A booster station drive fails on a Saturday. The truck has a 580 with the right voltage and current rating, and the label says ACS580 instead of ACQ580. Whether it can run that pump until Monday depends on which pump features the ACQ580 was actually using, and on how old the ACS580’s firmware is.
This is the water version of the ACH580 vs ACS580 comparison. The general pump setup (minimum speeds, ramps and filters) is in VFD for pumps and well pumps.
Same hardware family, different control program
ABB treats the ACS580, ACH580 and ACQ580 as one hardware family with the same frame sizes. For this comparison, the control program is the main difference, and a matching frame and voltage do not make two units interchangeable. The ACS580 runs the standard control program for general purpose machines. The ACH580 runs the HVAC control program. The ACQ580 runs the pump control program for water and wastewater, and its default setup is a water configuration instead of the ACS580’s list of general purpose macros.
What changes is what the drive knows about pumps.
The ACS580 caught up on some of it
This is the part that surprises people. ACS580 standard control program version 2.20 has dry pump protection, soft pipe fill, pump cleaning and cavitation control, and version 2.05 had none of the four. Sleep boost and pump and fan control (PFC and soft PFC), for running several motors from one drive, were already in version 2.05.
So “the ACS580 doesn’t have pump features” is only true on older drives. A newer ACS580 can do a lot of what a small pump job needs. Check the firmware version in the drive’s system information before deciding either way.
What the ACQ580 still adds
| Feature | ACQ580 (pump control program) | ACS580 (standard program, version 2.20) |
|---|---|---|
| Multiple pumps | Intelligent pump control: up to 8 drives linked, each pump on its own drive, with master autochange, plus single drive PFC and soft PFC | PFC and soft PFC from one drive |
| Level control | Yes, for filling and emptying | Not in the standard program |
| Quick ramps for submersibles | Two extra ramp stages built for borehole pumps | Two ramp sets, with automatic switching above a set frequency |
| Flow without a meter | Sensorless flow calculation from the pump’s curves | No |
| Check valve leak detection | Yes | No |
| Dry pump, soft pipe fill, pump cleaning, cavitation | Yes | Yes on current firmware, not on older firmware |
| Keypad | Hand-Off-Auto panel by default | Standard assistant panel |
| Embedded fieldbus | Modbus RTU | Modbus RTU |
Intelligent pump control. The ACQ580 links up to 8 drives, one per pump, over the embedded fieldbus port. If the running pumps cannot meet demand, the system starts pumps one at a time, and drops them one at a time as demand falls. If one pump or drive is down, the others can take over, within the capacity that is left and the way the system is set up. The master role can move from drive to drive automatically. The ACS580’s PFC runs extra motors from one drive’s relay outputs, which works, but if that one drive goes down, so does the control. One more thing about that link: because intelligent pump control uses the embedded fieldbus port, that port is not free for a SCADA connection on those drives.
Level control. Lift stations and tank fill jobs control on level, not pressure. The ACQ580 has a level control function for filling and emptying, with the pump starts, stops and alternation built in. An ACS580 can hold a single pump at a constant level with its PID loop, but the multi-pump fill and empty logic lives in a PLC or a station controller. The lift station VFD note covers level control setup.
Quick ramps. ABB built these for submersible pumps, where getting up to speed quickly lifts the impeller and lets the water protect the bearings and seals. The motor maker sets the target: Franklin, for example, wants 30 Hz within 1 second. ABB’s own example is a first stage from standstill to 25 or 30 Hz in 1 second, with an optional second stage up through the range where the pump starts moving water against the static head. One thing to watch: ABB sets the quick ramp times against the full speed scale, so the actual time is the set time multiplied by the stage’s span divided by the full scale. A stage set for 30 seconds across 20 to 40 Hz on a 60 Hz scale takes 10 seconds. Check the real ramp with a stopwatch.
Sensorless flow calculation. The ACQ580 estimates flow from the pump’s head and power curves entered in the drive. It is an estimate for trending and for spotting a pump that is wearing, not a flow meter for billing, compliance or primary protection.
Check valve leak detection. When a check valve leaks, water flows back through the pump and spins it backward while the drive is stopped. The ACQ580 can briefly check the motor’s speed while stopped and warn or trip if the pump is turning. It only catches leaks big enough to spin the pump backward, but those are the ones that hurt on the next start.
Hand-Off-Auto. The ACQ580’s default keypad is ABB’s Hand-Off-Auto panel, the same style operators see on the ACH580. The ACS580’s standard panel does the same job with local and remote control, which works differently and can confuse an operator used to three buttons.
Can the ACS580 go in on Saturday?
An ACS580 can sometimes replace an ACQ580 on a single pump. Before it goes in, list every control and protection function the old drive did and decide how each one will be kept.
| What the ACQ580 was doing | Can an ACS580 stand in? |
|---|---|
| Single pump holding constant pressure or constant level with PID from one transducer | Possibly, with the PID, sleep and protection rebuilt and tested |
| Submersible well pump | Possibly, with two ramp sets set to meet the motor maker’s ramp rule |
| Dry pump, pipe fill or pump cleaning | Only on firmware that has them, set up from scratch |
| One of several drives in an intelligent pump control system | Not as a drop-in. The other drives expect an ACQ580 on the link |
| The ACQ580 level control function on a lift station or tank: fill and empty bands, alternation and pump staging | Not without that logic moving to a PLC or station controller |
| Check valve leak detection or sensorless flow | No. Those functions are not in the standard program |
Before an ACS580 goes in
- Firmware and options. Read the firmware version in the drive’s system information, since it decides which pump features exist. Check the full type code and the option modules and I/O extensions, not just the frame and voltage.
- Ratings. Current rating at or above the motor’s nameplate amps, or the submersible’s maximum amps, at the right duty rating, plus enclosure and short circuit rating.
- Filters and cable. Confirm the existing dV/dt or sine filter suits the replacement drive and its switching frequency, and that the motor cable length is inside the drive’s limits. Long submersible leads are where swaps go wrong.
- Motor data. Enter the motor nameplate data and run the motor identification the drive maker calls for, because the setup starts from scratch.
- Ramps. On a submersible, set the fast ramp to reach the motor maker’s minimum speed in time, and switch to the normal ramp above it. Time it.
- Protection. Rebuild dry pump or underload protection and low level protection, and test them with a safe method. Do not run the pump dry to prove the trip. On a well, this is not optional.
- Backspin. Without check valve leak detection, confirm the check valve holds, or that the pump is stopped, before the first start.
- I/O and communication. Every input and output the old drive used: start, transducer, level, floats, interlocks, alarms, and any link to other drives. Both drives have Modbus RTU built in, but their register maps differ, so if SCADA reads the drive, redo the points list.
- Hand mode. Confirm which interlocks stay active in Hand on the replacement, and show the operators how its local and remote control works.
- The setup. Keep the old backup as a reference. The control programs differ, so do not plan on loading it into the ACS580. Ask ABB technical support before trying to move a backup or a control program between the two.
- The tests. A full cycle: start, run to setpoint, sleep, wake, plus stop, restart, interlock and alarm behavior. A pump reaching setpoint does not prove the station is ready for automatic service.
- Write it down. Record the swap as a temporary change and plan to put the right drive back, so the stand-in does not become the station’s standard.
Which one to order
Order the ACQ580 when the station relies on its pump functions, multipump control, level control, quick ramps, flow estimation or check valve detection, or when the operators expect a Hand-Off-Auto keypad. Order the ACS580 for general purpose machines, and keep in mind that a current one can cover a simple single pump job. Ultra low harmonic versions are available in the 580 family, including the ACQ580-31 and -34, for jobs where the harmonic study calls for them. Write the model and the firmware version on the spare parts list for each drive.
Setting up the ACQ580, ACS580 and ACH580 is covered in the ABB 580 start-up class at The Tolbert School. The water and pump drives guide covers wells, boosters and lift stations across the major pump drive brands.
Frequently Asked Questions
What is the difference between the ABB ACQ580 and ACS580?
They share ABB's 580 hardware family and run different control programs. The ACQ580 runs ABB's pump control program, with intelligent multipump control for up to 8 drives, level control, quick ramps for submersible pumps, sensorless flow calculation and check valve leak detection, and it ships with a Hand-Off-Auto panel as its default keypad. The ACS580 runs the standard control program for general purpose machines. ACS580 firmware version 2.20 also has dry pump protection, soft pipe fill, pump cleaning and cavitation control, which version 2.05 did not.
Can an ACS580 run a submersible well pump?
It can run the pump, if it is set up for the motor maker's rules. The ACS580 can switch to a second ramp set automatically above a set frequency, so it can be set to reach the minimum speed fast and then ramp normally. The ACQ580's quick ramps do that job directly. Either way, the motor maker's minimum speed, ramp, filter and underload rules still apply.
Does the ACS580 have pump cleaning and soft pipe fill?
On current firmware, yes. ACS580 standard control program version 2.20 has dry pump protection, soft pipe fill, pump cleaning and cavitation control. Version 2.05 did not. Check the firmware version on the drive before counting on any of these.
Can I load an ACQ580 parameter backup into an ACS580?
Do not count on it. The two run different control programs with different parameter groups. Whether a backup or a control program can be moved between the two in the field is a question for ABB technical support. Until they say otherwise, set the replacement up from the start-up record and test every function the pump depends on.