The VF-AS3 sorts what it tells you into four tiers, trips, alarms, pre-alarms, and messages, and the first job on a stopped Toshiba is working out which one you are looking at. The second job is checking the defaults, because several conditions a technician would expect to trip are set by Toshiba to stop the drive quietly or to be ignored entirely. Undervoltage stops without tripping, output phase loss detection is off, and a lost RS485 master is ignored unless two settings are changed. Each of those is a sensible factory choice and a trap for anyone who assumes otherwise.
Before you clear anything
The VF-AS3 keeps the last 8 trips with 13 items of detail each, including the date and time, and that history survives a reset and a power cycle. Write down the trip and what the machine was doing anyway, because the record holds values the drive detected, and Toshiba notes they are not always the true peak because detection takes time.
Timing narrows the field, and on this drive the code usually carries it. OC1 and OP1 happened during acceleration, OC2 and OP2 during deceleration, and OC3 and OP3 at constant speed.
Turn the power off and wait at least 15 minutes. Confirm the charge lamp is out, then measure between PA/+ and PC/- with a meter rated for at least 800 V DC and confirm the DC main circuit is at 45 V or less. Toshiba also asks you to check that the residual voltage on the AC main circuit cables is 45 V or less. On a PM motor, the output terminals can be live while the motor is turning even with the drive off, so make sure the motor is stopped. Match PPE to the arc flash rating. Live measurements are for a qualified person, and retorquing terminals is done de-energized.
Trips, alarms, pre-alarms, and messages
Toshiba defines four kinds of indication, and they behave differently.
A trip turns the inverter output off to protect the drive or the equipment. The failure signal goes out on the FL relay by default. Trips are what most of this page covers.
An alarm means a condition that could damage the drive or the equipment if it continued. Alarms blink on the panel. MOFF, the main circuit undervoltage alarm, is the one technicians meet most often, and it stops the drive without tripping.
A pre-alarm means the drive is near a trip level. During operation the panel shows “Overcurrent alarm”, “Overvoltage alarm”, “Motor/Inverter overload alarm”, or “Overheat alarm”, and each can drive an output terminal if assigned. The overload pre-alarm comes on when the overload count reaches 50 percent of the trip value.
A message is information, not an alarm. Some of them look alarming. E1, E2, and E3 mean the panel display overflowed by one, two, or three digits. CLr means the drive is ready to accept a reset. EOFF means one more press of STOP will apply emergency off. None of these is a fault.
Many trips on the VF-AS3 can be switched on or off by a parameter, and the manual marks each of those with an asterisk. A drive that should have tripped on something and did not may simply have that trip disabled.
Every trip also carries a failure code, a number with a hex equivalent, such as OC1 at 1 (0x0001) or Err5 at 24 (0x0018). That is the value a PLC reads over communication.
The quick table
The trips you meet on a running machine. An asterisk means the trip can be enabled or disabled by parameter.
| Display | Code | Trip |
|---|---|---|
| OC1 | 1 | Overcurrent during acceleration |
| OC2 | 2 | Overcurrent during deceleration |
| OC3 | 3 | Overcurrent at constant speed |
| OCL | 4 | Overcurrent, load side at startup |
| OCA1, OCA2, OCA3 | 5 to 7 | Overcurrent in the U, V, or W phase arm (IGBT) |
| EPHI | 8 | Input phase loss * |
| EPHO | 9 | Output phase loss * |
| OP1 | 10 | Overvoltage during acceleration |
| OP2 | 11 | Overvoltage during deceleration |
| OP3 | 12 | Overvoltage at constant speed |
| OL1 | 13 | Overload, inverter |
| OL2 | 14 | Overload, motor * |
| OLr | 15 | Overload, braking resistor * |
| OH | 16 | Overheat |
| E | 17 | Emergency off |
| EEP1, EEP2, EEP3 | 18 to 20 | EEPROM fault |
| Err2 to Err4, Err6, Err7 | 21 to 23, 25, 26 | RAM, ROM, CPU, gate array, current detector faults |
| Err5 | 24 | RS485 communication time out |
| Err8 | 27 | Communication option time out |
| Err9 | 28 | Panel disconnected during run |
| UC | 29 | Undercurrent * |
| UP1 | 30 | Undervoltage, power circuit * |
| Ot | 32 | Overtorque * |
| EF2 | 34 | Grounding fault * |
| OCr | 36 | Overcurrent, braking resistor circuit (larger 480 V models) |
| Etn, Etn1 to Etn3 | 40, 84 to 86 | Auto tuning errors |
| EtyP | 41 | Inverter type error |
| E-11 | 43 | Brake answer error * |
| E-12 | 44 | PG error |
| E-13 | 45 | Abnormal speed |
| OH2 | 46 | External thermal trip * |
| SOUT | 47 | PM motor step out * |
| E-18 | 50 | Analog input disconnection * |
| E-19, E-21, E-26 | 51, 53, 58 | CPU communication and CPU faults |
| E-20 | 52 | Over torque boost |
| E-23 to E-25 | 55 to 57 | Option fault, slot A, B, or C |
| PrF | 59 | STO circuit fault |
| Ut | 60 | Undertorque * |
| OL3 | 62 | Overload, IGBT |
| E-31 | 63 | Rush current suppression relay fault |
| E-32 | 64 | PTC failure |
| Ot2 | 65 | Overtorque 2 |
| OtC3, UtC3 | 72, 73 | Shock monitoring, over and under * |
| E-42 | 74 | Cooling fan fault |
| E-43 | 75 | Embedded Ethernet communication time out |
| E-44 | 76 | Panel battery failure |
| E-99 | 88 | Trip for test * |
The alarms worth knowing are MOFF, main circuit undervoltage; PrA, STO activated; A-18, analog input disconnection when set to alarm rather than trip; A-09, panel disconnected; A-17, a panel key held for 20 seconds or failed; t, communication close to a time out; and COFF and A-29 for the optional control power supply.
The trip details
OC1, OC2 and OC3, overcurrent
What it means. Output current passed the drive’s limit. OC1 happened during acceleration, OC2 during deceleration, and OC3 at constant speed.
Most likely cause. For OC1, an acceleration time too short, a V/f pattern in Pt that does not match the machine, a restart into a motor still turning after a power dip, a special or low inductance motor such as a high speed motor, or reversed PG polarity in closed loop. For OC2, a deceleration time too short. For OC3, a sudden change in load or something jammed in the machine. All three list a possible grounding fault and leakage current from a long motor cable.
The fix, in order. Lock out, wait the 15 minutes, and verify the bus. Disconnect the motor at U, V, and W and megger the cable and motor phase to ground, never through the drive. Use 500 V DC on a motor rated under 240 V and 1000 V DC on a 400 to 480 V motor, unless the motor manufacturer calls for something else. Under 1 megohm is a fail, 1 to 10 megohms means investigate, usually moisture or tired insulation, and over 10 megohms is generally healthy. The IEEE 43 minimum for a random wound motor is 5 megohms corrected to 40 C, which sits inside that investigate band, and why the 4.4 megohm number is wrong covers how to correct a cold reading. The 3 readings should sit within about 50 percent of each other, and a falling trend against earlier readings on the same motor says more than any single number. If the motor and wiring test clean, work the code. On OC1, lengthen ACC, and with Pt at 0, 1, 2, or 7, lower vb, the manual torque boost. For other Pt settings, run offline auto tuning with F400. If the motor may be turning at start, set F301, auto restart. On OC2, lengthen dEC. On OC3, look at the machine. For long motor leads, Toshiba refers you to its leakage current measures in section 2.4.3.
Worth knowing. Toshiba’s standard short circuit check at start uses a 50 microsecond pulse. On a low impedance motor such as a high speed motor, that check can trip falsely, and F613 with F614 lets you use a shorter pulse. F614 set to 0 with F613 at 2 or 3 turns the startup short circuit check off altogether. Changing either can mask a real short, so change them only for the motor type that needs it and never just to clear a trip.
OCL, OCA1 to OCA3 and OCr, the other overcurrent trips
What it means. OCL is a short or overcurrent on the load side found at startup. OCA1, OCA2, and OCA3 are faults in the IGBT in the U, V, or W phase arm. OCr is overcurrent in the braking resistor circuit on the larger 480 V models.
Most likely cause. For OCL, a short on the output, defective insulation in the motor or wiring, or a low impedance motor. For OCA1 to OCA3, a failed power device inside the drive. For OCr, a missing or disconnected braking resistor with F304 enabled, a resistor below the minimum allowed value, a short between PB and PC/-, or a failed braking IGBT.
The fix, in order. For OCL, check the output wiring and insulation, then look at F613. For OCA1 to OCA3, Toshiba’s measure is one line: fault in internal inverter, contact your Toshiba distributor. For OCr, confirm the right resistor is connected, or set F304 to disabled if no resistor is needed.
Worth knowing. OCr cannot be reset from the panel. It clears only by turning the power off and back on.
OP1, OP2 and OP3, overvoltage
What it means. The DC bus went over its limit. Toshiba uses OP for overvoltage rather than OV. OP1 happened during acceleration, OP2 during deceleration, and OP3 at constant speed.
Most likely cause. OP2 is the common one: a deceleration time too short for the regenerated energy, or F305, the overvoltage limit operation, set to disabled. All three list a high or fluctuating supply, a supply of 500 kVA or more, power factor capacitors switching, or thyristor equipment on the same system. OP3 adds a supply grounded at a point other than the neutral, such as a corner grounded delta, and a load that drives the motor into regeneration.
The fix, in order. On OP2, lengthen dEC and make sure F305 is set to 0, 2, or 3 so the overvoltage limit operation is active. If the deceleration time cannot grow, install a braking resistor. For supply problems, an input AC reactor. On a corner grounded supply, an IT system, or any supply grounded other than at the neutral, Toshiba says the grounding capacitor must not be grounded or increased, and section 2.3.4 gives the switching method. How it is done depends on the frame size, and changing it can affect EMC compliance, so follow that section for the drive in front of you rather than a general rule.
Worth knowing. OP1 on a restart into a turning motor is the same story as OC1, and F301 auto restart with F302 is Toshiba’s answer to both.
UP1 and MOFF, undervoltage
What it means. The power circuit voltage dropped. What the drive does next depends on F627.
Most likely cause. A sag, a supply outage, a soft supply, or a loose connection in the feed.
The fix, in order. A qualified person measures the input voltage under load. Then lock out and check the feed de-energized. Review F625, the undervoltage detection level.
Worth knowing. F627, the undervoltage trip, ships at 0, disabled. With the default, an undervoltage shows MOFF and the drive stops, but it does not trip and the failure signal on FL does not operate. Only with F627 set to 1 does it trip as UP1. A drive that stopped for no recorded reason may have seen a MOFF. To ride through a momentary power failure instead, Toshiba suggests leaving F627 disabled and setting F301 and F302 to 1. F719 decides whether the run command is held or cleared after a MOFF, which decides whether the drive restarts itself when power returns. It ships at 2, which clears the run command at a coast stop and at MOFF during panel or RS485 run, so by default the drive does not restart itself after a MOFF in those modes.
EPHI and EPHO, phase loss
What it means. EPHI is input phase loss. EPHO is output phase loss, which can also trigger when output current is very small, under 8 percent of motor rated current.
Most likely cause. A blown fuse, a loose terminal, or a failed contactor pole on the side named.
The fix, in order. Check the wiring and protective devices on the side the code names.
Worth knowing. F608, input phase loss trip, ships enabled. F605, output phase loss detection, ships at 0, disabled. Settings 1 through 4 check at the first start after power on, at every start, during run, or at every start and during run. An AS3 running a motor with an open lead and no EPHO may simply have the check turned off. On a lightly loaded motor, the under 8 percent rule can cause a nuisance EPHO, and on a PM motor EPHO can occur regardless of F605. Setting 5 is a different function, output shut off detection, for systems that disconnect the motor at the output. Toshiba gives two cautions. In the F605 section, it says not to use output phase loss detection when Pt, the V/f pattern, is 5, 6, or 12. In the F301 auto restart section, it says not to set F605 to 1, 2, or 4 when auto restart is used, and the F605 section notes that detection is not performed during auto restart. Confirm the control mode and the restart settings before enabling it.
EF2, grounding fault
What it means. A ground fault in the output wiring or the motor.
Most likely cause. Insulation breaking down in the cable or motor. Toshiba adds that on some motors a very fast acceleration or deceleration can cause it.
The fix, in order. Megger the output wiring and motor with the drive disconnected, at the voltage and bands given under OC1 to OC3 above. If they test clean, lengthen ACC and dEC.
Worth knowing. EF2 is one of the trips that can be disabled by parameter. A drive that never shows EF2 is not proof the motor is healthy.
OL1, OL2, OL3 and OLr, overloads
What it means. Four overloads. OL1 is the inverter, OL2 is the motor, OL3 is the IGBT, and OLr is the braking resistor.
Most likely cause. For OL1, a fast acceleration, a V/f pattern that does not suit the machine, a restart into a turning motor, too much DC braking, or a drive too small for the load. For OL2, a locked motor, long running at low speed, a real overload, or electronic thermal settings that do not match the motor. For OL3, overload at low speed, 15 Hz or less, with a high carrier frequency. For OLr, too much braking or a deceleration time too short.
The fix, in order. For OL2, set the electronic thermal to match the motor in OLM and tHrA, then look at the machine. For OL1, lengthen ACC, set Pt to suit the machine, and reduce F251 and F252 if DC braking is heavy. For OL3, reduce the load, lower F300, the carrier frequency, or set F316 to let the drive lower it, and look at the stall prevention level. For OLr, lengthen dEC or fit a larger resistor and set F309 to match.
Worth knowing. The motor and inverter overload pre-alarm comes on at 50 percent of the overload trip value, and an output assigned to it gives the PLC a warning long before OL1 or OL2 stops the line.
OH, OH2 and E-32, temperature
What it means. OH is the drive overheating. OH2 is an external thermal trip input. E-32 is a PTC failure, either the motor PTC protection or a fault in the drive’s PTC circuit.
Most likely cause. For OH, a cooling fan not running, a high ambient, a blocked fan vent, or another heat source mounted nearby. For OH2, a motor running hot enough to open its external thermal device. For E-32, a hot motor or a failed PTC circuit.
The fix, in order. For OH, check the fan while running, lower the ambient, clear the vent, and move heat sources away, then reset after the drive cools. For OH2 and E-32, check the motor first.
Worth knowing. E-42 is a separate trip for a failed cooling fan, and the cooling fan and capacitor replacement alarms live in the monitor mode parts replacement information. The overheat pre-alarm warns before OH trips.
Ot, Ot2, UC, Ut, OtC3 and UtC3, load monitoring
What it means. Ot is overtorque, Ot2 is a stall at the stall prevention or torque limit level for longer than F452, UC is undercurrent, Ut is undertorque, and OtC3 and UtC3 come from the shock monitoring function.
Most likely cause. The machine. Overtorque means binding or overload, and undercurrent or undertorque means something came loose or the load went away.
The fix, in order. Check the load side, then confirm the detection settings match the machine: F615 to F619 for overtorque, F610 to F612 for undercurrent, F651 to F654 for undertorque, and F590 to F598 for shock monitoring.
Worth knowing. F615, overtorque trip, ships at 0. These functions do nothing until somebody sets them up, and set up, they make the drive a condition monitor for the machine.
E and E-18, emergency off and analog loss
What it means. E is emergency off: STOP pressed twice when the run command comes from somewhere other than the panel, a terminal assigned to emergency off, or an emergency off from communication. E-18 is the II analog input falling to or below F633 for about 0.3 seconds.
The fix, in order. For E, clear the emergency off signal and reset. For E-18, check the signal wire to terminal II and the F633 setting.
Worth knowing. Pressing STOP once shows EOFF, and a second press applies emergency off, which is why a technician who taps STOP twice during a panel check gets an E trip. F603 sets how the motor stops on emergency off, from an immediate coast to a decel stop or DC braking first. This is a drive stop function. It is not a substitute for a properly engineered, safety rated emergency stop system, which on this drive means STO and the machine’s own safety circuit. F633 ships at 0, which disables analog loss detection. When it is set, F644, which ships at 4, decides whether the drive trips as E-18 or keeps going with the A-18 alarm, holding the last frequency, ramping, coasting, or running at the fallback frequency in F649.
PrA and PrF, safe torque off
What it means. The AS3 removes torque through two dedicated inputs, STOA and STOB. PrA is an alarm: STO is active because STOA and STOB are open to PLC. PrF is a trip: the two inputs are at different levels, or the STO circuit inside the drive has failed.
Most likely cause. For PrA, a real safety demand, the factory shorting bar removed, an overloaded 24 V supply on PLC or P24, or SW1 in its factory PLC position on an installation that expects an external supply and does not have one. For PrF, one channel opened without the other from wiring, a loose screw, a failed device, or an internal fault.
The fix, in order. For PrA, find which safety device opened, or on a machine that does not use STO, confirm the shorting bar across STOA, STOB, and PLC. Check the 24 V load and the SW1 position. For PrF, check the wiring and the screw tightening on STOA and STOB and the device feeding them, then call Toshiba if it persists.
Worth knowing. Toshiba says to drive STOA and STOB at the same level, both high or both low. When STO opens during a run, the motor coasts, and it will not restart when STO closes until the run command is turned off and on again. PrA also clears the run command no matter how F719 is set. The full detail is in Toshiba’s Safety Function Manual, E6582067. A channel mismatch is a different condition from both channels opening, and the drive keeps them separate. Jumpering a safety circuit to clear a code is not troubleshooting.
Err5, Err8 and E-43, communication time outs
What it means. Err5 is an RS485 time out, Err8 a communication option time out, and E-43 an embedded Ethernet time out. The alarm t, and A-43 for Ethernet, mean the drive is close to a time out but has not tripped yet.
The fix, in order. Check the communication equipment and wiring, then the settings against the master.
Worth knowing. Two settings decide what a lost master does, and both ship in the do nothing position. F803, the RS485 port 1 time out time, ships at 0.0, disabled. F804, the response, ships at 1, continue running. Setting F803 alone only teaches the drive to notice the loss and keep going. To make it stop, set F804 to 4, which trips at once and lets the motor coast, or to 6, which decelerates to a stop and then trips. Both trip as Err5. F808, which ships at 1, checks for the time out while the run or frequency command comes from communication. RS485 port 2 has the matching set F823, F824, and F828 with the same defaults. Test the loss of communication with the machine in a safe state.
Etn and Etn1 to Etn3, auto tuning errors
What it means. Auto tuning failed. Etn is the general error, and Etn1 to Etn3 narrow it.
Most likely cause. Motor parameters that do not match the motor, tuning while the motor was still rotating, no motor or something other than a motor on the output, or a rated speed in F417 set to the synchronous speed instead of the nameplate speed.
The fix, in order. Set vL, vLv, F405, F415, and F417 from the nameplate, make sure the motor is stopped and connected, and run the tune again.
E-31, rush current suppression relay fault
What it means. The relay that limits inrush at power up failed, or the drive was powered on and off too often.
The fix, in order. Start and stop the motor with the run command, not by switching the drive’s power. If it returns, it is an internal fault for Toshiba.
The internal faults
What it means. EEP1 to EEP3 are EEPROM faults. Err2, Err3, Err4, Err6, and Err7 are RAM, ROM, CPU, gate array, and current detector faults. E-19, E-21, and E-26 are CPU faults. E-22 is an embedded Ethernet hardware fault. EtyP is an inverter type error, which can follow a control board replacement.
The fix, in order. For EEP1 and EEP3, cycle power, and contact Toshiba if it returns. EEP2 can follow a power loss while tyP, default setting, was being applied, so set tyP again. After a board replacement, EtyP is cleared with tyP set to 6, initialize typeform. Everything else in this group is a fault in the drive and goes to Toshiba.
Worth knowing. E-99 is a trip for test, and E-44 means the operation panel battery is missing or low, which also makes the trip dates wrong. Neither is a drive fault.
The faults you prevent are the ones you never read
The VF-AS3 retains 8 detailed trip records.
Past trip 1 through 8 in monitor mode hold the last 8 trips, Past trip 1 being the latest. Pressing OK on one shows 13 items: the number of occurrences, output frequency, direction of rotation, frequency command, output current, DC input voltage, output voltage, the input terminal status, the output terminal status, cumulative operation time, the date, the time, and the internal temperature. These survive power off and reset. “nErr” means no trip is recorded. E-99, the test trip, is not recorded on CPU versions after 114.
The date and time let this drive tell you a trip happened at 2:14 on a Tuesday, which is enough to line it up against a shift change, a compressor start, or a utility event. The date depends on the panel’s battery. With the panel removed, or a flat battery, the date is recorded as 0 or wrong.
The terminal status pair records which inputs were on and which outputs the drive was driving at the trip, which settles whether the run command and the permissives were present.
The record is of values the drive detected. Toshiba notes they are not always the maximum, because detection takes time, so a fast transient may read lower than it really was.
Monitor mode also holds the parts replacement alarms for the cooling fan and capacitors, the cumulative run time, and the number of starts, which date the drive’s life before anything fails.
Reading and clearing faults
Remove the cause, then reset. Pressing STOP once shows CLr, and pressing it again resets, or turn a terminal assigned to reset on and then off. OCr resets only by cycling power.
F602, trip record retention, ships at 0, which clears the active trip when power goes off. Set to 1, the drive is still tripped after a power cycle and needs a deliberate reset, which keeps a power cycle from hiding a trip. The 8 trip history is kept either way.
Retry lives in F303, 0 to 10 attempts, and ships at 0. Only OC1 to OC3, OP1 to OP3, OL1 to OL3, OLr, OH, and SOUT are retried. The first retry comes about 1 second after the trip, the second about 2 seconds after, and so on up to about 10 seconds for the tenth. Overvoltage retries wait for the DC bus to fall, overheat retries wait for the drive to cool, and overload retries wait out a virtual cooling time. The panel shows “rtry” while it works. The failure signal on the FL relay does not operate during retry, so a drive retrying into a fault looks healthy from outside. If you want a failure signal during retry, assign output function 116 or 117, failure signal 4.
Toshiba is blunt about retry: stand clear of the motor and machine, because they will restart suddenly, and put caution labels on the drive, the motor, and the machine. Toshiba also says not to use retry or auto restart on cranes.
Where this fits
Most of what appears on this page was decided before the drive was first powered: the supply and its grounding, the motor cable length, the cabinet, the motor data somebody entered, and which trips somebody left enabled. The VFD Installation Guide and the VFD Troubleshooting Guide cover the work that keeps those decisions from showing up later as trips.
The same treatment for other platforms is in the ABB Drive Fault Field Guide, the PowerFlex 525 Fault Field Guide, the Yaskawa Fault Field Guide, the Invertek Optidrive E3 Fault Field Guide, the AutomationDirect GS20 Fault Field Guide, and the Fuji FRENIC-Ace Fault Field Guide, and every brand is listed on the guides page. For the competency behind the codes, that is what the VFD training does, and Before the First Fault is the field record the approach came out of.
Trip codes, parameter references, and behavior on this page are taken from the Toshiba VF-AS3 Instruction Manual E6582062 and the VF-AS3 RS485 Communication Function Manual E6582143. Several functions depend on the CPU version, so confirm against the manual revision and the CPU version of the drive in front of you. Toshiba and VF-AS3 are trademarks of Toshiba Corporation, used here for identification.
Frequently Asked Questions
Why does a Toshiba VF-AS3 show OP instead of OV for overvoltage?
Toshiba uses OP for its overvoltage trips. OP1 happened during acceleration, OP2 during deceleration, and OP3 at constant speed. OP2 is the common one, from a deceleration time too short for the regenerated energy.
Why did my VF-AS3 stop without a trip?
The most likely reason is undervoltage. F627, the undervoltage trip, ships disabled, so a power circuit undervoltage shows the MOFF alarm and stops the drive without tripping or operating the FL relay. Set F627 to 1 if you want it to trip as UP1.
What do PrA and PrF mean on a VF-AS3?
Both concern safe torque off. PrA is an alarm meaning STOA and STOB are open, so STO is active. PrF is a trip meaning the two inputs are at different levels or the STO circuit has failed. After STO opens during a run, the run command must be cycled before the motor will restart.
Does the VF-AS3 detect output phase loss?
Only if it is turned on. F605, output phase loss detection, ships at 0, disabled. Settings 1 to 4 check at the first start, at every start, during run, or both.
Why does my VF-AS3 keep running when the PLC stops communicating?
F803, the RS485 time out, ships at 0.0, disabled, and F804, the response, ships at 1, continue running. Set a time out in F803 and set F804 to 4 or 6 to trip, then test it with the machine in a safe state.
Where does the VF-AS3 store its trip history?
Monitor mode, Past trip 1 through 8. Press OK on a trip to see 13 items including output frequency, current, DC voltage, terminal status, internal temperature, and the date and time, which depend on the panel battery.