The booster at a small subdivision holds 60 psi all day. At 2 in the morning it starts, runs for 20 seconds, stops, and starts again 3 minutes later, all night long. The homeowners do not notice. The drive’s start counter does. Somewhere a toilet flapper is leaking, the tank precharge has dropped, and the wake pressure was set 2 psi under the setpoint at start-up because that is what the last job used.
A constant pressure system is a simple idea that lives or dies on 5 small settings. This note covers how the system works, where the savings come from, and the setup for the transducer, the tank, the PID loop, sleep and wake, pipe fill, and alternating pumps. The motor rules for submersibles, the 30 Hz minimum and the 1 second ramp, are in VFD for pumps and well pumps. They apply to every constant pressure well.
How a constant pressure system works
A pressure transducer on the discharge sends the drive a 4 to 20 mA signal. The drive’s PID loop compares that pressure with the setpoint and changes the pump speed to hold it. Open a faucet and the pressure dips, so the pump speeds up. Close it and the pressure rises, so the pump slows down. When nobody is using water, the drive tops up the tank and goes to sleep.
The other parts matter as much as the drive:
- A pressure tank, much smaller than a pressure switch system needs, to carry small demands and give the drive something to sleep on.
- A check valve that holds the system pressure when the pump stops.
- A pressure relief valve, because a drive is not a relief valve. Franklin’s SubDrive manuals call for one that can pass full pump flow, installed near the tank and piped to a drain.
Every pump drive from the makers who build for water does this out of the box: ABB’s ACQ580, Danfoss’s VLT AQUA Drive FC 202, Yaskawa’s iQpump family, Franklin’s SubDrive line, and the packaged drives from the pump makers. A general purpose drive can do it too with its PID loop, but the pump drives add the sleep, pipe fill and protection features this note keeps coming back to.
Where the savings come from
The biggest wins come from systems that were throwing pumped water away. The Hydraulic Institute published a case on a small water system with two 30 HP boosters, one duty and one standby, rated 400 gpm at 80 psi. They ran across the line, and a relief valve dumped the excess back to the reservoir to hold 80 psi. Drives holding 80 psi on a pressure transmitter, with the relief valve and its recirculation piping removed, took the station from 176,295 kWh a year to 117,895, about 33 percent less, for $5,864 a year and a 5.1 year payback.
A well is a different story. Most of the power on a deep well goes into lifting water, and lift does not drop when the pump slows down. A constant pressure well still earns its keep with steady pressure, soft starts and fewer hard starts on the motor, but the energy savings are smaller. The water and pump drives guide covers when a drive pays and when it doesn’t.
The transducer
Range. Pick a transducer whose range covers the highest pressure the system can see, with some margin, so the signal uses most of its span. A 300 psi transducer on a 50 psi system works, but most of its signal goes unused and the drive’s resolution suffers. Franklin, for example, offers 100, 150 and 200 psi transducer kits for its SubDrive drives.
Location. Put it where it reads the pressure the system sees. Franklin’s instructions are to mount it vertically after the pressure tank, within 6 feet of the tank, with no elbows between the tank and the transducer. A transducer right at a pump discharge, after a fitting that churns the water, or far from the tank makes the loop chase noise.
Scaling. The drive has to know the transducer’s range. If the transducer is 0 to 150 psi and the drive thinks it is 0 to 100, the pump holds the wrong pressure and nobody knows until a gauge disagrees. Check the drive’s reading against a gauge at the transducer.
Wiring and loss. Run the 4 to 20 mA signal on shielded cable, away from the motor leads, with the shield grounded the way the drive maker says. Decide what the drive does if the signal is lost or out of range: fault and stop, run at a set safe speed, or hold its last speed. Holding the last speed or running to maximum on a dead signal can overpressure the system or short cycle the pump once the wiring fails. Then test it by unplugging the transducer while the pump runs, and confirm the drive does what you set.
The tank
A drive system needs a much smaller tank than a pressure switch system, but it still needs one. The tank carries the small demands so the pump is not starting for every glass of water, and it is what the system lives on while the drive sleeps.
Franklin’s minimum tank sizes for its SubDrive Connect Plus run from 2 gallons at 10 gpm of pump flow to 20 gallons above 40 gpm, with larger flows sized by the tank maker. It sets the tank precharge at 70 percent of the system pressure setpoint. Check the precharge with the pump off and the water side of the tank drained to zero pressure. A reading taken with water in the tank is not a precharge reading. A tank that has lost its air charge acts like no tank at all, and short cycling is the first symptom, so check it again after the first week of running.
The PID loop
Set the setpoint in pressure units, then start with conservative gains and tighten them only as far as the system stays stable. A loop that is too aggressive hunts: the pump speeds up and slows down every few seconds and the pressure gauge needle swings. A loop that is too slow lets pressure sag when a big demand comes on.
Before blaming the gains, check the things that make a good loop look bad: the transducer location and scaling, the tank precharge, air in the lines, and a minimum speed set so low that the pump cannot make pressure at the bottom of its range. On a well, the minimum speed has to clear the head the pump works against, not just the motor’s 30 Hz bearing rule.
Sleep and wake
At low demand, the drive should stop the pump instead of running it at minimum speed doing nothing. There are 3 settings that decide whether sleep works.
When to sleep. Drives detect low demand either by the pump running near minimum speed for a set time or by watching for no flow. Danfoss’s AQUA Drive offers both. Set the delay long enough that a short dip in demand does not put the pump to sleep in the middle of a shower.
Boost before sleep. Most pump drives can push the pressure a few psi above the setpoint just before they stop, to fill the tank and stretch the sleep. ABB, Danfoss and Yaskawa all build this in. Yaskawa calls it sleep boost and says it is for use with a pressure tank, which is the point: the boost only helps if there is a tank to store it.
When to wake. The wake pressure, or the wake difference below the setpoint, decides how far pressure falls before the pump starts again. Set it too close to the setpoint and the pump wakes for every drip. Set it too far and the users feel the pressure drop. Franklin calls this drawdown on the SubDrive Connect Plus: the default is 5 psi below the setpoint, adjustable from 5 to 20 psi, and its own example holds 50 psi while running and does not restart until pressure falls below 30. That is a long way from the 2 psi band in the subdivision story above. A wider band lets the tank do its job.
On a submersible, every wake is a motor start. Franklin allows no more than 200 starts in 24 hours on a drive, and fewer is better. If the start counter climbs at night, look for the leak, the lost precharge or the wake band before changing anything else. Danfoss’s AQUA Drive has short cycle protection, and other pump drives have similar limits, but those hide the symptom. The cause is still in the system.
Pipe fill
An empty or drained system filled at full speed slams water into the pipe. Pump drives have a fill mode for that: ABB calls it soft pipe fill and raises the pressure setpoint gradually over a set time, Danfoss’s pipe fill mode fills at a set rate before handing over to the normal loop, and Yaskawa’s iQpump calls it pre-charge. Use it on any system that starts with empty or partly drained pipe, and set its time limit so a broken pipe or a closed valve shows up as a fault instead of a pump that runs forever trying to fill.
On a submersible, pipe fill still has to respect the motor maker’s ramp rule: the motor reaches 30 Hz within 1 second, and the gentle fill happens above that.
Protecting the pump
A constant pressure system runs unattended, so the drive’s protection is the only thing watching it.
- Dry run or loss of prime. Every pump drive has it under some name: dry run on ABB and Danfoss, loss of prime on Yaskawa, underload on Franklin. Turn it on and test it.
- No flow and broken pipe. A pump at full speed that never reaches setpoint is either against a closed valve or pumping out a broken pipe. Danfoss calls the check end of curve detection, and Yaskawa’s iQpump has broken pipe protection. Set the time long enough to ride through a big demand.
- Low suction pressure. A booster fed from a city main or a tank can pull its suction down below what the pump can take. ABB’s ACQ580 has inlet pressure protection, and the system may also need a low suction pressure switch. Check what the local water utility and plumbing code require.
- High pressure. The relief valve is the real protection. A high pressure alarm in the drive is a backup.
Alternating pumps
Two or more pumps on one system should share the work. Alternation keeps the standby pump from sitting for months and seizing, and the Hydraulic Institute case above calls out alternating duty for exactly that reason. Lead and lag staging brings a second pump on when one cannot hold the setpoint at full speed and drops it off when demand falls.
Every water drive maker builds this in, in different ways:
- ABB ACQ580. Multipump control links up to 8 drives, one pump per drive, and keeps running if one drive or pump is down.
- Danfoss VLT AQUA Drive FC 202. Built-in motor alternation and a basic cascade controller, with the MCO 101 and MCO 102 cascade options and Multi-Master cascade control for larger systems.
- Yaskawa iQpump1000. Drive to drive multiplexing with up to 8 pumps, or a single drive running up to 5 constant speed lag pumps.
- Franklin SubDrive Connect Plus. Built-in lead and lag with alternation for up to 8 drives.
Set the staging and destaging points with margin so the lag pump does not start and stop every few minutes near the switch point. With one drive and fixed speed lag pumps, expect a pressure bump when a lag pump comes on across the line, and a soft starter on the lag pumps helps. With a drive on every pump, the handoff is smoother and any pump can lead.
Before you leave the site
Test the relief valve and confirm the check valve holds pressure with the pump stopped. Both are part of the system, not assumptions. Then write down the setpoint, the transducer range and where it is mounted, the tank size and precharge, the minimum and maximum speed and why, the sleep, boost and wake settings, the pipe fill time, the dry run and no flow settings, and the alternation setup. Then watch the system through a full cycle: a big demand, a small one, sleep, and a wake. If you can, come back and read the start counter after the first night.
Setting up pump control on an ABB 580 drive is covered in the ABB 580 start-up class, and lead length, filters and grounding are in the free First Power class, both at The Tolbert School. The water and pump drives guide covers wells, boosters, lift stations and when a drive pays.
Frequently Asked Questions
How does a constant pressure pump system work?
A pressure transducer on the discharge tells the drive what the system pressure is. The drive's PID loop speeds the pump up when pressure drops and slows it down when pressure rises, so pressure stays near the setpoint as demand changes. A small pressure tank carries the system through short demands, and a sleep function stops the pump when nobody is using water.
Is a constant pressure well pump worth it?
For steady pressure and fewer hard starts, usually yes. The energy savings depend on the system. A booster that was dumping water through a relief valve can save a lot: one Hydraulic Institute case cut energy by about a third. A deep well that mostly lifts water saves less, because the lift does not drop when the pump slows down.
What size pressure tank does a constant pressure system need?
Smaller than a pressure switch system, but not zero. Franklin's minimum for its SubDrive Connect Plus runs from 2 gallons at 10 gpm to 20 gallons above 40 gpm, with larger flows sized by the tank maker, and a precharge of 70 percent of the system pressure setpoint. A tank that is too small makes the pump short cycle.
Where should the pressure transducer go?
Where it reads the pressure the system sees, without turbulence. Franklin says to mount it vertically after the pressure tank, within 6 feet of the tank, with no elbows between the tank and the transducer. A transducer right at the pump discharge or past a fitting that churns the water makes the loop hunt.
Why does my constant pressure pump keep cycling on and off?
Common causes are a tank that is too small or has lost its precharge, a wake pressure set too close to the setpoint (Franklin's default drawdown is 5 psi and goes to 20), a leak or a dripping fixture that pulls the pressure down while the pump sleeps, and a sleep setting that stops the pump before the tank is topped up. Fix the cause instead of lengthening the delays to hide it.
Online start-up courses, filmed on real drives
One drive per course, filmed uncut with a clock on screen from first power to a saved backup. The install course is free, and the ABB ACS380 and ACS580 start-up course is open now.