The FRENIC-Ace tells you when a trip happened, through numbered codes like OC1, OC2, and OC3 for acceleration, deceleration, and steady speed, which most compact drives leave you to work out. For many alarms, the drive also stores a diagnostic subcode that narrows the cause. The core protections, overcurrent, overvoltage, undervoltage, overheat, and overload, are active from the factory. Several supplemental protection and early warning features are not, including a light alarm tier that keeps the motor running, so what this drive tells you depends a great deal on how it was set up.
Before you clear anything
The Ace keeps its last 4 alarms with a full record of what the drive was doing at each one, so a reset does not erase the history. It does clear the active display, and if the run command is still on when the alarm releases, the motor starts. Fuji’s own first instruction is to remove the cause, confirm every run command is off, and only then release the alarm.
Timing narrows the field faster than a meter does, and on this drive the code carries it. OC1 and OU1 happened on acceleration, which points at ramp time, inertia, torque boost, and current limit. OC2 and OU2 happened on deceleration, which points at regeneration. OC3 and OU3 happened at steady speed, which points at the load, the supply, and the wiring.
Turn the power off and wait at least 5 minutes on smaller units, FRN0115E2■-2, FRN0072E2■-4, and FRN0011E2■-7 and below, or at least 10 minutes on FRN0085E2■-4 and above. Confirm the keypad LEDs and charging lamp are out, then measure between P(+) and N(-) and confirm the DC bus is at 25 V DC or below before touching anything. Fuji also warns that with power on the input, voltage can appear on U, V, and W even after the drive has stopped the motor. Match PPE to the arc flash rating. Any live measurement on this page is for a qualified person, and retorquing terminals is always done de-energized.
Heavy alarms, light alarms, and what ships turned off
Fuji splits its protective functions into two tiers.
A heavy alarm displays the alarm code, trips the drive, and changes the state of the 30A/B/C fault relay. This is the tier every technician knows.
A light alarm displays l-al, blinks the KEYPAD CONTROL LED, and lets the drive keep running. It can drive a digital output, the L-ALM signal, if somebody assigns function 98 to Y1, Y2, or the relay in E20, E21, or E27. Function codes H81 and H82 decide which conditions are light alarms. Both ship at 0000, so out of the box every condition the manual allows as a light alarm is either a heavy alarm or nothing.
Several of the alarms can be either tier. Braking resistor overheat (dbH), cooling fin overheat (OH1), external alarm (OH2), inverter internal overheat (OH3), charging resistor overheat (OH6), motor overloads (OL1 and OL2), PID feedback wire break (CoF), RS-485 communications errors (Er8 and ErP), option errors (Er4 and Er5), speed deviation (ErE), and positioning error (Ero) can all be moved to the light alarm tier. A second group exists only as light alarms: DC fan lock (FAL), lifetime alarm (LiF), cooling fin overheat early warning (OH), overload early warning (OL), PID alarm (PId), PTC thermistor activated (PTC), reference command loss (rEF), machine life (rTE), startup count (CnT), and low torque detection (UTL).
Moving an alarm to the light tier is a protection decision, not a display preference. A motor overload or a heat sink overheat set as a light alarm lets the drive keep running through a condition that can damage the motor or the drive, so it belongs only where a stop is worse than the damage and somebody is watching the warning.
One detail catches people. When an alarm is assigned to the light tier, the 30A/B/C relay does not change state. If the plant watches only the fault relay, a light alarm is invisible to it until somebody wires L-ALM.
Fuji’s own protection table marks several supplemental functions as disabled by factory default: light alarm detection, overload prevention control (H70), anti-regenerative control (H69), the braking performance improvement (H71), reference loss detection (E65), the motor overload early warning (E34 and E35), retry (H04 and H05), forced stop (H56), and momentary power failure restart (F14). On a drive that keeps tripping, the first question is often which of these nobody turned on.
The quick table
The heavy alarms. “Retry” means the H04 auto reset can clear it. “Light” means H81 or H82 can make it a light alarm instead. OH6 is marked retry eligible in the Chapter 6 table but left out of the H04 description, so its retry status is unconfirmed.
| Code | Alarm | Retry | Light |
|---|---|---|---|
| OC1 | Instantaneous overcurrent during acceleration | Y | |
| OC2 | Instantaneous overcurrent during deceleration | Y | |
| OC3 | Instantaneous overcurrent at constant speed | Y | |
| OU1 | Overvoltage during acceleration | Y | |
| OU2 | Overvoltage during deceleration | Y | |
| OU3 | Overvoltage at constant speed | Y | |
| LU | Undervoltage | ||
| Lin | Input phase loss | ||
| OPL | Output phase loss | ||
| EF | Ground fault, FRN0085E2■-4 and above only | ||
| OH1 | Cooling fin overheat | Y | Y |
| OH2 | External alarm | Y | |
| OH3 | Inverter internal overheat | Y | Y |
| OH4 | Motor protection, PTC thermistor | Y | |
| OH6 | Charging resistor overheat | see note | Y |
| OL1, OL2 | Motor 1 and motor 2 overload | Y | Y |
| OLU | Inverter overload | Y | |
| OS | Overspeed | ||
| dbH | Braking resistor overheat | Y | Y |
| dbA | Braking transistor broken | ||
| EcF | Enable circuit failure, the STO circuit | ||
| Er1 | Memory error | ||
| Er2 | Keypad communications error | ||
| Er3 | CPU error | ||
| Er4 | Option communications error | Y | |
| Er5 | Option error | Y | |
| Er6 | Operation error | ||
| Er7 | Tuning error | ||
| Er8 | RS-485 communications error, port 1 | Y | |
| ErP | RS-485 communications error, port 2 | Y | |
| ErF | Data saving error during undervoltage | ||
| ErH | Hardware error | ||
| ErT | CAN communications failure | ||
| CoF | PID feedback wire break | Y | |
| FUS | DC fuse blown | ||
| PbF | Charger circuit fault, FRN0203E2■-4 and above | ||
| ErE | Speed inconsistency or excessive speed deviation | Y | |
| Erd | PM motor step out | ||
| PG | PG wire break | ||
| Ero | Positioning control error | Y | |
| EcL, Err | Customizable logic failure, simulated failure |
Where one code has several causes, the drive stores a subcode with it. The manual lists which subcodes mean what for undervoltage, tuning, operation errors, speed deviation, and the STO circuit. Subcodes marked “for manufacturer” are for Fuji, and the manual asks that you pass them along when you contact Fuji or send a drive for repair.
The fault details
OC1, OC2 and OC3, instantaneous overcurrent
What it means. Output current passed the drive’s instantaneous overcurrent level. OC1 happened during acceleration, OC2 during deceleration, and OC3 at constant speed.
Most likely cause. Fuji’s list starts with the motor wiring: a short between output phases, or a ground fault on the output lines. After that come overload or a sudden change in load, too much torque boost, a ramp too short for the inertia, electrical noise, and a motor already spinning when the drive started into it. On smaller models the manual also names a short between the PLC and CM terminals.
The fix, in order. Lock out, wait, and verify the bus. Disconnect the motor wiring at U, V, and W, measure phase to phase resistance on the motor side, and insulation test the cable and motor to ground. Do not megger the drive itself. Fuji says the inverter was insulation tested at the factory and asks that you avoid a megger test on it in the field. Megger the cable and motor phase to ground, T1, T2 and T3 to PE, with the drive disconnected. Use 500 V DC on a motor rated under 240 V, which covers the 200 V class Ace, and 1000 V DC on a 400 to 480 V motor, unless the motor manufacturer calls for something else. Under 1 megohm is a fail, 1 to 10 megohms means investigate, usually moisture or tired insulation, and over 10 megohms is generally healthy. The IEEE 43 minimum for a random wound motor is 5 megohms corrected to 40 C, which sits inside that investigate band, and why the 4.4 megohm number is wrong covers how to correct a cold reading. The 3 readings should sit within about 50 percent of each other, and a falling trend against earlier readings on the same motor says more than any single number. If the motor and wiring test clean, work the code. On OC1, lengthen acceleration in F07 and the other ramps, reduce manual torque boost in F09 if the motor does not stall without it, and look at the current limiter in F43. On OC2, lengthen deceleration. On OC3, measure and trend the running current for sudden changes in load. If the motor may be turning when the drive starts, turn on auto search in H09.
Worth knowing. H12, instantaneous overcurrent limiting, ships enabled. It lets the drive ride through short current spikes instead of tripping, which is why a hard OC on an Ace usually means something real.
When to stop. The separate EF ground fault alarm is specified only for FRN0085E2■-4 and above. On smaller units, expect an output ground fault to show up through the overcurrent protection as an OC, which is why Fuji puts the ground fault check at the top of the OC list. If OC trips return with the motor leads disconnected and the output open, the drive itself is the suspect and the next call is to Fuji.
OU1, OU2 and OU3, overvoltage
What it means. The DC bus went over its overvoltage level. OU1 happened during acceleration, OU2 during deceleration, and OU3 at constant speed.
Most likely cause. OU2 is regeneration on a deceleration ramp that is too short for the load’s inertia, the common one by a wide margin. OU1 points at a ramp that overshoots and then regenerates, which the manual ties to rapid acceleration. OU3 points at the supply: voltage above the drive’s range, or a surge from power factor capacitors or a thyristor converter switching on the same line.
The fix, in order. On OU2, lengthen deceleration in F08 and the other ramps, then turn on anti-regenerative control in H69 or the braking performance improvement in H71, both of which ship disabled. If the process needs a fast stop, the energy needs a path, which means a braking resistor. On OU3, measure the incoming supply. Fuji’s answer to capacitor switching surges is a DC reactor.
Worth knowing. Fuji gives one more option that few people try: setting F05, the rated voltage at base frequency, to 0 improves braking capability. Read the F05 description before you use it, because it changes how the drive applies voltage to the motor.
LU, undervoltage, and Lin, input phase loss
What it means. LU means the DC bus dropped below the undervoltage level. Lin means an input phase is missing or the phases are badly unbalanced.
Most likely cause. For LU, a momentary power failure, a supply below the drive’s range, a large motor starting on the same supply, a weak supply transformer, or a faulty contactor or breaker in the feed. The subcode tells you which version: subcode 1 is low voltage while the output was on with F14 at 0, subcode 2 is a run command applied during low voltage, and subcode 3 is an undervoltage trip on recovery from a momentary power failure with F14 at 1. For Lin, a broken input wire, a loose input terminal, unbalanced phases, repeated overload, or single phase power on a 3 phase drive.
The fix, in order. A qualified person measures the input voltage under load. Then lock out and check the input wiring and devices de-energized, and retorque the input terminals to the specified torque. For phase unbalance, Fuji recommends an AC reactor. For Lin caused by repeated overload, measure the bus ripple, and if it is large, the drive is too small.
Worth knowing. If you want the drive to ride through a momentary power failure instead of tripping, F14 set to 3, 4, or 5 restarts the motor depending on the load type. On units with separate auxiliary control power, Fuji warns that feeding R0 and T0 from the supply side of the breaker can cause a Lin alarm with no real phase loss. Input phase loss protection is bit 1 of H98, and it ships enabled.
OPL, output phase loss
What it means. One output phase is missing.
Most likely cause. A broken output wire, a broken motor winding, a loose output terminal, or a single phase motor connected to the drive, which the Ace cannot run.
The fix, in order. With the drive running, a qualified person measures the three output currents. Then lock out, retorque the output terminals de-energized, and check the motor and its wiring.
Worth knowing. Output phase loss protection is bit 2 of H98. On the smaller Ace models H98 ships at 83, and on FRN0085E2■-4 and above it ships at 19. Neither value includes bit 2, so output phase loss protection is off from the factory. An Ace running a motor with an open lead and no OPL alarm may simply have the protection turned off. Check bit 2 of the value actually set before changing it. On a drive still at the factory value, adding 4 turns it on, giving 87 or 23. On a drive somebody has already customized, set bit 2 without disturbing the other bits.
OH1, OH3, OLU, the drive’s own heat
What it means. OH1 is the heat sink running too hot. OH3 is the air inside the drive too hot. OLU is inverter overload, which Fuji describes as the temperature inside the drive rising abnormally.
Most likely cause. A surrounding temperature above the drive’s rating, blocked clearances, clogged fins, a cooling fan that has reached the end of its life or failed, overload, and on OLU, too much torque boost or too short a ramp. Fuji also names long motor leads for OLU, because the leakage current through a long cable heats the drive.
The fix, in order. Measure the air at the drive intake with the panel closed, not the room. Check the clearances and clean the fins. Check the fan, both by eye and by its run time in the maintenance information under Menu 5. On OH1, the subcode 6 means the drive detected the fan stopped. Then measure the output current and look at the load. For long leads, measure the leakage current, and Fuji’s answer is an output circuit filter.
Worth knowing. Overload prevention control, H70, will lower the output frequency before OH1 or OLU trips, and the motor overload early warning, E34, can warn you before the load gets that far. Both ship disabled. H70 only helps where the load drops as the speed drops, like a pump or a fan. Fuji says plainly that it has no effect on a load that does not fall with frequency and should not be used there, so leave it off on a conveyor or a positive displacement load. Lowering the carrier frequency in F26 also buys thermal headroom. Bit 0 of H98, automatic carrier lowering, ships enabled, so the drive already does some of this on its own.
OL1 and OL2, motor overload
What it means. The electronic thermal overload for motor 1 or motor 2 tripped.
Most likely cause. The thermal settings do not match the motor, the activation level in F11 is set wrong, the ramps are too short, the load is too heavy, or there is too much torque boost.
The fix, in order. Check the motor’s continuous allowable current against F11, and check F10 and F12 against the motor’s cooling and thermal time constant. Then measure the load. Fuji notes that loads tend to rise in winter, which is worth remembering for a fan or a conveyor that only trips in January.
Worth knowing. E34 and E35, the overload early warning, work on motor 1 only. Setting them gives you a signal before OL1 trips.
OH4, motor PTC thermistor
What it means. A PTC thermistor wired to the drive says the motor is too hot.
Most likely cause. A hot motor: high surrounding temperature, a failed motor cooling system, overload, too much torque boost, or a V/f pattern that does not match the motor nameplate. Then the setup: the H27 trip level set wrong, H26 and E59 set wrong, or the C1 terminal switches SW3 and SW4 in the wrong position.
The fix, in order. Check the motor before the drive. Then confirm F04 and F05 match the nameplate. For the setup, Fuji’s own correct configuration is E59 = 0 and H26 = 1, with SW3 on the C1 side and SW4 on the PTC side.
Worth knowing. If nobody wired a thermistor and the drive trips OH4, check H26. Set to 1, the drive expects a thermistor and trips on an open input. H26 = 2 keeps the motor running and raises the motor overheat signal THM instead. THM is its own output, function 56, which has to be assigned to Y1, Y2, or the relay in E20, E21, or E27. It is separate from the L-ALM light alarm output, and nothing outside the drive hears it unless somebody assigns it.
OH2, external alarm
What it means. The external alarm input, THR, opened. THR is digital input function 9, assigned in E01 to E05, E98, or E99.
The fix, in order. Find what opened. Then check the wiring to the THR terminal, and confirm the logic of the input matches the signal. A normally open device on an input expecting normally closed trips every time.
dbH and dbA, braking
What it means. dbH is braking resistor overheat, and dbA is a broken braking transistor.
Most likely cause. For dbH, too much braking load, a deceleration time that is too short, or F50, F51, and F52 set wrong for the resistor. For dbA, a failed transistor, sometimes from a wrong or misconnected resistor.
The fix, in order. For dbH, recalculate the braking duty against the real load, lengthen deceleration, and review the resistor selection. For dbA, check the resistance and connection of the braking resistor, then contact Fuji for repair.
Worth knowing. dbH is not measured on the resistor. The drive calculates it from the braking load and the settings in F50, F51, and F52, so it can trip while the resistor is cool if the settings are wrong. Fuji says to set those three codes while measuring the actual resistor surface temperature. Braking transistor error detection is bit 6 of H98.
EcF, the safe torque off circuit
What it means. The Ace removes torque through two enable inputs, EN1 and EN2. When either one goes off against PLC, the output transistors stop switching, which is safe torque off. EcF means the drive diagnosed a fault in that enable circuit.
Most likely cause. The subcode tells you. Subcode 10 is a contact problem on the interface board. Subcode 3000 is EN1 and EN2 not at the same logic level, meaning one channel opened without the other. Fuji’s terminal description is direct about this: operate EN1 and EN2 at the same time, or the drive issues EcF and disables operation. Any other subcode is a single failure in the safety circuit inside the drive.
The fix, in order. For subcode 3000, trace both channels from the safety relay or switch and confirm they switch together, High and High or Low and Low. For subcode 10, confirm the interface board is firmly seated. Both clear by cycling power. If EcF persists after that, the drive’s safety circuit has failed and it goes back to Fuji.
Worth knowing. The Ace ships with shorting bars across EN1 to PLC and EN2 to PLC. On a machine that does not use STO, those bars stay in. EN1 and EN2 are source only and cannot be switched to sink. A channel fault is a different condition from both channels opening, and the drive keeps them separate. Jumpering a safety circuit to clear a code is not troubleshooting.
Er8, ErP and ErT, communication
What it means. Er8 is an RS-485 error on port 1, ErP on port 2, and ErT a CAN bus failure.
Most likely cause. Settings that do not match the master, a master that stopped sending inside the time out, a bad RS-485 converter, a broken cable, noise, or a missing terminating resistor.
The fix, in order. Compare y01 through y10 for port 1, or y11 through y20 for port 2, against the master. Check the cable and its routing away from motor leads. Set the terminating resistor switches, SW2 for port 1 and SW6 for port 2, on at the end of the network. On CAN, check the baud rate in y24.
Worth knowing. These errors only count when the drive is taking its run or frequency command over RS-485. The drive ignores them while stopped. y02 decides what happens: 0 trips at once, 1 keeps running for the y03 timer and then trips, 2 retries for the y03 timer and keeps running if communication comes back, and 3 keeps running no matter what. y08, the no response time out, ships at 0, which Fuji describes as not checking the time out at all. An Ace under Modbus control left at that default will not notice if the master stops talking. Set y08 and test the loss of communication with the machine in a safe state.
Er6, operation error
What it means. Somebody did something the drive was set to refuse. The subcode tells you what.
Most likely cause. Subcode 1 is the STOP key pressed while H96 makes it active and the run command came from the terminals or the network, or the forced stop input STOP going off. Subcodes 2 to 6 are the start check function, which refuses to start the motor when a run command is already present at power on, at alarm reset, or when the command source switches to the network.
The fix, in order. Review the run sequence so the run command is off at those moments, and turn the run command off before releasing an alarm. If the behavior was not intended, check H96.
Worth knowing. H96 ships at 3 on the U destination for the USA, STOP key priority and start check both on, and at 0 on the other destinations, including the J destination of the bench unit. Two identical Ace drives from different destinations will handle a run command at power up differently.
Er7, tuning error
What it means. Auto tuning failed. The subcode says why, from a run command dropped mid tune to an alarm during tuning or an EN terminal failure.
Most likely cause. A missing motor phase, motor data that does not match the nameplate, a motor cable over 50 m on a small drive, a motor several sizes off from the drive, a special motor such as a high speed motor, or a rotating tune with the motor brake set.
The fix, in order. Connect the motor properly, check F04, F05, P02, and P03 against the nameplate, release the brake for a rotating tune or use the static tune with P04 = 1, and for long leads or mismatched motors, disable auto tuning and auto torque boost with F37 = 1 and enter the motor constants by hand.
Er1, Er2, Er3, ErF, ErH, FUS, OH6 and PbF, internal and power section faults
What it means. Er1 is a memory error, Er2 a keypad communications error, Er3 a CPU error, ErF a failure to save data at power down, ErH a bad connection between the control and power boards, FUS a blown internal DC fuse, OH6 charging resistor overheat, and PbF a charger circuit fault on the larger models.
The fix, in order. For Er1, Fuji’s procedure is to initialize with H03, check whether the alarm releases, and then restore the settings, so have the saved parameter file ready. For Er2, check the keypad cable and connector, and check that bundled control wires are not lifting the front cover off the keypad. For Er3 and ErF, look for noise and grounding problems first. For OH6, Fuji’s answer is to cycle power no more than once per 30 minutes, and if OH6 appears on every power up, the charging circuit has failed. For PbF, do not flick the breaker on and off quickly while checking wiring. Wait for the bus to drop, release the alarm, and power up once. ErH and FUS go to Fuji for repair.
Worth knowing. Err is a simulated failure that appears when somebody holds two keys for 5 seconds or more, and H45 can generate a mock alarm on purpose. Both are useful for testing an alarm circuit and confusing when nobody knows they exist.
The faults you prevent are the ones you never read
The Ace keeps a detailed record, and it is often overlooked.
The alarm history holds the last 4 alarms under Menu 6, Alarm Information. With an alarm on the display, the arrow keys step back through the 3 before it. Viewing the full alarm information menu needs E52 set to 2, the full menu mode.
The alarm information for each of the 4 alarms includes the output frequency, output current, output voltage, calculated torque, reference frequency, rotation direction, running status, cumulative power on time, number of startups, DC bus voltage, internal temperature on the larger models, heat sink temperature, the digital input and output terminal status, how many times the same alarm occurred in a row, and any other alarms that were active at the same moment. These are values captured at the trip, not a waveform, so they may not show the exact peak of a fast transient.
The terminal status and the consecutive count repay attention. The terminal status shows whether the run command and the permissives were present when the drive stopped. The consecutive count tells you whether this is a single trip or the drive retrying into the same fault over and over.
The light alarm history lives separately, in Menu 5 maintenance information, items 5_36 through 5_39, the latest and the 3 before it. Menu 5 also holds the cooling fan run time and the capacitor life data that warn you before OH1 and the lifetime alarm do.
H97 = 1 clears the alarm data. Read it before anybody uses it.
Reading and clearing faults
Remove the cause, confirm the run command is off, and press the reset key, or switch a digital input assigned to RST off and on. A reset does nothing while the cause is still present, and with several alarms active, nothing releases until every cause is gone. If the run status information is on the display after the cause is removed, pressing the key twice releases the alarm, and the motor starts if a run command is present.
Auto reset lives in H04 and H05. H04 sets the number of attempts, 0 to 20, and ships at 0. H05 sets the interval, 0.5 to 20.0 seconds, and ships at 5.0. Only some alarms are eligible: OC1 to OC3, OU1 to OU3, OH1, OH3, OH4, OL1, OL2, OLU, and dbH, which is the list in the H04 description. The alarm table in Chapter 6 also marks OH6 as retry eligible, so treat OH6 as unconfirmed until you see it on your own drive. Fuji notes that during auto reset the drive does not put out an alarm signal, so a drive retrying into a real fault looks healthy from the outside until it runs out of attempts. The consecutive count in the alarm information is how you catch it afterward. Fuji also warns to design the machine so a restart is safe for people and equipment, because a drive that restarts itself is attached to a machine that starts itself.
Where this fits
Most of what appears on this page was decided before the drive was first powered: the destination setting, the supply, the motor cable length, the cabinet, the motor data somebody entered, and which of the protective functions somebody bothered to switch on. The VFD Installation Guide and the VFD Troubleshooting Guide cover the work that keeps those decisions from showing up later as alarms.
The same treatment for other platforms is in the ABB Drive Fault Field Guide, the PowerFlex 525 Fault Field Guide, the Yaskawa Fault Field Guide, the Invertek Optidrive E3 Fault Field Guide, and the AutomationDirect GS20 Fault Field Guide, and every brand is listed on the guides page. For the competency behind the codes, that is what the VFD training does, and Before the First Fault is the field record the approach came out of.
Alarm codes, function codes, and behavior on this page are taken from the Fuji Electric FRENIC-Ace User’s Manual 24A7-E-0043e and the FRENIC-Ace Instruction Manual INR-SI47-1733f-E. Factory defaults vary by destination and capacity, so confirm against the manual revision and the destination code of the drive in front of you. Fuji Electric and FRENIC-Ace are trademarks of Fuji Electric Co., Ltd., used here for identification.
Frequently Asked Questions
What is the difference between OC1, OC2 and OC3 on a FRENIC-Ace?
All three are instantaneous overcurrent. OC1 happened during acceleration, OC2 during deceleration, and OC3 at constant speed. Fuji's first checks for all three are a short between output phases and a ground fault on the output wiring, then load, torque boost, and ramp times.
What does l-al mean on a FRENIC-Ace?
It is a light alarm. The drive found a condition you chose to treat as a warning, and it keeps running. H81 and H82 decide which conditions are light alarms, and both ship at 0000. The cause is in Menu 5, items 5_36 to 5_39. The 30A/B/C fault relay does not operate on a light alarm, so use the L-ALM output if you want a contact.
Why doesn't my FRENIC-Ace trip on output phase loss?
Output phase loss protection is bit 2 of H98, and the factory values, 83 on smaller units and 19 on larger ones, leave it off. Check bit 2 of the current value first. At the factory value, adding 4 turns it on.
What does EcF mean on a FRENIC-Ace?
A fault in the enable circuit that provides safe torque off. Subcode 3000 means EN1 and EN2 were not at the same logic level, so one STO channel opened without the other. Subcode 10 is an interface board contact problem. Both clear by cycling power. Any other subcode is an internal safety circuit failure.
Why does my FRENIC-Ace keep running when the PLC stops communicating?
y08, the RS-485 no response time out, ships at 0, which does not check for a time out. Set y08, choose the response in y02, and test it with the machine in a safe state.
Where does the FRENIC-Ace store its alarm history?
Menu 6, Alarm Information, holds the last 4 alarms, each with output frequency, current, voltage, torque, DC bus voltage, heat sink temperature, terminal status, run time, startup count, and the number of consecutive occurrences. Set E52 to 2 to see the full menu.
Online start-up courses, filmed on real drives
One drive per course, filmed uncut with a clock on screen from first power to a saved backup. The install course is free, and the ABB ACS380 and ACS580 start-up course is open now.