ocS | 6 | Overcurrent at stop |
| ovA | 7 | Overvoltage during acceleration |
| ovd | 8 | Overvoltage during deceleration |
| ovn | 9 | Overvoltage at constant speed |
| ovS | 10 | Overvoltage at stop |
| LvA | 11 | Low voltage during acceleration |
| Lvd | 12 | Low voltage during deceleration |
| Lvn | 13 | Low voltage at constant speed |
| LvS | 14 | Low voltage at stop |
| orP | 15 | Input phase loss |
| oH1 | 16 | IGBT overheating |
| tH1o | 18 | IGBT temperature detection failure |
| oL | 21 | Drive overload |
| EoL1 | 22 | Electronic thermal relay 1 (motor 1) |
| EoL2 | 23 | Electronic thermal relay 2 (motor 2) |
| oH3 | 24 | Motor overheat, PTC or PT100 input |
| ot1 | 26 | Over torque 1 |
| ot2 | 27 | Over torque 2 |
| uC | 28 | Under current |
| cF2 | 31 | EEPROM read error |
| cd1, cd2, cd3 | 33 to 35 | U, V, W phase current detection error |
| Hd0 | 36 | Current clamp hardware error |
| Hd1 | 37 | Overcurrent hardware error |
| AUE | 40 | Auto tuning error |
| AFE | 41 | PID feedback loss |
| ACE | 48 | Analog input loss |
| EF | 49 | External fault |
| EF1 | 50 | Emergency stop |
| bb | 51 | External base block |
| Pcod | 52 | Password locked |
| CE1 to CE4 | 54 to 57 | Modbus illegal command, address, value, write to read only |
| CE10 | 58 | Modbus transmission time out |
| dEb | 62 | Deceleration energy backup |
| oSL | 63 | Over slip |
| STL1, STL2, STL3 | 72, 77, 78 | STO channel 1 open alone, channel 2 open alone, internal loop failure |
| STo | 76 | Safe torque off active |
| Aoc, boc, coc | 79 to 81 | U, V, W phase short found before run |
| oPL1, oPL2, oPL3 | 82 to 84 | U, V, W output phase loss |
| oL3 | 87 | Low frequency overload |
| CD10 | 97 | Ethernet card time out |
| Hd6 | 140 | Ground fault hardware error |
| b4GFF | 141 | Ground fault found before run |
| AuE1, AuE2, AuE3, AuE5 | 142 to 144, 149 | Auto tune errors by test stage |
The warning table covers the same ground with its own IDs, including CE1 to CE10 for communication, oH1 for IGBT temperature, AnL for analog signal loss, PHL for input phase loss, oPHL for output phase loss, ot1 to ot4, uC, oSL, PID, tUn during auto tuning, Fire for fire mode, and a long list of PLC, Ethernet card, and copy errors that belong to commissioning rather than running. Gaps in the fault ID numbers are reserved. AutomationDirect asks that a drive repeatedly showing a reserved number be reported to its technical support with the ID.
The most common GS20 call has no fault code at all: the drive is healthy and the motor will not start, or will not stop. Out of the box, P00.21 takes the run command from the keypad and P00.20 takes speed from the keypad UP and DOWN setpoint, not the dial, so a switch on DI1 does nothing until P00.21 is set to 1. If the hand, off, auto function is in use, there is a second, hand or local pair, P00.30 and P00.31, and a drive left in local ignores whatever P00.20 and P00.21 say. The factory jumper from +24V to both STO terminals must be in until a real safety circuit replaces it. Most important: P00.32 ships at 0, which disables the keypad STOP key whenever the run command comes from somewhere other than the keypad. A GS20 running from terminals or a network will not stop from its own STOP key until P00.32 is set to 1, so set it on any drive people will stand next to.
When the documents disagree
AutomationDirect’s own documents do not always match. This page uses the manual at Rev F, dated October 21, 2026, and AutomationDirect’s own pages have not always agreed on which revision is current, so check the revision history. The quick start guide calls P01.01 maximum output frequency, while the manual makes P01.00 maximum frequency and P01.01 base frequency. Teach the manual.
The firmware has changed behavior that shows up as faults. AutomationDirect’s firmware history lists these:
| Firmware | Change that touches faults |
|---|---|
| 1.01 | Fixed restart after fault (P07.10) and an oL that followed an oc or ov fault. Improved auto-tune |
| 1.02 | Changed the motor overload defaults, P06.13 and related, to 1 |
| 1.04 | Accel, decel, and some other values now survive a power loss |
| 1.06 | Fixed OT1 not resetting |
A drive below 1.02 may not match this page’s motor overload description, and one below 1.04 may lose a ramp change on a power cycle and start tripping on a ramp that someone already lengthened. Read P00.06 before trusting any table, this one included.
The fault details
ocA, ocd, ocn and ocS, overcurrent
What it means. Output current passed 300 percent of the drive rating. The drive shuts the output off immediately and the motor coasts. The last letter tells you when: A for acceleration, d for deceleration, n for steady operation, and S at stop.
Most likely cause. For ocA, an acceleration ramp too short for the inertia, a jam, or a short on the output. For ocd, a deceleration ramp too short, or a motor brake that sets while the drive is still turning the motor, which the manual calls out. For ocn, a load that slammed, a mechanical bind, or insulation breaking down under running voltage. ocS is a different animal: overcurrent with the drive stopped, or a failure in the drive’s own current detection.
The fix, in order. Lock out, verify the bus is discharged, disconnect the motor leads at the drive, and megger the cable and the motor phase to ground, T1, T2 and T3 to PE, never through the drive. Use 500 V DC on a motor rated under 240 V, which covers the 115 V and 230 V GS20s, and 1000 V DC on a 460 V or 575 V motor, unless the motor manufacturer calls for something else. Under 1 megohm is a fail, 1 to 10 megohms means investigate, usually moisture or tired insulation, and over 10 megohms is generally healthy. The IEEE 43 minimum for a random wound motor is 5 megohms corrected to 40 C, which sits inside that investigate band, and why the 4.4 megohm number is wrong covers how to correct a cold reading. The 3 readings should sit within about 50 percent of each other, and a falling trend against earlier readings on the same motor says more than any single number. Ring the windings phase to phase for balance. If the copper tests clean, work the code. On ocA, lengthen the acceleration time in P01.12, add S curve, or turn on over current stall prevention in P06.03. On ocd, lengthen deceleration and check the timing of any motor brake. On any of them, confirm the motor nameplate current is not larger than the drive rating, and check the timing of any contactor between drive and motor, since the manual’s list includes a contactor opening or closing while the drive is putting out voltage.
Worth knowing. The manual’s own check for a failed output stage is a meter test from the DC bus terminals to U, V, and W. A short there is a call to AutomationDirect technical support, not a reset. After any of the oc faults the drive will not reset until 5 seconds after the fault clears, which is the drive giving the power devices time to recover.
When to stop. An ocS that comes back after a power cycle, or a cd1, cd2, or cd3 at power up, means the drive’s current detection has failed. The manual’s answer is to cycle power once and call support if it returns.
GFF, Hd6 and b4GFF, ground faults
What it means. GFF is a ground short on the output terminals, found while running. b4GFF is the same condition found by the drive’s output wiring check before it runs. Hd6 is a failure in the ground fault detection hardware itself, found at power up.
Most likely cause. For GFF and b4GFF, a damaged motor cable, moisture in the motor terminal box, a failing winding, or insulation that has been aging for a while. The software ground fault detection also works from current unbalance, so a badly unbalanced motor can contribute.
The fix, in order. Megger the cable and the motor phase to ground at the voltage and bands given under the overcurrent faults above, and open the motor terminal box and look for water and corrosion while you are there. Check the cable length, since a long cable adds capacitive current that the drive sees.
Worth knowing. GFF has a software side you can tune. P06.60 sets the unbalance level that trips software ground fault detection, 60 percent by default, and P06.61 sets the filter time, 0.10 seconds by default. b4GFF is the more useful of the two codes in practice, because it catches the short before the drive puts power into it, which is the cheapest time to find one.
When to stop. An Hd6 that returns after a power cycle is a drive problem, and the manual sends it to support.
Aoc, boc and coc, shorts found before run
What it means. The drive’s output wiring check found a short on one phase before it started: U for Aoc, V for boc, W for coc. On the GS4-KPD remote keypad these display as UoC, VoC, and WoC.
Most likely cause. Wrong wiring inside the motor or at the drive output terminals, a damaged cable, or failed motor insulation.
The fix, in order. Check the motor’s internal connections and the U, V, W wiring at the drive, which is first on the manual’s list. Then insulation test the cable and motor on the named phase. The drive has already told you which phase to start on.
Worth knowing. Naming the phase, and doing it before the motor ever turns, is real diagnostic value. Most compact drives find a short only after they have tried to drive current into it.
ovA, ovd, ovn and ovS, overvoltage
What it means. The DC bus went over its trip level: 410 V DC on 120 V and 230 V models, 820 V DC on 460 V models, and 1116 V DC on 575 V models. The drive will not reset until the bus drops below 90 percent of that level.
Most likely cause. ovd is regeneration on a deceleration ramp that is too short, which is the common one by a wide margin. ovn at steady speed points at an overhauling load or a supply surge. ovA and ovS point at the supply. The manual specifically names power factor capacitors switching on the same system and the line surges that come with them.
The fix, in order. On ovd, lengthen the deceleration time in P01.13, P01.15, P01.17, or P01.19 depending on which ramp is active, and try over voltage stall prevention in P06.01 or auto acceleration and deceleration in P01.44. If the process needs a fast stop, the energy needs a path, which means a braking resistor or braking unit. On ovA, ovn, or ovS, measure the incoming line and look for surges. An AC line reactor is the manual’s answer to capacitor switching surges.
Worth knowing. The manual’s ovA list includes a check that the stall prevention level is not set below no load current. A stall level set too low keeps the drive fighting itself and pushes the bus up during acceleration.
LvA, Lvd, Lvn, LvS and orP, low voltage and input phase loss
What it means. The DC bus fell below the level in P06.00, which defaults to 180 V DC on 120 V and 230 V models, 360 V DC on 460 V models, and 450 V DC on 575 V models. As with the other groups, the last letter tells you when. orP is input phase loss, which the drive sees as ripple on the bus.
Most likely cause. A sag or brownout, a supply too small for the load, a loose line side connection, or a large load starting on the same feeder. orP is a blown fuse, a loose line terminal, or a failed contactor pole. No setting turns orP off: P06.53 only chooses whether it ramps or coasts the motor to a stop. LvS can also mean a failure in the drive’s voltage detection, which the manual includes.
The fix, in order. A qualified person measures the supply under load at the drive terminals rather than at rest. Then lock out, verify the bus is discharged, and retorque the line side connections de-energized. On orP, measure all three phases and check fuses individually. The manual adds a DC reactor to its list for low voltage, and for repeated LvS after the supply checks out it says to send the drive back for repair.
Worth knowing. This is the group to understand on a single phase GS21 like the bench unit. A 3 phase supply with one phase gone looks like orP on a 3 phase model, but a single phase model on a weak single phase circuit shows up as the Lv codes under load instead.
oH1, tH1o, IGBT temperature
What it means. oH1 as a fault means the IGBT temperature went 5 degrees C past the warning level set in P06.15, and the drive stopped. The same name as a warning means it crossed P06.15 and is still running. tH1o means the drive cannot read its IGBT temperature at all, an NTC sensor failure or its wiring.
Most likely cause. A hot cabinet, a blocked or failed fan, dirty fins, too little clearance, or a heat source like a braking resistor mounted next to the drive, which the manual names.
The fix, in order. Measure the air at the drive intake with the panel closed, not the room. Clean the heatsink, check the fan, and check the clearances. The manual’s list also says to move heat sources away and add cabinet cooling if needed. After the fault, the drive will not reset until the IGBT is 10 degrees C below the trip level.
Worth knowing. P06.15 is your early warning, and P06.43 shows the live IGBT temperature. If P06.15 is set higher than the trip level, the drive skips the warning and goes straight to the fault, so leaving it at its default is the setting that keeps the warning.
oL, EoL1, EoL2 and oL3, overloads
What it means. Four different overloads. oL is the drive itself: in VT duty it carries 120 percent for 1 minute and 150 percent for 3 seconds, and in CT duty 150 percent for 1 minute and 200 percent for 3 seconds. EoL1 and EoL2 are the electronic thermal relays for motor 1 and motor 2, the drive acting as the motor overload. oL3 is low frequency, high current protection.
Most likely cause. For oL, a drive undersized for the duty or an aggressive ramp. For EoL1, a real motor overload, a wrong motor current setting, or a self cooled motor run slowly for long periods. For oL3, high current at low speed, often too much torque boost or a V/F midpoint set too high.
The fix, in order. For EoL1, confirm the motor rated current and frequency settings match the nameplate first, then measure the load. Look at P06.13: 1 is a standard motor with a shaft fan, which derates the protection at low speed, 0 is an inverter duty motor with forced cooling, and 2 disables it. For oL, check the drive rating against the real duty cycle, not the motor nameplate. For oL3, look at the V/F curve and torque compensation in P07.26.
Worth knowing. P06.13 = 2 is for one drive running several motors, and the manual says each motor then needs its own thermal overload relay. A GS20 on a multi motor conveyor with P06.13 at 2 and no external overloads has no motor protection at all.
oH3, motor overheat
What it means. A motor temperature sensor wired to an analog input crossed its limit. The manual lists two versions under one code. With P03.00 or P03.01 set to 6, the input reads a PTC thermistor and trips at the P06.30 level, 50 percent by default. With it set to 11, the input reads a PT100 RTD, with its levels in P06.56 and P06.57.
Most likely cause. A motor that is actually hot: a locked shaft, too much load, a failed motor fan, a hot room, or long running at low speed on a self cooled motor. Then the sensor wiring.
The fix, in order. Check the motor before the drive. Feel for heat, check the fan and the load, then check the sensor connection.
Worth knowing. P06.29 decides what oH3 does: 0 warns and keeps running, 1 faults and ramps to stop, 2 faults and coasts, and 3 does nothing. Set to 0, the warning clears itself when the temperature drops. A motor with a thermistor wired in and P06.29 at 3 has a sensor and no protection.
ot1, ot2, uC, oSL, over torque, under current and slip
What it means. ot1 is over torque detection on motor 1: output current above P06.07 for longer than P06.08. ot2 is the same on motor 2, using P06.10 and P06.11. ot3 and ot4 cover motors 3 and 4. uC is low current detection. oSL is speed deviation beyond the slip limit, induction motors only.
Most likely cause. The machine. Over torque means something is binding, under current means something came loose or the pump lost its prime, and over slip means the motor cannot hold speed under the load.
The fix, in order. Go look at the driven equipment before changing any settings. Then confirm the detection levels and times match what the machine really does.
Worth knowing. P06.06 for motor 1 and P06.09 for motor 2 have five settings. 0 is off. 1 and 3 warn and keep running, at constant speed only or during the whole run. 2 and 4 stop and record a fault, at constant speed only or during the whole run. The default is 0. Set to warn, these turn the drive into a condition monitor for the machine, and they do nothing until somebody configures them.
oPL1, oPL2 and oPL3, output phase loss
What it means. One output phase is missing or low: U, V, or W. P06.45 decides whether it warns (shown as oPHL), faults with a ramp stop, faults with a coast stop, or does nothing. P06.45 ships at 3, no action, so output phase loss detection is off until somebody turns it on. A GS20 running a motor with an open lead and no oPL fault may simply have the detection off.
Most likely cause. A loose or broken motor lead, a failed contactor pole between drive and motor, an unbalanced motor, or a single phase motor on a 3 phase drive, which the manual lists.
The fix, in order. With the drive running, a qualified person can clamp all three output phase currents to confirm the imbalance. Then lock out, and with the drive de-energized and the bus verified discharged, retorque the output terminations at both ends and check any contactor or disconnect between drive and motor. The manual says if the currents are balanced and the fault remains, check the flat cable on the control board, then call support.
EF, EF1 and bb, external stops
What it means. EF is an external fault input, a digital input set to 10, and the drive stops the way P07.20 tells it to. EF1 is an emergency stop input. The output shuts off immediately and the motor coasts. bb is external base block. The output shuts off and the motor coasts, but nothing has failed.
The fix, in order. Find what opened before clearing anything. The input that tripped belongs to somebody’s interlock, and it did its job.
Worth knowing. EF can ramp to a stop on any of the four deceleration times, depending on P07.20. EF1 and bb always coast. A machine that coasts when somebody expected a controlled stop is usually wired to the wrong one.
ACE and AFE, analog and feedback loss
What it means. ACE is a 4 to 20 mA analog input below 4 mA. AFE is PID feedback loss on the same kind of signal.
Most likely cause. A broken wire, a loose terminal, or a failed transmitter.
The fix, in order. Measure at the drive terminals so the wire is part of the test, tighten the terminal, and check the transmitter.
Worth knowing. P03.19 decides what the drive does when the analog signal drops: 0 ignores it, 1 keeps running at the last frequency and shows the AnL warning, 2 ramps to stop with the AnL warning, and 3 stops and shows the ACE fault. P08.09 does the same job for PID feedback, with a choice to keep running at the last frequency. A GS20 holding speed with AnL on the display is doing what it was set to do, and it is worth deciding whether the process can tolerate that.
CE1 through CE4 and CE10, Modbus
What it means. CE1 through CE4 are Modbus protocol errors: an illegal function code, an illegal address, an illegal data value, or a write to a read only address. CE10 is a Modbus time out, meaning the master did not send anything inside the time set in P09.03.
Most likely cause. For CE1 to CE4, a mistake in the master’s program, usually the wrong register or the wrong function code. For CE10, a master that stopped polling, a cable or termination problem, or noise.
The fix, in order. Check that the communication settings in P09.01 and P09.04 match the master, which the manual puts at the top of the whole fault chapter. Check the cable and grounding, and route the RS 485 run away from motor leads or cross them at 90 degrees, which is the manual’s own advice. For CE1 to CE4, check the register and function code the master is using.
Worth knowing. Two settings decide what happens when the master goes quiet, and both ship in the do nothing position. P09.03 sets the time out, from 0.0 to 100.0 seconds, and ships at 0.0. P09.02 decides the response, warn and keep running, fault and ramp, fault and coast, or nothing, and ships at 3, nothing. The manual does not say in so many words that 0.0 turns the check off, but with P09.02 at 3 the drive takes no action either way. Setting only one of them is not enough. A GS20 under Modbus control left at the defaults will keep running at its last command if the PLC dies, so set both and test the loss of communication with the machine in a safe state. A CE10 fault, once it trips, does not clear when communication comes back, so the master has to send a reset.
STo and STL1 through STL3, safe torque off
What it means. The GS20 has two STO inputs, STO1 and STO2, each referenced to SCM. Appendix E of the manual maps what each combination shows. Both channels open together gives STo, the safety function working normally. STO1 open while STO2 stays closed gives STL1. STO2 open while STO1 stays closed gives STL2. STL3 is a fault detected in the drive’s internal loop on either channel. Chapter 6 calls STL1 and STL2 internal loop detection errors, and both descriptions apply: a single channel opening, whether from wiring or from an internal failure, is a discrepancy the drive will not ignore.
Most likely cause. For STo, a real safety demand: an e stop, a gate, or a safety relay that dropped out. For STL1 and STL2, one channel of the safety circuit opened without the other, from a loose wire, a failed contact, a missing STO to SCM jumper on a machine that does not use STO, or a fault inside the drive. For STL3, the drive itself.
The fix, in order. For STo, find which safety device opened. For STL1 and STL2, trace the named channel from the safety relay output to the STO terminal and check the jumpers, then the control terminal connections, which is the manual’s list, then call support.
Worth knowing. The reset rules differ by code. STo clears with the Reset key, or clears itself once both channels close if P06.44 is set to 1. P06.44 ships at 0, which latches. STL1 and STL2 need a power cycle. STL3 cannot be reset and means an internal drive failure. The GS20 ships with STO1 and STO2 tied to +24 V. AutomationDirect rates the STO function at ISO 13849-1 Category 3 PL d and IEC 61508 SIL 2, with a response time of 20 ms or less. Relay R1 can be set to a safety status output with P02.13 = 66.
EF1, the emergency stop input, is a standard control input. It stops the drive and the motor coasts, but it is not a safety rated function and is not a substitute for STO. Jumpering a safety circuit to clear a code is not troubleshooting.
dEb, deceleration energy backup
What it means. The power dropped out, the bus fell below the dEb level, and the drive used the load’s own energy to ramp the motor down in a controlled stop rather than letting it coast. This only happens when P07.13 is not 0.
The fix, in order. Look at the supply. The manual points at an unstable or interrupted supply and at large loads on the same system.
Worth knowing. P07.13 = 2 lets the drive pick the motor back up and run when power returns, and dEb clears on its own. P07.13 = 1 stops at 0 Hz and waits for a manual reset. Know which one is set before somebody finds a machine running after a power blip.
cF2, cd1 to cd3, Hd0, Hd1, and the internal codes
What it means. cF2 is an EEPROM read error. cd1 to cd3 are phase current detection errors at power up. Hd0 and Hd1 are current clamp and overcurrent hardware errors at power up. ictE and CP20 to CP33 are internal communication errors.
The fix, in order. The manual’s instruction for nearly all of these is the same: cycle power, and if the code returns, contact AutomationDirect technical support. The cd and Hd codes reset only by removing power.
Pcod, password locked
What it means. Somebody entered the wrong password in P00.07 three times in a row.
The fix, in order. Cycle power and enter the right password. If nobody knows it, the manual gives a recovery: enter 9999 and press ENTER, then do it again within 10 seconds. That clears the password, and it also returns every parameter to default, so have the saved parameter file ready before you do it.
The faults you prevent are the ones you never read
The GS20 keeps two records, and between them they answer most of what a technician wants to know.
The fault records are P06.17 through P06.22, the last 6 faults by ID number. P06.63 onward give the drive’s operating time at each of them, in days and minutes, which tells you whether the faults are clustered or spread out.
The malfunction snapshot is P06.31 through P06.42, values captured at the last trip: frequency command, output frequency, output voltage, DC bus voltage, output current, IGBT temperature, motor speed, torque command, the status of the digital inputs, the status of the digital outputs, and the drive status word. The next trip overwrites them.
These are operating values captured at the trip, not a waveform recording, so they may miss the exact peak of a fast transient. They are still the best evidence you will get after the fact.
The terminal status pair is worth more than it looks. It records which digital inputs were on and which outputs the drive was driving at the moment it stopped, which settles whether the run command was present and whether the permissive was made without anybody instrumenting anything. An ocA with the bus at nominal and current at 300 percent is a different story from an ovd with the bus at 410 V and current falling, and the snapshot gives you the numbers to tell them apart.
All of it is Modbus readable, P06.17 at decimal address 41554 and the rest in sequence, so a PLC can log the history instead of a single fault bit. P06.23 through P06.26 let you assign specific faults to the multi function outputs, so a ground fault and an overload can light different lamps, once an output is set to the matching function, 35 through 38.
Reading and clearing faults
Reset a fault from the keypad, a digital input set to reset, or the Modbus control word, once the cause is gone. The reset rules vary by code and are worth knowing, because some of them make you wait:
The oc, GFF, and EoL faults reset 5 seconds after the fault clears. The ov faults reset once the bus drops below 90 percent of the trip level. oH1 resets once the IGBT is 10 degrees C below its trip. The cd and Hd codes and STL1 and STL2 reset only by cycling power. STL3 cannot be reset. bb clears on its own when the input releases, and STo clears on its own only if P06.44 is set to 1.
Automatic restart lives in P07.10 and P07.11. P07.11 sets the number of restart attempts, 0 to 10, and ships at 0. P07.10 sets how the drive picks the motor back up: stop, speed tracking from the current speed, or speed tracking from minimum frequency. The manual limits restart to base block, overcurrent, and overvoltage faults. Everything else waits for a person. A drive that restarts itself is attached to a machine that starts itself, so turn this on only where an unattended restart is safe.
The warning tier is where this drive earns its keep, and only if somebody wires it. Any of the conditions that can be set to warn, over torque, slip, phase loss, analog loss, and the Modbus time out, shows on the keypad, and a multi function output can carry it to the PLC once that output is configured for the warning. A plant that reads warnings hears about a developing problem while the line is still running.
Where this fits
Most of what appears on this page was decided before the drive was first powered: the supply, the single phase sizing, the motor cable, the cabinet, and the motor data somebody entered. The VFD Installation Guide and the VFD Troubleshooting Guide cover the work that keeps those decisions from showing up later as faults.
The same treatment for other platforms is in the ABB Drive Fault Field Guide, the PowerFlex 525 Fault Field Guide, the Yaskawa Fault Field Guide, and the Invertek Optidrive E3 Fault Field Guide, and every brand is listed on the guides page. For the competency behind the codes, that is what the VFD training does, and Before the First Fault is the field record the approach came out of.
Fault codes, parameter references, and behavior on this page are taken from the AutomationDirect DURApulse GS20 and GS20X AC Drive User Manual, GS20-UMW, 1st Edition Rev F. Confirm against the manual revision that matches the firmware in front of you. AutomationDirect and DURApulse are trademarks of AutomationDirect, used here for identification.
Frequently Asked Questions
What is the difference between ocA, ocd, ocn and ocS on a GS20?
All four are overcurrent above 300 percent of the drive rating. The last letter says when it happened: A during acceleration, d during deceleration, n at steady speed, and S at stop. ocA points at the acceleration ramp, ocd at the deceleration ramp or a motor brake setting early, ocn at the load or insulation, and ocS at wiring or the drive's own current detection.
Why won't my GS20 reset right after an overcurrent fault?
The oc, GFF, and EoL faults only reset 5 seconds after the fault clears, and overvoltage faults only reset once the bus is below 90 percent of the trip level. Wait, then find the cause before resetting.
What do Aoc, boc and coc mean on a GS20?
The drive's output wiring check found a short on the U, V, or W phase before it started. On the GS4-KPD keypad they show as UoC, VoC, and WoC. Check the motor wiring and insulation on the named phase.
Why did my GS20 keep running when the PLC stopped communicating?
P09.03, the Modbus time out, ships at 0.0, and P09.02, the response, ships at 3, no warning and no fault. Set a time out in P09.03 and a response in P09.02, then test it with the machine in a safe state.
What is the difference between STo and STL1 on a GS20?
STo means both safe torque off inputs opened together, which is the safety function working, and it clears with Reset. STL1 means STO1 opened without STO2, and STL2 the reverse, usually wiring or a missing jumper, and both need a power cycle. STL3 is an internal drive failure that cannot be reset.
Why won't the STOP key stop my GS20?
P00.32 ships at 0, which disables the keypad STOP key whenever the run command comes from terminals or a network. Set P00.32 to 1 so STOP works from any source.
Where does the GS20 store its fault history?
P06.17 through P06.22 hold the last 6 faults by ID, with operating time at each from P06.63 on. P06.31 through P06.42 hold a snapshot of the last trip, including frequency, current, bus voltage, IGBT temperature, and the state of the digital inputs and outputs.