Inverter duty is printed on a lot of motor data sheets and asked for in a lot of specs, and it means less than people think and more than the price difference suggests. The industry uses the words for motors built to run on a PWM drive, and NEMA MG-1 Part 31 sets the requirements for what it calls definite purpose inverter fed motors, with a specific voltage envelope.
This note covers what the 2 parts of MG-1 that apply to drives allow, what you get in an inverter duty motor beyond the insulation, and how to decide whether the motor on a given drive needs to be one.
What the standard actually says
NEMA MG-1 covers motors on drives in 2 parts, and they are written for different people. Part 30 is the guide for the buyer applying an ordinary general purpose motor to a drive. Part 31 is the guide for the motor maker designing a motor specifically for drive duty.
| Part 30 | Part 31 | |
|---|---|---|
| Motor | General purpose motor used on a drive | Definite purpose inverter fed motor (inverter duty) |
| Peak voltage at the motor terminals, motors 600 V and below | 1,000 V | 3.1 times rated line to line voltage |
| Rise time | 2 microseconds or slower | 0.1 microsecond or slower |
| Example, 460 V motor | 1,000 V peak | about 1,426 V peak |
For inverter duty motors rated above 600 V, the limit is 2.04 times rated line to line voltage with rise times of 1 microsecond or slower.
The rise time column is the one that gets read backwards. The limit sets how fast the edge is allowed to be. A rise time of 0.1 microsecond or longer is inside the Part 31 envelope. A faster edge, from a newer IGBT or SiC drive, is outside it even when the peak voltage is fine, because a fast edge piles its voltage onto the first few turns of each coil instead of spreading it across the winding. That first turn stress is what kills windings on drives.
The peak column is a multiplier, not a number. A 460 V inverter duty motor is held to about 1,426 V peak. A 575 V motor is held to about 1,783 V. The 1,600 V figure in a lot of specs is a real winding rating that fits 460 V motors and does not fit 575 V ones. The note on where the 1600 volt number comes from works through what that does to a spec.
Why the motor sees more than the line voltage
A 460 V motor on a 480 V line sees about 680 V peak, rising over several milliseconds. The same motor on a drive sees the DC bus, about 650 VDC, switched on in a fraction of a microsecond. The motor cable acts like a transmission line, and the pulse reflects off the motor terminals and adds to itself. On standard drives with 200 to 300 feet of cable, 1,200 to 1,600 V at the motor terminals is a common reading, and on long runs it approaches twice the bus. That puts an ordinary 480 V job right at the Part 31 line. Reflected wave and long motor leads covers the mechanism.
What an inverter duty motor gives you
| Feature | Standard motor | Inverter duty motor |
|---|---|---|
| Insulation class (temperature) | B or F | F or H |
| Voltage withstand | Part 30 envelope | Part 31 envelope |
| First turn insulation | Varies by design | Often reinforced |
| Constant torque speed range | Not rated | Rated, and it varies widely by motor line |
| Bearing protection | None | Often offered, not always included |
| Typical cost premium | Baseline | Often about 10 to 20 percent, varying by line and features |
The insulation class in that table is a temperature rating, not a voltage rating. A Class F winding can still fail on a drive if its turn insulation was not built for PWM spikes, so the voltage withstand line is the one to read.
The speed range rating is the part people skip, and inverter duty on the nameplate does not tell you what it is. Nidec’s catalog shows how wide the spread runs: its inverter duty NEMA frame motors are rated 10 to 1 variable torque but only 5 to 1 constant torque, some lines carry 10 to 1 constant torque, and its vector duty motors make full torque down to zero speed. A 1,800 RPM motor rated 20 to 1 can carry full torque continuously down to 90 RPM. One rated 1000 to 1 can carry it at 1.8 RPM. One rated 5 to 1 runs out of cooling at 360 RPM, about 12 Hz. Those ratings depend on the motor design, its cooling and the drive control mode it was rated with, and the insulation rating says nothing about them. Low speed heat and voltage spikes are 2 separate questions: a lightly loaded fan can have plenty of thermal margin at low speed and still see high spikes at the terminals. A TEFC motor with no speed range rating on a constant torque load should not run for long below about 20 Hz, because its fan slows with the shaft and the cooling falls off faster than the losses do. The note on how much cooling a motor loses at reduced speed has the numbers.
Bearing protection is not automatic. Read the data sheet for insulated bearings or a shaft grounding provision, and see a grounding ring cannot outrun a bad install for what to add if they are missing and what has to be right first.
What motor makers actually publish
Part 31 sets the minimum, and the motor makers build to it in their own ways. Baldor rates its 460 V inverter motors at 1,600 V peak against the 1,426 V Part 31 asks for, and its 575 V motors at 1,850 V against the 1,783 V Part 31 asks for. That 575 V number is the one to look for, because it is the voltage class where a plain 1,600 V winding comes up short.
The warranty is where the words on the data sheet turn into money. Nidec covers its inverter grade motors on drives for 3 years. Its premium efficient motors without that insulation can go on a drive with a shorter warranty and tighter limits, about 127 feet of cable at 460 V and a 3 kHz carrier, shrinking to 49 feet at 20 kHz. Its standard and energy efficient motors are not covered for drive related failures at all. Inverter grade motors are allowed 400 feet without an output filter. Other makers draw these lines in other places, which is why the next section ends with asking the motor maker in writing.
Deciding whether the motor needs to be inverter duty
- New motor on a new drive: specify the numbers, not just the words. Ask for a documented peak voltage withstand and rise time at the motor’s voltage, and the constant torque speed range the load needs. In practice that usually means buying inverter duty, and the premium is small enough that there is rarely a good reason to save it.
- Existing motor going on a drive: read the nameplate. Insulation class, age, voltage, and whether the maker says anything about drive duty. A Class B motor from stores deserves a hard look before it goes on a drive.
- Measure the cable run. A field rule for screening: over 100 feet, use an inverter rated motor, and over 300 feet, use an inverter rated motor and put an output reactor or a dV/dt filter on the drive. The drive maker’s cable length table for that drive and motor rating replaces the rule when you have it. If one drive feeds several motors, add every lead together to check the drive’s own cable limit, and judge each motor’s insulation on the length of its own run, since each run reflects on its own.
- Look at the duty. A variable torque fan or pump that rarely runs slow is easy on a motor. A constant torque conveyor at low speed is hard on it.
- Ask the motor maker for the real peak withstand and rise time, in writing, at the motor’s voltage. “Inverter ready” and “suitable for inverter use” on a data sheet mean whatever that maker says they mean.
- Take that rating to the drive maker’s cable length table for the run you have. The table decides whether the drive output needs a reactor or a filter, and reflected wave and long motor leads covers what each one does to the peak. A motor that meets Part 31 can still need a filter on a long run. The insulation rating is not permission to skip the table.
A low risk retrofit looks like a newer Class F motor on 30 feet of cable running a fan. A high risk one looks like an older Class B motor on 250 feet of cable running a loaded conveyor. The second one is where the output filter earns its money, or where the motor gets replaced at the next outage.
2 things to get right on the drive
Do not count on the nameplate service factor on a drive. Many motors rated 1.15 service factor on sine wave power drop to 1.0 on inverter power, because PWM current heats the winding more than a sine wave does, low speed cuts the cooling on a TEFC motor, and ambient and altitude take their share. Unless the motor maker says in writing that the service factor holds on a drive, size the motor so its rated horsepower covers the load. If the load needs 11 HP, buy a 15.
And when the motor goes on the drive, enter the motor’s nameplate full load amps for the voltage it is connected for, not the service factor amps and not the NEC table value. The note on the 2 full load amp numbers covers why. The full treatment of motor selection for drives is in Before the First Fault, and the free First Power course on the online training page starts with reading the nameplate.
Frequently Asked Questions
What is an inverter duty motor?
A motor built to run on a VFD's PWM output, covered by NEMA MG-1 Part 31 as a definite purpose inverter fed motor. For motors rated 600 V or less, its insulation is designed for peak voltages up to 3.1 times rated line to line voltage with rise times of 0.1 microsecond or slower. It usually adds reinforced insulation on the first turns, Class F or H insulation, and a rated constant torque speed range.
Can I run a standard motor on a VFD?
Often, with conditions. NEMA MG-1 Part 30 says a general purpose motor of 600 V or less should see no significant loss of life if the peak voltage at its terminals stays at or below 1,000 V and the rise time is 2 microseconds or slower. A modern Class F motor on a short cable running a fan or pump is low risk. An old Class B motor on a long cable running a constant torque load is not.
Is 1600 V the NEMA rating for inverter duty motors?
No. Part 31 sets a multiplier, 3.1 times the motor's rated voltage, not a flat number. For a 460 V motor that is about 1,426 V peak, which a 1,600 V winding clears. For a 575 V motor it is about 1,783 V, which a 1,600 V winding does not.
What does the rise time limit in NEMA MG-1 mean?
It sets the fastest voltage edge the rating covers. Part 31 covers rise times of 0.1 microsecond or slower and Part 30 covers 2 microseconds or slower. A faster edge than the standard covers puts more stress on the first turns of the winding, so it is outside the rating even if the peak voltage is inside it.
Does service factor apply on a VFD?
Do not count on it. Many motors rated 1.15 service factor on sine wave power are limited to 1.0 on a drive, because PWM adds heat to the winding, low speed reduces cooling on a TEFC motor, and ambient and altitude take their share. Unless the motor maker permits it in writing, size the motor so its rated horsepower covers the load.
Online start-up courses, filmed on real drives
One drive per course, filmed uncut with a clock on screen from first power to a saved backup. The install course is free, and the ABB ACS380 and ACS580 start-up course is open now.