This page covers three Danfoss drives: the VLT Midi Drive FC 280 and the VLT AutomationDrive FC 301 and FC 302. Danfoss gives its warnings and alarms numbers instead of names, and many common alarm numbers mean the same thing across these three drives. Alarm 13 is overcurrent on an FC 280 and on an FC 302, and alarm 14 is a ground fault on both. What changes between the drives is how hard each alarm stops you. Some alarms are a plain trip you clear with the Reset key, and some are a trip lock that will not clear until the power has been off. The FC 280 and the FC 302 do not always agree on which is which, so the drive in front of you decides how you clear it.
Before you clear anything
Both drives keep an alarm log, so a reset does not erase the history. Write down the alarm number and what the machine was doing anyway.
Timing still narrows the field faster than a meter. A trip on acceleration points at ramp time, inertia, and current limit. A trip at steady speed points at load, cooling, and sizing. A trip on deceleration points at regeneration. A trip at power up points at wiring and the supply. On the FC 280, Danfoss adds a specific check for an overcurrent alarm at power up: make sure the supply cables were not landed on the motor terminals.
Disconnect the AC supply and any DC link supply, including battery back ups, UPS, and DC links to other drives, and stop or lock a PM motor. Then wait the discharge time. On the FC 280 that is 4 minutes for 200 to 240 V units from 0.37 to 3.7 kW and 380 to 480 V units from 0.37 to 7.5 kW, and 15 minutes for 380 to 480 V units from 11 to 22 kW. On the FC 301/302 it runs from 4 minutes on the smallest units to 15 minutes on larger ones, and the time is printed on the label on top of the drive. Measure to confirm the capacitors are discharged before you touch anything. Danfoss is explicit that the Off key does not disconnect the supply and is not a safety switch. Match PPE to the arc flash rating. Live measurements are for a qualified person, and retorquing terminals is done de-energized.
Warnings, alarms, and trip locks
Danfoss uses three levels.
A warning shows a yellow indicator and a number. Under some circumstances the drive can keep running, and it may act to reduce the condition. Warning 12, torque limit, means the drive has reached its torque limit, which can slow acceleration or pull speed down. The warning stays until the cause goes away, and some warnings become alarms if the condition worsens.
An alarm shows a flashing red indicator. The drive trips and the motor coasts. You clear it with the Reset key, a digital input set to reset, or a reset over serial communication or fieldbus. After a reset with the Reset key, the motor does not restart until you press Auto On.
A trip lock shows yellow and red together. Danfoss uses it for alarms where the cause could damage the drive or connected equipment. A trip lock clears only after the power has been removed long enough for the display to go blank. After power comes back, it becomes an ordinary alarm that you can reset once the cause is fixed.
Many alarms are marked in Danfoss’s tables as dependent on a parameter. Those can be set to warn, to trip, or to do nothing, so whether you ever see them depends on how the drive was set up. The FC 280 also shows its trip state on the display’s first line as Trip (auto restart), Trip (reset), or Trip lock (disc>mains), which tells you which kind of clearing it needs before you look anything up.
The FC 301/302 on software 10.00 goes a step further. Parameter 14-90 Fault Level lets the user set how a list of alarms responds: off, warning, trip, trip lock, or trip with a delayed reset. The list includes ground fault, short circuit, overcurrent, the temperature alarms, motor phase loss, locked rotor, current limit, and fieldbus fault. Danfoss notes that changing an alarm from trip lock to trip lets it reset automatically, and that Off ignores every warning and alarm from that source. If an FC 302 is not behaving the way the table says, read 14-90 before anything else.
The quick table
The codes you meet on a running machine. W is a warning, A an alarm, and TL a trip lock. “Par.” means the parameter in brackets decides whether it warns, trips, or does nothing.
| No. | Description | FC 280 | FC 301/302 |
|---|---|---|---|
| 1 | 10 volts low | W | |
| 2 | Live zero error | W, A (6-01) | W, A (6-01) |
| 3 | No motor | W | W (1-80) |
| 4 | Mains phase loss | W, A, TL (14-12) | W, A, TL (14-12) |
| 5, 6 | DC link voltage high, low | W | |
| 7 | DC overvoltage | W, A | W, A |
| 8 | DC undervoltage | W, A | W, A |
| 9 | Inverter overloaded | W, A | W, A |
| 10 | Motor ETR overtemperature | W, A (1-90) | W, A (1-90) |
| 11 | Motor thermistor overtemperature | W, A (1-90) | W, A (1-90) |
| 12 | Torque limit | W, A | W, A |
| 13 | Overcurrent | W, A, TL | W, A, TL |
| 14 | Ground fault | A, TL | A (14-90) |
| 16 | Short circuit | A, TL | A, TL |
| 17 | Control word timeout | W, A (8-04) | W, A (8-04) |
| 25 | Brake resistor short circuit | A, TL | W |
| 26 | Brake resistor power limit | W, A | W, A (2-13) |
| 27 | Brake chopper short circuit | A, TL | W, A |
| 28 | Brake check | A | W, A (2-15) |
| 29 | Heat sink temperature | A, TL (14-90) | |
| 30, 31, 32 | Motor phase U, V, W missing | A, TL | W, A, TL (4-58) |
| 33 | Inrush fault | A, TL | |
| 34 | Fieldbus fault | W, A | W (14-90) |
| 36 | Mains failure | W, A (14-10) | W, A (14-10) |
| 38 | Internal fault | A, TL | A, TL |
| 46 | Gate drive voltage fault (FC 280), power card supply (FC 301/302) | A, TL | A, TL |
| 47 | 24 V supply low | W, A, TL | W, A, TL |
| 50 to 58 | AMA errors | A | A |
| 59 | Current limit | W, A | W, A |
| 60 | External interlock | A | W, A |
| 61 | Encoder loss (FC 280), feedback error (FC 301/302) | W, A | W, A (4-30) |
| 63 | Mechanical brake low | A | A (2-20) |
| 65 | Control card temperature | W, A, TL | A, TL (14-90) |
| 68 | Safe Torque Off | W, A (5-19) | W, A (5-19) |
| 69 | Power card temperature | W, A, TL | A, TL (14-90) |
| 80 | Drive initialized to default | A | A |
| 99 | Locked rotor | A | A, TL |
| 188 | STO internal fault | A |
Some codes appear on one drive only and come up in the field. On the FC 280, 95 is broken belt, 126 is a PM motor rotating during AMA, and 127 is PM back EMF too high before starting. On the FC 301/302, 22 is the hoist mechanical brake, 71 and 72 come from the MCB 112 PTC thermistor card acting through STO, and 122 is a motor rotating unexpectedly when the drive needed it stopped. Err. on either drive means a wrong password was entered for a protected parameter, which is not a fault at all.
The most common Danfoss call has no alarm at all: the drive is healthy and the motor will not turn. Before chasing a fault, check four things. Terminal 27 is coast inverse from the factory, so without 24 V on it, or 5-12 changed, the display shows Coast, and alarm 60 appears if 27 was set as an external interlock. The STO jumper from terminal 12 to 37, and to 38 on the FC 280, must be in until real STO wiring replaces it. Terminal starts are ignored until the drive is in Auto On, and Standby on the status line means it is waiting for a start. On an FC 302 with software 10.00, a Smart Setup screen opens at first power up and after a factory reset, and the drive ignores start commands until you finish it or back out.
When the manuals disagree
Danfoss manuals are written for a software version, and the drive in front of you may not run the version the manual describes. Four things cause most of the disagreements you will find.
Editions cover different software. For the FC 280, the operating guide dates from 2018 and covers software 1.5, the programming guide from 2019 and covers software 1.6, and the installation guide from 2022. No newer FC 280 programming guide is published, so nothing on paper describes the software a new FC 280 ships with today. For the FC 301/302, the programming guide was reissued in February 2026 for software 10.00, replacing the 2019 edition for software 8.43.
Alarm behavior changed between editions. Comparing the two FC 301/302 programming guides, five codes changed:
| Alarm | 2019 guide, software 8.43 | 2026 guide, software 10.00 |
|---|---|---|
| 14 Ground fault | Warning, then alarm | Alarm, trip by default, can be set to trip lock |
| 29 Heat sink temperature | Warning, alarm, trip lock | Alarm, trip lock |
| 34 Fieldbus fault | Warning, alarm | Warning |
| 59 Current limit | Warning | Warning, alarm |
| 65 Control card temperature | Warning, alarm, trip lock | Alarm, trip lock |
Software 10.00 also added 14-90 Fault Level, which lets the user change how many alarms respond. Two FC 302s side by side can clear the same alarm differently because of their software, or because someone changed 14-90.
Some manuals disagree with themselves. The FC 280 troubleshooting text tells you to check an input switch for the thermistor, while its parameter list sets the input mode in 6-19 and 6-29. The FC 280 AMA description says to press Hand On, while its step lists leave that out. The 2026 FC 301/302 guide lists alarm 9 as a warning and alarm in its code list, but shows trip lock as the only setting in its 14-90 table. The 2019 FC 301/302 design guide says the FC 301 runs PM motors, while the 2026 programming guide says it does not.
Defaults depend on where and when the drive was bought. The region a drive was ordered for and the software it shipped with both change its defaults. A default quoted in any manual, or on this page, is a starting point, not a promise.
The way through is the same every time. Read 15-43 Software Version, use the guide that matches it, read the parameter on the drive itself, and trust what the drive shows over any table, including the one above.
The fault details
13, overcurrent
What it means. Output current passed the inverter’s peak current limit, about 200 percent of rated current. The warning comes first and lasts about 5 seconds on the FC 280 and about 1.5 seconds on the FC 301/302, then the drive trips. It is a trip lock on both.
Most likely cause. Danfoss names shock loading and fast acceleration of a high inertia load. On the FC 302, a fast ramp after kinetic back up can also cause it.
The fix, in order. Remove power and check that the motor shaft turns, which is Danfoss’s first step. Check that the motor size matches the drive. Check the motor data in parameters 1-20 to 1-25. Then lock out, wait the discharge time, disconnect the motor, and megger the cable and motor phase to ground, never through the drive. Use 500 V DC on a motor rated under 240 V and 1000 V DC on a 380 to 500 V motor. On 525 to 690 V motors, use the test voltage the motor manufacturer gives. Under 1 megohm is a fail, 1 to 10 megohms means investigate, usually moisture or tired insulation, and over 10 megohms is generally healthy. The IEEE 43 minimum for a random wound motor is 5 megohms corrected to 40 C, which sits inside that investigate band, and why the 4.4 megohm number is wrong covers how to correct a cold reading. The 3 readings should sit within about 50 percent of each other, and a falling trend against earlier readings on the same motor says more than any single number. On the FC 280, if the trip comes at power up, check that the supply cables are not on the motor terminals.
Worth knowing. On FC 301/302 software 10.00, the drive’s hardware forces a 3 minute recovery after 2 overcurrent trips close together, and no setting overrides it. A plant that watches the overcurrent warning bit in the warning word, parameter 16-92, can see the trip coming. Treat that as a diagnostic clue, not a protective interval: a hard short or a severe shock load can trip the drive with little or no warning at all.
14, ground fault, and 16, short circuit
What it means. Alarm 14 means current is flowing from an output phase to ground, in the motor cable or the motor. The FC 301/302 finds it by comparing the current going out to the motor with the current coming back, and trips when the difference is too large. Alarm 16 means a short in the motor or its wiring.
Most likely cause. Damaged cable insulation, moisture in the motor terminal box, or a failing winding.
The fix, in order. Remove power and repair the fault. Danfoss’s check is to measure the resistance to ground of the motor cables and the motor with a megohmmeter, using the test voltage and bands given under alarm 13 above.
Worth knowing. This is where the two drives differ most. On the FC 280, alarm 14 is a trip lock, so it needs a power cycle before it will reset. On the FC 301/302, alarm 14 is an ordinary trip by default, though on software 10.00 it can be changed to a trip lock in 14-90. The 2019 guide also showed a warning stage for it, which the 2026 code list does not. On the FC 302, Danfoss adds a step most people never try: if the power card was changed, the three current transducers can carry an offset that reads as a ground fault, and a manual initialization or a complete AMA resets it. Alarm 16 is a trip lock on both.
7 and 8, DC overvoltage and undervoltage, with warnings 5 and 6
What it means. Alarm 7 means the DC link went over its limit and the drive tripped after a delay. Alarm 8 means it fell below the undervoltage limit. On the FC 301/302, warnings 5 and 6 come first as the bus approaches either limit, and the unit keeps running.
Most likely cause. Alarm 7 is regeneration on a ramp too short for the load. Alarm 8 is a supply too low or too weak for the drive, or a soft charge problem.
The fix, in order. For alarm 7, extend the ramp time and change the ramp type, which is the FC 280’s whole list. The FC 302 adds a brake resistor, the functions in parameter 2-10 Brake Function, a longer delay in 14-26 Trip Delay at Inverter Fault, and kinetic back up in 14-10 if the trip comes during a sag. For alarm 8, check that the supply matches the drive’s voltage, then test the input voltage and the soft charge circuit.
Worth knowing. The FC 301/302 manual publishes its limits. On a 3 x 200 to 240 V drive, alarm 8 is at 185 V DC, warning 6 at 205 V DC, warning 5 at 390 V DC without a brake or 405 V DC with one, and alarm 7 at 410 V DC. On a 3 x 380 to 500 V drive, the same five are 373, 410, 810, 840, and 855 V DC. On a 3 x 525 to 600 V drive, they are 532, 585, 943, 965, and 975 V DC. All carry a tolerance of plus or minus 5 percent. Divide the DC value by 1.35 to get the matching mains voltage. If the FC 301/302 has a 24 V DC back up supply connected, it checks for it before tripping on alarm 8.
4, mains phase loss, and 36, mains failure
What it means. Alarm 4 means a supply phase is missing or the voltage imbalance is too high, and it also appears for a fault in the input rectifier. Alarm 36 means the supply was lost, and it appears only when 14-10 Mains Failure is set to something other than [0] No function.
Most likely cause. A blown fuse, a loose line terminal, a failed contactor pole, or utility imbalance.
The fix, in order. Check the supply voltage and the supply currents to the drive. For alarm 36, check the fuses and the supply.
Worth knowing. 14-12, the response to mains imbalance, ships at [0] Trip on the FC 280. Danfoss warns that running under severe imbalance shortens motor life, so changing it to warning or disabled has a cost. Alarm 4 can be a trip lock, so check how the drive is reporting it before you start resetting. Danfoss also notes that mains distortion can cause alarms 4, 7, and 8 on the FC 280, and that a line filter may fix it.
9, inverter overload
What it means. The drive ran above 100 percent of its rating for too long and its electronic thermal protection is about to trip it, or has. On the FC 301/302 the warning comes at 98 percent, the trip at 100 percent, and the drive cannot be reset until the counter is below 90 percent. The FC 280 warns at 90 percent and trips at 100 percent.
Most likely cause. A drive too small for the duty, an aggressive ramp, or a load that grew.
The fix, in order. Compare the output current on the LCP with the drive’s rated current, then compare it with the motor current you measure. Watch the thermal drive load on the LCP. It climbs when the drive runs above its continuous rating and falls when it runs below.
10 and 11, motor overtemperature
What it means. Alarm 10 means the electronic thermal model, ETR, says the motor is too hot. Alarm 11 means a motor thermistor says so, or its wiring is open. Parameter 1-90 Motor Thermal Protection decides whether either one warns, trips, or does nothing.
Most likely cause. A real overload, wrong motor data, a blocked motor fan, or a thermistor wired to the wrong input.
The fix, in order. Check the motor and the load. Confirm 1-24 Motor Current and the rest of 1-20 to 1-25 match the nameplate, and run AMA in 1-29, which Danfoss says tunes the drive to the motor and reduces thermal loading. On the FC 302, if the motor has an external fan, select it in 1-91. For alarm 11, check that the thermistor is wired between terminal 53 or 54 and terminal 50, with that input set for voltage, or between a PNP digital input and terminal 50, and that 1-93 selects the terminal actually used. The FC 301/302 sets voltage or current with a switch on the control card. The FC 280 sets it in a parameter, 6-19 for terminal 53 and 6-29 for terminal 54, even though its own troubleshooting text mentions a switch.
Worth knowing. On the FC 280, the programming guide parameter list gives 1-90 a default of [0] No protection. The default on a given drive depends on where and when it was bought, so read 1-90 rather than assume either way. An FC 280 left at No protection has no electronic motor overload protection at all, and Danfoss describes that setting as for a motor that is continuously overloaded when no warning or trip is required, and the 2022 FC 280 installation guide states plainly that motor overload protection is not active by default. Set 1-90 to [4] ETR trip 1, or to a thermistor setting if a thermistor is wired. The FC 302 manual notes that for the North American market the ETR functions provide class 20 motor overload protection in accordance with the NEC, which only applies once ETR is selected. 1-90 is set separately in each set-up, so check it in every set-up the machine uses, not just the active one. Check 1-90 on every Danfoss drive you commission.
12, torque limit, and 59, current limit
What it means. Warning 12 means torque passed 4-16 Torque Limit Motor Mode or 4-17 Torque Limit Generator Mode. Warning 59 means current passed 4-18 Current Limit. Both are warnings first. 14-25 Trip Delay at Torque Limit can turn torque limit into a warning followed by an alarm.
The fix, in order. If the motor torque limit is hit during ramp up, extend the ramp up time. If the generator torque limit is hit during ramp down, extend the ramp down time. If it happens while running, increase the limit, but only after making sure the system can run safely at the higher torque. For current limit, check the motor data first.
Worth knowing. While warning 12 is active the drive is at its torque limit, so acceleration can stretch out or speed can sag under load. A machine that runs slow with warning 12 on the display is usually the drive holding its limit, not a speed control fault.
30, 31 and 32, motor phase missing
What it means. Motor phase U, V, or W is missing between the drive and the motor.
Most likely cause. A loose or broken motor lead, an open winding, or a failed contactor pole on the output.
The fix, in order. With the drive de-energized, check the leads and terminations on the phase named, then the motor.
Worth knowing. On the FC 280, 4-58 Missing Motor Phase Function ships at [1] On, and alarms 30 to 32 are trip locks. On the FC 301/302, 4-58 offers several detection modes: [1] Trip 100 ms, recommended above 10 Hz, [2] Trip 1000 ms, recommended between 1 and 10 Hz, and a 3 phase detection mode for very low current applications such as lowering a lift, which needs flux closed loop on the FC 302. Danfoss also notes that missing phase detection is not active with 1-10 Motor Construction set to PM non salient SPM on the FC 301/302.
17, control word timeout
What it means. The drive stopped getting control words from serial communication or the fieldbus within the time in 8-03 Control Word Timeout Time, which defaults to 1 second.
Most likely cause. A broken or loose communication cable, a master that stopped sending, or noise.
The fix, in order. Check the communication cable connections, increase 8-03 if the network is just slow, check the communication equipment, and verify the EMC installation.
Worth knowing. 8-04 decides what happens. On the FC 280 it ships at [0] Off, and the warning and alarm only exist when 8-04 is not Off. An FC 280 at the default will keep running at its last command if the master stops sending. The choices are freeze output, stop, jog, run at maximum speed, or stop and trip. Set to [5] Stop and trip, the drive shows the warning, ramps down, and then shows alarm 17. On the FC 301/302 the default depends on the unit, so read it. Choose the response with the machine in mind, and test the loss of communication with the machine in a safe state.
2, live zero error
What it means. An analog input dropped below 50 percent of the minimum programmed for it, for the time in 6-00 Live Zero Timeout Time. It only appears if 6-01 Live Zero Timeout Function is set.
Most likely cause. A broken wire or a failed transmitter.
The fix, in order. Check the analog input connections: terminals 53 and 54 for signals and 55 common on the control card, plus the option terminals on an FC 302 with I/O options. Check that the input is set for the signal type, and run an input terminal signal test. On the FC 301/302 that means the input switches, set with the power off. On the FC 280 only terminal 54 takes current, and only with 6-29 Terminal 54 Mode at [0] Current mode, which ships at voltage mode.
Worth knowing. 6-01 ships at [0] Off on both drives, so a lost 4 to 20 mA signal produces no alarm at all until somebody sets it. Setting 6-01 is not always enough. The input’s low current setting must be above 2 mA for live zero detection to work: 6-12 for terminal 53 and 6-22 for terminal 54 on the FC 301/302, where 6-12 defaults to 0.14 mA. The FC 280 6-22 defaults to 4 mA. After setting it, pull the signal with the machine in a safe state and confirm the drive does what you chose. When set, the choices are freeze output, stop, jog, run at maximum speed, or stop and trip. Maximum speed on a lost signal is a deliberate choice for a few applications and a hazard on most.
25 to 28, the brake circuit
What it means. Alarm 25 is a short circuited brake resistor, 26 is the brake resistor power limit, 27 is a short circuited brake transistor, and 28 is a failed brake check, meaning the resistor is missing or not working.
Most likely cause. For 26, braking too often or too hard. For 25, 27, and 28, a failed resistor, a failed transistor, or a wiring problem.
The fix, in order. For 26, reduce the braking energy with a lower speed or a longer ramp. For 25 and 27, remove power and check, or remove, the brake resistor. For 28, check 2-15 Brake Check on the FC 302.
Worth knowing. The two drives handle a shorted brake differently. On the FC 280, alarms 25 and 27 are trip locks, and the FC 280 checks the resistor at start up. On the FC 301/302, alarm 25 is a warning: the brake function is disabled and the drive keeps running without it. With a shorted brake transistor on the FC 302, Danfoss warns that substantial power goes into the resistor even when braking is off, so remove power and disconnect the resistor. The brake power limit is calculated, not measured, as an average over the last 120 seconds based on the DC link voltage and the resistor value you entered. On the FC 280 the drive trips if warning 26 lasts 1200 seconds.
29, 65 and 69, temperature
What it means. Alarm 29 is the heat sink over its maximum, on the FC 301/302. Alarm 65 is the control card over temperature, with a cutout at 85 degrees C on the FC 302. Alarm 69 is the power card temperature sensor reading too hot or too cold.
Most likely cause. A high ambient, blocked airflow, a dirty heat sink, a failed fan, or too little clearance above and below the drive. Danfoss adds long motor cables to the list for alarm 29.
The fix, in order. Measure the air at the drive intake with the panel closed. Check the clearances, the fan, and any filters, and clean the heat sink.
Worth knowing. Alarm 29 does not reset until the heat sink drops below a reset point that depends on the power size, and alarms 29, 65, and 69 can be trip locks, so the drive may need to cool and be power cycled. On the FC 301/302 software 10.00 guide, 29 and 65 default to trip lock and can be changed to trip in 14-90, and alarm 69 is only a warning on small and medium power drives.
68 and 188, safe torque off
What it means. Alarm 68 means STO has been activated. The FC 280 has two STO inputs, terminals 37 and 38. The FC 301/302 programming guide describes STO on terminal 37. Alarm 188 on the FC 280 means 24 V DC reached only one of the two terminals, or the drive found a failure in the STO channels. Code 68 can show as a warning or an alarm, and 5-19 decides which. At [1] Safe Torque Off Alarm, the default on the FC 280, it is alarm 68 and needs a reset. At [3] Safe Torque Off Warning it is warning 68, and the drive will restart on its own when the STO inputs return. Know which one you are looking at before anyone stands near the machine.
Most likely cause. For 68, a real safety demand: an e stop, a gate, or a safety relay that dropped out. For 188, one channel opened without the other, from wiring, a failed contact, or an internal fault.
The fix, in order. For 68, find which safety device opened. To resume, apply 24 V DC to the STO terminals again and send a reset from the fieldbus, a digital input, or the Reset key. On an FC 302, if alarm 68 appears at start up, Danfoss says to check that the 4 pole fused disconnect is closed, and mains power must be present to clear it. For 188, make sure both terminals are powered and that the two signals switch within 12 ms of each other, then contact Danfoss if it persists.
Worth knowing. On the FC 280, the two STO signals must stay low together for at least 80 ms to activate STO, must be high together for at least 20 ms to release it, and must not disagree for longer than 12 ms. 5-19 Terminal 37/38 Safe Torque Off ships at [1] Safe Torque Off Alarm, which coasts the motor and needs a manual reset. Setting [3] Safe Torque Off Warning lets the drive restart on its own when STO releases. Automatic reset in 14-20 does not clear alarm 68 or 188 on FC 280 software 1.2 and later, and on the FC 301/302 it clears STO only on firmware 4.3x or earlier. On the FC 302, warning 73 tells you STO is set to restart automatically, so the motor can start when the cause clears. The FC 280 STO is rated SIL 2 and EN ISO 13849-1 Category 3 PL d. A channel discrepancy is a different condition from both channels opening, and the drive keeps them separate. If STO opens while the FC 280 already shows warning or alarm 8, DC undervoltage, the drive skips alarm 68, though STO still works, so a missing 68 after a power dip does not mean the safety circuit failed to open. Jumpering a safety circuit to clear a code is not troubleshooting.
38, internal fault, and 46 and 47, supplies
What it means. Alarm 38 is an internal fault with a code number that says more. Alarm 46 is a gate drive voltage fault on the FC 280 and a power card supply fault on the FC 301/302. Warning or alarm 47 means the 24 V supply is low.
The fix, in order. For 38, cycle power, check that options are properly installed, and check for loose or missing wiring. Then read the code: 15-31 on both drives holds the extra detail. On the FC 302, codes 256 to 258 mean the power EEPROM data is defective or too old and the power card needs replacing, and codes 1299 to 1318 mean option software is too old or not supported in a named slot. For 46 on the FC 302, Danfoss lists the power card, the control card, an option card, a 24 V DC back up supply, and a failed heat sink fan as suspects. For 47, check the load on the 24 V supply, since it may be overloaded.
50 to 58, AMA errors, and 80, drive initialized
What it means. Alarms 50 to 58 mean the automatic motor adaptation failed, and the number says why: a calibration error, wrong motor voltage or current settings, current too low, a motor too big or too small for AMA, motor parameters out of range, AMA interrupted, a time out, or an internal fault. Alarm 80 means the parameters were reset to default.
The fix, in order. For the AMA alarms, correct the motor data from the nameplate and run AMA again. Repeated retries after a time out heat the motor, so let it cool. If the motor is much smaller than the drive, the FC 301/302 guide is plain about the limit: AMA works on a motor one size down, typically on two, rarely on three, and never on four. On a small motor, Reduced AMA or U/f with good nameplate data is the way through. For alarm 80, reset the unit and reload the saved parameters.
Worth knowing. On the FC 280, an initialization through 14-22 Operation Mode keeps the fault log and alarm log, along with operating hours and serial communication settings. A manual initialization at power up erases them, so read the alarm log first if you are about to reset a drive to defaults. The FC 280 can hold a parameter backup on its memory module, which makes recovering from alarm 80 a matter of minutes rather than a reprogram. The FC 301/302 can do the same with the LCP copy function or the MCT 10 software.
The faults you prevent are the ones you never read
Both drives keep a fault log, and it is often overlooked.
The Alarm Log key on the LCP shows different amounts on the two drives. On the FC 280 it shows current warnings, the last 10 alarms, and the maintenance log. On the FC 301/302 it shows the 5 latest alarms, numbered A1 to A5, with details of the drive’s condition when each one tripped.
Parameter group 15-3* holds the same history as parameters a PLC can read. 15-30 is the error code, the alarm number, and 15-31 is extra detail, used mostly with alarm 38. On the FC 301/302, 15-32 gives the time of each logged alarm in seconds from drive start, and 15-33 gives a date and time, which is only useful if the drive’s clock was set. These are 10 entry arrays, 0 being the most recent and 9 the oldest, so the FC 301/302 parameter log reaches back further than its keypad display.
The alarm, warning, and extended status words, 16-90 to 16-97, carry every active alarm and warning as a bit. A PLC that reads these instead of a single fault bit knows that warning 13 is active before the overcurrent trip arrives, or that the inverter overload counter is climbing. Danfoss built them for exactly that use.
On the FC 301/302, 8-17 makes a configurable alarm and warning word whose 16 bits can each be set to any of a long list of warnings, so you can send just the ones that matter to the PLC in one word.
Reading and clearing faults
Fix the cause, then reset with the Reset key, a digital input set to reset, or a reset over serial communication or fieldbus. After a manual reset with the Reset key, press Auto On to restart the motor. A trip lock clears only after the power has been off long enough for the display to go blank.
Automatic reset lives in 14-20 Reset Mode, which ships at [0] Manual reset on both drives. Settings 1 to 12 give 1 to 20 automatic resets, 13 is infinite, and 14 resets at power up. 14-21 sets the time from trip to reset, 10 seconds by default on the FC 280. Trip locks are never cleared by automatic reset. On the FC 301/302, if the set number of automatic resets is used up within 10 minutes, the drive drops back to manual reset until somebody resets it by hand.
Danfoss puts a warning about unintended start right on 14-20: the motor can start without warning. A drive that resets itself is attached to a machine that starts itself, so enable automatic reset only where an unattended restart is safe.
Where this fits
Most of what appears on this page was decided before the drive was first powered: the supply, the motor cable, the cabinet, the motor data somebody entered, and settings like 1-90, 6-01, and 8-04 that decide whether the drive protects anything at all. The VFD Installation Guide and the VFD Troubleshooting Guide cover the work that keeps those decisions from showing up later as alarms.
The same treatment for other platforms is in the ABB Drive Fault Field Guide, the PowerFlex 525 Fault Field Guide, the Yaskawa Fault Field Guide, the Invertek Optidrive E3 Fault Field Guide, the AutomationDirect GS20 Fault Field Guide, the Fuji FRENIC-Ace Fault Field Guide, and the Toshiba VF-AS3 Fault Field Guide, and every brand is listed on the guides page. For the competency behind the codes, that is what the VFD training does, and Before the First Fault is the field record the approach came out of.
Warning and alarm codes, parameter references, and behavior on this page are taken from the Danfoss VLT Midi Drive FC 280 Programming Guide MG07C402, Operating Guide MG07A502, and Installation Guide AN41533976851002, and the Danfoss VLT AutomationDrive FC 301/302 Programming Guides AU275636650261 (software 10.00) and M0013101 (software 8.43). Defaults and behavior vary with the region and date of purchase, the software version, and on the FC 301/302 the control card generation, so confirm against the guide that matches the drive in front of you. Danfoss and VLT are trademarks of Danfoss A/S, used here for identification.
Frequently Asked Questions
What is the difference between an alarm and a trip lock on a Danfoss VLT?
An alarm trips the drive and clears with the Reset key, a digital input, or a fieldbus reset once the cause is fixed. A trip lock is used where the cause could damage the drive or connected equipment, shows yellow and red together, and clears only after the power has been removed long enough for the display to go blank.
Why won't my Danfoss FC 280 reset after a ground fault?
On the FC 280, alarm 14, ground fault, is a trip lock. Remove power until the display goes blank, fix the ground fault, then power up and reset. On the FC 301/302, alarm 14 is an ordinary trip by default.
Does the Danfoss FC 280 protect the motor from overload out of the box?
The FC 280 programming guide gives parameter 1-90 Motor Thermal Protection a default of No protection, though the default depends on where and when the drive was bought. Read 1-90 on every FC 280 you commission rather than assume, and set it to ETR trip 1, or to a thermistor setting if a thermistor is wired.
What is alarm 188 on a Danfoss FC 280?
STO internal fault. 24 V DC reached only one of the two STO terminals, 37 and 38, or the drive found a failure in an STO channel. Both terminals must be powered and the two signals must switch within 12 ms of each other.
Why does my Danfoss drive keep running when the PLC stops communicating?
Parameter 8-04 Control Word Timeout Function decides, and on the FC 280 it ships at Off. Set it to Stop or Stop and trip, set the time in 8-03, and test the loss of communication with the machine in a safe state.
Why does my Danfoss manual disagree with my drive?
Danfoss writes each manual for a software version. The FC 280 guides date from 2018 to 2022, and the FC 301/302 programming guide changed several alarms between its 2019 and 2026 editions. Defaults also depend on where and when the drive was bought. Read 15-43 Software Version, use the guide that matches it, and trust the parameter values on the drive.
Where does a Danfoss VLT store its fault history?
The Alarm Log key shows the last 10 alarms on the FC 280 and the last 5 on the FC 301/302. Both drives keep 10 entries in parameters 15-30 and 15-31, with times in 15-32 on the FC 301/302, and the live alarm and warning words are in 16-90 to 16-97 for a PLC to read.
Online start-up courses, filmed on real drives
One drive per course, filmed uncut with a clock on screen from first power to a saved backup. The install course is free, and the ABB ACS380 and ACS580 start-up course is open now.