Field note

Lift Station VFDs: When They Pay and How to Set Them Up

Say a town puts drives on its duplex lift station to save power. The pumps now run at 38 Hz on 60 Hz motors most of the day, the bill barely moves, and a year later the crew is jetting the force main because the solids settled out. Nothing failed. The drives did exactly what they were set to do. Nobody asked what speed the force main needed or how much of the pump’s work was lift.

Lift stations are where the cube law gets tested hardest. This note covers why a drive often saves less than promised, when it is still worth it, the minimum speed the force main sets, level control, ragging, and water hammer. The broader question of when a drive pays on any pump is in the water and pump drives guide.

Why the savings are often small

A lift station pump has to overcome static head plus friction in the piping. The static head is set by the wet well level and the discharge end of the force main, not necessarily the pipe’s high point. At a given wet well level, slowing the pump reduces the flow and the friction loss, but it does not reduce the static head. On a station where most of the head is lift, slowing the pump cuts flow much faster than it cuts power, and below a certain speed the pump makes no flow at all.

The Hydraulic Institute puts a number on it with specific energy: the energy used divided by the volume pumped, in practice kWh per 1,000 gallons. On a low static head system, specific energy generally falls as the pump slows, though pump, motor and drive efficiencies all change at reduced speed. On a higher static head system, it reaches a low point and then starts climbing again as speed drops further. Running slower than that point costs more energy per gallon, not less. The way to find it is to measure input energy per gallon pumped at a few speeds and compare it with full speed cycling.

The Department of Energy has a case that makes the point. At the Welches Point lift station in Milford, Connecticut, engineers considered drives on the 75 HP pumps and passed. The wet well gave the station plenty of storage, so the outflow rate did not need to change often, and the DOE notes that drives are not generally recommended for systems with large static heads. Instead, one of the 3 original pumps was replaced with a smaller pump on a 35 HP motor that runs longer at a lower rate, with the big pumps saved for heavy inflow. Energy use dropped more than 15 percent, with a 5.4 year payback. Sometimes the right answer is a smaller pump, and a start-up tech who says so earns more trust than one who sells a drive.

When a drive is still worth it

Long force mains. When the force main is long and friction is a large part of the head, slowing the pump does save energy, the same as on any friction dominated system.

Flow pacing. A station that feeds a treatment plant can hand the plant a steady flow instead of slugs. The Ten States Standards call for considering variable speed pumps especially at stations that are part of treatment facilities, and for delivering as uniform a flow as practicable to limit hydraulic surges.

Running at the best speed. The Hydraulic Institute calls lift stations a prime application for combining variable speed with on/off control and some storage. When inflow is low, the pump cycles on and off at the speed where specific energy is lowest instead of at full speed. If that speed sits above the force main’s minimum, run there. It runs the pump longer per cycle, which can also mean fewer starts.

Soft starts and stops. A drive eliminates across-the-line starts on big pumps, and a controlled stop helps with water hammer. A soft starter can do much of that too, as covered below.

The minimum speed the force main sets

The lowest useful speed on a lift station is usually set by the force main, not the pump. The Ten States Standards size a station to keep at least 2 feet per second in the force main at its design pumping rates, so the solids stay in suspension. They do not say every drive operating point has to stay there. Some designs let the drive run below cleansing velocity and schedule a regular high speed run to flush the line. Holding 2 feet per second at all times is the conservative choice, and it is the one I would make unless the design calls for a flush schedule. Either way, 2 feet per second is a minimum, not a comfortable place to live: low spots still collect solids, and grease and grit build up over time.

Work out the flow that makes 2 feet per second from the force main’s inside diameter. Use the actual inside diameter for the pipe material and class, not the nominal size, because the two can differ enough to move the answer 10 percent or more. For a true 6 and 8 inch bore:

  • A 6 inch force main has about 0.196 square feet of area, so 2 feet per second is about 0.39 cubic feet per second, or roughly 175 gpm.
  • An 8 inch force main has about 0.349 square feet, so 2 feet per second is about 0.70 cubic feet per second, or roughly 315 gpm.

Find that flow on the pump and system curves. Then check the other limits, and keep them separate:

  • Zero flow speed. The speed where the pump’s shutoff head equals the static head and flow stops. It is about full speed times the square root of static head divided by shutoff head. A pump with 85 feet of shutoff head against 60 feet of static head stops moving water near 84 percent speed, about 50 Hz on a 60 Hz motor. This is not a limit you run near. It is the bottom under the next check.
  • Minimum continuous stable flow. The pump maker’s minimum flow to avoid recirculation, vibration and heating. Catalogs usually give it at full speed, so what matters is that flow on the reduced speed curve, against this system.
  • Motor and drive limits. Low speed cooling, which works differently on a submersible cooled by the sewage or a jacket than on a fan cooled motor, plus the maker’s speed range on a drive.

On a duplex station, the force main velocity depends on total flow, while the minimum stable flow applies to each running pump. Check them for one pump running and for two. Check the minimum speed at the highest normal static head too, which is the low end of the wet well band. The note on VFD for pumps and well pumps works through the zero flow math in more detail.

If the flow that makes 2 feet per second only comes near full speed, or the minimum stable flow sits up there, the drive buys a soft start and little else. The options then are a smaller pump, scheduled flush runs, or no drive at all.

The Ten States Standards also require flow measurement, indicating, totalizing and recording, at stations with variable frequency drives and at stations with a design peak hourly flow of 350 gpm or more. A drive station without a flow meter is guessing at all of the above. Check which version of the standards your state adopts, and any state rules on top of them.

Level control

A lift station’s job is to keep the wet well between its levels. With drives, the level becomes the process signal: the pump speeds up as the level rises and slows down as it falls, instead of starting at full speed on a float.

  • The level sensor. The Ten States Standards want level sensing located away from the turbulence of the incoming flow and the pump suctions, and require dual air compressors if a bubbler system is used. Submersible transducers, ultrasonic and radar sensors are all common. A level signal that bounces makes the drive hunt.
  • Backup floats. Keep a high level float and a low level float that work without the level transducer. Be clear about what they can do. A low float can stop the pumps through a hardwired path. A high float can alarm and call for pumping, but it cannot make a failed drive run its pump, so the high float needs an independent path to a pump that can still run: the other pump’s drive, a bypass starter, or whatever the design calls for. If the spec says the station has to pump with a drive failed, name that path and test it.
  • Alternation. The Ten States Standards require automatic alternation of the pumps in use. The pump drives named below can do it, but having the feature does not mean the station is wired and set up to alternate, so test it.
  • Wet well cycle time. The standards size the wet well for a fill time of no more than 30 minutes at design average flow, unless it is designed for flow equalization, and they defer to the pump maker’s duty cycle for the minimum cycle time. A drive that runs the pump longer and slower helps the motor on starts, but sewage held too long in the wet well goes septic, so the level band still has to turn the well over.

The water pump drives build this in. ABB’s ACQ580 has level control and multipump control. Yaskawa’s iQpump1000 has low and high water float inputs and pump down control. Danfoss’s VLT AQUA Drive FC 202 has cascade control for running several pumps together. Use the drive’s level features or the station controller’s, not both fighting each other. Wet wells are slow and noisy, so a simple proportional setup, minimum speed at the low level and full speed at the high level, usually hunts less than an aggressive PID loop.

Ragging

Wipes and rags wrap impellers. The first sign is usually less delivery and longer drawdown times, and the current often rises too, which is what the drives watch. Pump drives now have cleaning functions that run the pump through a sequence, often with reverse rotation, to shake the rag loose: ABB calls it pump cleaning, Danfoss calls it deragging, and Yaskawa’s iQpump has impeller anti-jam. Before turning on any sequence that reverses the pump, confirm with the pump maker that the pump is built to run backward, and watch the first few cleaning cycles. A cleaning cycle that runs every hour is telling you about the station, not the drive.

Water hammer and soft stops

When a lift station pump stops at full speed, the column in the force main can reverse and slam the check valve shut. A drive’s decel ramp slows the water before the pump stops and helps the check valve close gently, though it does not guarantee the valve seats before the flow turns around. A power loss gives no ramp at all, so the check valve and any surge protection have to be picked for the stop the drive cannot control. How well any controlled stop works depends on the force main profile, the check valve and the stop sequence. If the drive trips on overvoltage during a long decel, the note on VFD overvoltage faults covers it.

On a constant speed station, a soft starter is often the better tool. It cuts the starting current and the mechanical shock on the shaft and coupling, which is what a soft starter is for. Set it with a short start ramp. My rule is under 10 seconds and inside what the motor’s overload class allows, not a long ramp that tries to act like a drive. For the stop, pick a soft starter with a pump stop function. ABB’s PSTX, for example, has torque control, which follows a torque curve designed for pumps instead of a straight voltage ramp, because a pump on a simple linear ramp tends to hold speed and then drop off all at once at the end, which is the hammer. A soft starter does not change the pumping rate, so it gives no flow pacing or level control. The note on soft starter vs VFD covers that choice in general.

Classified areas and motor leads

Wet wells are often classified as hazardous locations under NFPA 820 and the local code. The drive normally goes outside the classified area, an explosion proof submersible motor has to be suitable for use on a drive, and its thermal protection has to be wired into the controls the way its listing and the approved design require. Long leads from the drive to a submersible motor also bring the output filter and grounding questions from well jobs, which the free First Power class covers.

Before you leave the site

Write down the force main size and actual inside diameter, the flow that makes 2 feet per second, the minimum speed and which limit set it, checked at the highest normal static head, the measured flow at minimum speed with the wet well level and which pumps were running, any flush schedule, the area classification and how motor thermal protection is wired, the level setpoints and the backup float levels, the alternation setup, the cleaning settings, the decel time, and the flow meter reading at minimum and full speed. Then watch the station through a few fill and draw cycles, and check the wet well for solids building up in the corners after the first month.

Setting up a 580 series drive for level control and pump cleaning is covered in the ABB 580 start-up class, and lead length, filters and grounding are in the free First Power class, both at The Tolbert School. The water and pump drives guide covers wells, boosters and when a drive pays.

Frequently Asked Questions

Does a VFD save energy on a lift station?

Usually less than people expect. Most lift stations spend much of their energy on static head, and static head does not drop when the pump slows down. The Hydraulic Institute notes that on higher static head systems, the energy per gallon pumped starts to rise again as speed drops. A drive still pays on some stations, especially with a long force main where friction is a large part of the head, and on stations that feed a treatment plant that wants steady flow.

What is the minimum speed for a lift station pump on a VFD?

The highest of three limits: the speed that keeps the force main at its cleansing velocity, usually 2 feet per second, unless the design uses a scheduled flush instead; the speed where each running pump stays above its minimum continuous stable flow against the static head; and the pump and motor maker's limits. On many stations the force main velocity sets the minimum.

Can a soft starter replace a VFD on a lift station?

On a constant speed station, often yes. A soft starter cuts the starting current and the mechanical shock, and soft starters with a pump stop function, such as ABB's torque control stop, slow the pump in a way that can reduce water hammer. A soft starter does not change the pumping rate, so it does not give flow pacing or level control.

Does a lift station with a VFD need a flow meter?

Yes, where your state has adopted the Ten States Standards. They require indicating, totalizing and recording flow measurement at stations with variable frequency drives, and at stations with a design peak hourly flow of 350 gpm or more. Check what your state adopts.

Online start-up courses, filmed on real drives

One drive per course, filmed uncut with a clock on screen from first power to a saved backup. The install course is free, and the ABB ACS380 and ACS580 start-up course is open now.

See the online courses

Wayward Leaders® is a veteran-owned VFD training practice. We teach maintenance teams and plant electricians to install, commission, and troubleshoot variable frequency drives correctly.

Every class ends with a scored competency assessment. The plant gets a way to prove what each technician can do, not a roster of who sat in the room.

The instruction is field-trained. It is drawn from nearly 8,000 VFD, power, and motor documents and from more than 750 commissioned drives captured through personal field experience and data collection. Carl Lee Tolbert, PhD, CMRP, and ATD Master Trainer™, leads it. He has delivered more than 5,000 hours of VFD instruction across 30 years and trained 8,000 industrial professionals, from International Paper to the U.S. Navy.

The premise is simple: VFDs do not fail. Installations fail them. The curriculum is built backward from that.

Installation, commissioning, troubleshooting, and fault diagnosis guides are published openly at waywardleaders.com.